PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Output Relay 1 Delay

Delay between sensing of the alarm condition and

Out-Rly 1 Dly m+

Security Level {1}

activation of Output Relay 1. An alarm condition

0 sec

[SYSTEM/OUT-RLY/RLY-

must exist for longer than the delay to be

 

 

MAP]

activated.

 

 

 

 

 

Output Relay 6 Delay

Delay between sensing of the alarm condition and

Out-Rly 6 Dly m+

Security Level {1}

activation of Output Relay 6. An alarm condition

0 sec

[SYSTEM/OUT-RLY/RLY-

must exist for longer than the delay to be

 

 

MAP]

activated.

 

 

Output Relay Major Alias

An alternate name (alias) can be assigned to the

Relay Major

m+

Security Level {1}

major Relay if desired.

Major

 

[SYSTEM/OUT-RLY/ALIAS]

 

 

 

Output Relay Minor Alias

An alternate name (alias) can be assigned to the

Relay Minor

m+

Security Level {1}

Minor Relay if desired.

Minor

 

[SYSTEM/OUT-RLY/ALIAS]

 

 

 

PIN 1 change

Permanently change password (PIN) that permits

PIN

m+

Security Level {2}

security Level 1 parameter changes - limited

1111

[SYSTEM/SETUP]

access.

 

 

PIN 2 Change

Permanently change password (PIN) that permits

PIN 2

m+

Security Level {2}

security Level 2 parameter changes - unlimited

2222

[SYSTEM/SETUP]

access.

 

 

PIN Entry

Screen for entry of the active password (PIN).

PIN

m+

Security Level {0}

Before any changes can be made, the correct pin

0000

[PIN]

for the desires security level must be entered.

 

 

 

Level 0 – full read access. Level 1 –full read and

 

 

 

limited write access. Level 2 – full read and write

 

 

 

access.

 

 

Rectifier Communications Fail

The maximum rectifier communications response

RectFailComm

m+

Timeout

time allowed before a communications failure is

1 min

Security Level {1}

declared.

 

 

[MODULES/RECT/PARAM]

 

 

 

Rectifier Configuration Alarm

The output relay energized if the rectifier

Rect Cfg Alm

m+

Security Level {1}

configuration differs from its stored configuration.

Minor

 

[SYSTEM/SET-ALM]

This occurs if a rectifier is added after

 

 

 

configuration.

 

 

Rectifier Current Limit Alarm

The output relay that is energized or special

Rect CL Alm

m+

Security Level {1}

rectifier alarm group n of N that occurs when a

n of N

 

[MODULES/RECT/SET-ALM]

rectifier has been forced into the current limited

 

 

 

mode.

 

 

Rectifier Current Limit Alarm

The status will be “ON” if the rectifier has been

Rect 1 CL

#

Status

forced into its current limited mode. NOTE: This

OFF

 

{Status Only}

information can be viewed for each rectifier

 

 

[MODULES/RECT/INFO]

installed by using the horizontal arrow keys.

 

 

Rectifier Current Output Status

A display of the DC output current for the

Rect 1 Curr

#

{Status Only}

individual rectifier. NOTE: This information can

24.9 A

[MODULES/RECT/INFO]

be viewed for each rectifier installed by using

 

 

 

the horizontal arrow keys.

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 42

Image 47
Contents VDC Power Systems Table of Contents Commissioning and Preventive Maintenance APC Worldwide Customer Support Limited Product Warranty Revision Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information How to Use This ManualIntroduction 1 MX28B-1200 -48 VDC Power Plant Rectifier Bay 2 MX28B Block Diagram Room / Location InstallationMechanical Installation Unpacking EquipmentMounting Power Bus Connections2 MX28B-1200-2400 has a maximum 5 Circuit Breaker / LVD Expansion Board Circuit Breaker/LVD Ribbon Cable ConnectionsVentilation AC Power ConnectionsFuse Alarm Ribbon Cable Connections 1 AC Input Wiring Planning the Battery Installation Battery Connections1 Battery Cable Connection Locations Connecting the Battery CablesDC System Grounding 2 Battery Probe ConnectionDC Plug-in Circuit Breakers DC Power Output Over-Current ProtectionBreaker Part Number Rating 2 Plug-in Circuit Breakers 4 Bolt-in Circuit Breakers DC Bolt-in Circuit Breakers5 Telecom Fuses Telecom FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and Fuses2 Circuit Breaker Alarm Wiring Bolt-in Circuit Breaker InstallationGMT Fuse Installation Telecom Fuse InstallationCircuit Breaker Connections 60-100 Amps Load ConnectionsCable Size Considerations Circuit Breaker Connections 1 to 50 AmpsSmart Cable DB9 Connection Monitoring and Relay Output ConnectionsGMT Fuse Connections Front Panel DB9 ConnectionRelay Output Connections RJ45 Ethernet ConnectorNO-NC-C External Alarm Input ConnectionsRectifier Module Installation Pre-Commissioning Inspection Commissioning and Preventive MaintenanceElectrical Installation Battery Visual and Safety InspectionInitial Set-up AC Power UpCommissioning LVD Test DC Power UpBattery Power Up Rectifier TestOutput Relays Battery Temperature CompensationCircuit Breaker/ Fuse Test User InputsFinal Inspection Rectifier Management OperationTechnical Description System Current System ManagementSystem Output Capacity System Voltage ControlDC Distribution Battery ManagementSystem Status and Alarm Reporting Battery Charging and ProtectionFront Panel User Interface Controls and IndicatorsBattery/Load Low Voltage Disconnect Parameter Locations, Descriptions, and Default Values Status Alarms System Modules Batt PIN OEMSwitzer Alarm ItemNo Alarms AddressBatt HV Alm Batt HT AlmBatt HT Thr 70.0 CComp Hknee Cir Bkr 1 Alm m+Major Cir Bkr 72 Almm+Minor Fuse 1 AlmFuse 16 Alm Hw Batt C Almm+LVD Trip LVD ResetLVD Option 48.00Relay Major Out-Rly 1 Dly m+Sec Out-Rly 6 Dly m+Rect 1ofN Almm+ DisableRect 1 Desc MRF28H54Sys LT Thr Sys HV AlmSys HV Thr Sys LT Alm90025 TimeControl Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin Modrec AM Info Modfuse LM Alias Fuse MOD Modlvd Modlvd LM Param Section Alarm Outputs Output RelaysFront Panel LED Indicators External Alarm Inputs Input Relays Physical Connections Command and Monitoring ProtocolRemote Monitoring DescriptionInspection Preventive MaintenanceSystem Visual and Safety Inspection EquipmentRectifier Current Test TestSystem Voltage Test Rectifier Current Share Test Rectifier Alarm TestSystem Temperature Test Battery Current TestBattery Preventive Maintenance Procedure Battery Temperature TestFinal Inspection 1MRF28H54BV50 Rectifiers SpecificationsAC Input 1MRF28H54BV RectifiersRectifiers VDCPower Shelf Control Unit Compliance MechanicalEnvironmental Worldwide APC Worldwide Customer SupportUS and Canada Toll FreeLimited Product Warranty