American Power Conversion MX28B4800, MX28B2400 manual Vdc, Rectifiers

Page 66

8.2.DC Output (with either 1MRF28H54BV Rectifiers and 1MRF28H54BV50 Rectifiers)

Nominal Output Voltage (factory set)

54.5

VDC

 

 

 

Operating Voltage Range

44 –

58 VDC

 

 

Rated Output Current (per Rectifier)

50 A

 

 

Rated Output Power (per Rectifier)

2800 W (45ºC)

 

 

Efficiency

91% Typical

 

 

 

8.3. Controls and Indicators

Rectifiers

Input Healthy LED

AC power present.

 

 

Output Healthy LED

DC output voltage within operating range (-39.5 to –59.5 VDC).

 

 

Output Current LED

On when rectifier is supplying current.

 

 

Thermal Control LED

On when one of three internal sensors is above 90ºC

 

 

Current Limit LED

On when rectifier is in current limit.

 

 

Overvolts LED

On when rectifier is above 57 Volts. (Must be powered down to reset)

 

 

Overtemp LED

On when one of three internal sensors is above 130ºC. Power

 

Conversion is inhibited.

 

 

Fan fail LED

On when Fan is running too slow.

 

 

Standby LED

On when the unit is in the standby mode. No output power is

 

produced. Rectifier is still active

 

 

+V Test Point

Rectifier Voltage can be measured with a voltmeter between COM

 

and +V.

 

 

COM Test Point

Negative reference for both +V and +I

 

 

+I Test Point

Rectifier Current can be measured with a voltmeter between COM

 

and +I.

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 61

Image 66
Contents VDC Power Systems Table of Contents Commissioning and Preventive Maintenance APC Worldwide Customer Support Limited Product Warranty Revision History Revision Date DescriptionSafety First General PrecautionsHow to Use This Manual IntroductionGeneral Information 1 MX28B-1200 -48 VDC Power Plant Rectifier Bay 2 MX28B Block Diagram Unpacking Equipment InstallationMechanical Installation Room / LocationPower Bus Connections Mounting2 MX28B-1200-2400 has a maximum Circuit Breaker/LVD Ribbon Cable Connections 5 Circuit Breaker / LVD Expansion BoardAC Power Connections Fuse Alarm Ribbon Cable ConnectionsVentilation 1 AC Input Wiring Battery Connections Planning the Battery InstallationConnecting the Battery Cables 1 Battery Cable Connection Locations2 Battery Probe Connection DC System GroundingDC Power Output Over-Current Protection DC Plug-in Circuit BreakersBreaker Part Number Rating 2 Plug-in Circuit Breakers DC Bolt-in Circuit Breakers 4 Bolt-in Circuit BreakersTelecom Fuses 5 Telecom FusesInstallation of Circuit Breakers and Fuses Plug-in Circuit Breaker InstallationBolt-in Circuit Breaker Installation 2 Circuit Breaker Alarm WiringTelecom Fuse Installation GMT Fuse InstallationCircuit Breaker Connections 1 to 50 Amps Load ConnectionsCable Size Considerations Circuit Breaker Connections 60-100 AmpsFront Panel DB9 Connection Monitoring and Relay Output ConnectionsGMT Fuse Connections Smart Cable DB9 ConnectionRJ45 Ethernet Connector Relay Output ConnectionsExternal Alarm Input Connections NO-NC-CRectifier Module Installation Battery Visual and Safety Inspection Commissioning and Preventive MaintenanceElectrical Installation Pre-Commissioning InspectionAC Power Up CommissioningInitial Set-up Rectifier Test DC Power UpBattery Power Up LVD TestUser Inputs Battery Temperature CompensationCircuit Breaker/ Fuse Test Output RelaysFinal Inspection Operation Technical DescriptionRectifier Management System Voltage Control System ManagementSystem Output Capacity System CurrentBattery Charging and Protection Battery ManagementSystem Status and Alarm Reporting DC DistributionControls and Indicators Battery/Load Low Voltage DisconnectFront Panel User Interface Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default ValuesAddress Alarm ItemNo Alarms Switzer70.0 C Batt HT AlmBatt HT Thr Batt HV AlmCir Bkr 72 Almm+ Cir Bkr 1 Alm m+Major Comp HkneeHw Batt C Almm+ Fuse 1 AlmFuse 16 Alm Minor48.00 LVD ResetLVD Option LVD TripOut-Rly 6 Dly m+ Out-Rly 1 Dly m+Sec Relay MajorMRF28H54 DisableRect 1 Desc Rect 1ofN Almm+Sys LT Alm Sys HV AlmSys HV Thr Sys LT ThrTime 90025SYS MS System Module SET-ALM Setup DA Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin Modrec AM Info Modfuse LM Alias Fuse MOD Modlvd Modlvd LM Param Alarm Outputs Output Relays Front Panel LED IndicatorsSection External Alarm Inputs Input Relays Description Command and Monitoring ProtocolRemote Monitoring Physical ConnectionsEquipment Preventive MaintenanceSystem Visual and Safety Inspection InspectionTest System Voltage TestRectifier Current Test Battery Current Test Rectifier Alarm TestSystem Temperature Test Rectifier Current Share TestBattery Temperature Test Battery Preventive Maintenance ProcedureFinal Inspection 1MRF28H54BV Rectifiers SpecificationsAC Input 1MRF28H54BV50 RectifiersVDC RectifiersPower Shelf Control Unit Mechanical EnvironmentalCompliance Toll Free APC Worldwide Customer SupportUS and Canada WorldwideLimited Product Warranty