PARAMETER NAME/ | DESCRIPTION | DISPLAY SCREENS / | ||
[MENU LOCATION] |
| DEFAULT SETTINGS | ||
|
|
| ||
Output Relay 1 Delay | Delay between sensing of the alarm condition and |
| ||
Security Level {1} | activation of Output Relay 1. An alarm condition | 0 sec | ||
must exist for longer than the delay to be |
|
| ||
MAP] | activated. | • |
| |
• | • |
| ||
• |
| |||
• | • |
| ||
• | • | • |
| |
Output Relay 6 Delay | Delay between sensing of the alarm condition and |
| ||
Security Level {1} | activation of Output Relay 6. An alarm condition | 0 sec | ||
must exist for longer than the delay to be | ||||
|
| |||
MAP] | activated. |
|
| |
Output Relay Major Alias | An alternate name (alias) can be assigned to the | Relay Major | m+ | |
Security Level {1} | major Relay if desired. | Major |
| |
|
|
| ||
Output Relay Minor Alias | An alternate name (alias) can be assigned to the | Relay Minor | m+ | |
Security Level {1} | Minor Relay if desired. | Minor |
| |
|
|
| ||
PIN 1 change | Permanently change password (PIN) that permits | PIN | m+ | |
Security Level {2} | security Level 1 parameter changes - limited | 1111 | ||
[SYSTEM/SETUP] | access. |
|
| |
PIN 2 Change | Permanently change password (PIN) that permits | PIN 2 | m+ | |
Security Level {2} | security Level 2 parameter changes - unlimited | 2222 | ||
[SYSTEM/SETUP] | access. |
|
| |
PIN Entry | Screen for entry of the active password (PIN). | PIN | m+ | |
Security Level {0} | Before any changes can be made, the correct pin | 0000 | ||
[PIN] | for the desires security level must be entered. |
|
| |
| Level 0 – full read access. Level 1 |
|
| |
| limited write access. Level 2 – full read and write |
|
| |
| access. |
|
| |
Rectifier Communications Fail | The maximum rectifier communications response | RectFailComm | m+ | |
Timeout | time allowed before a communications failure is | 1 min | ||
Security Level {1} | declared. |
|
| |
[MODULES/RECT/PARAM] |
|
|
| |
Rectifier Configuration Alarm | The output relay energized if the rectifier | Rect Cfg Alm | m+ | |
Security Level {1} | configuration differs from its stored configuration. | Minor |
| |
This occurs if a rectifier is added after |
|
| ||
| configuration. |
|
| |
Rectifier Current Limit Alarm | The output relay that is energized or special | Rect CL Alm | m+ | |
Security Level {1} | rectifier alarm group n of N that occurs when a | n of N |
| |
| rectifier has been forced into the current limited |
|
| |
| mode. |
|
| |
Rectifier Current Limit Alarm | The status will be “ON” if the rectifier has been | Rect 1 CL | # | |
Status | forced into its current limited mode. NOTE: This | OFF |
| |
{Status Only} | information can be viewed for each rectifier |
|
| |
[MODULES/RECT/INFO] | installed by using the horizontal arrow keys. |
|
| |
Rectifier Current Output Status | A display of the DC output current for the | Rect 1 Curr | # | |
{Status Only} | individual rectifier. NOTE: This information can | 24.9 A | ||
[MODULES/RECT/INFO] | be viewed for each rectifier installed by using |
|
| |
| the horizontal arrow keys. |
|
|
MX28B1200/2400 MX28B1200/4800 | Page 42 |