1.Use the right or left arrow keys to position the cycling cursor below “SYSTEM”.

2.Press the down arrow key once.

3.Use the right arrow key to position the cycling cursor below “IN-RLY”.

4.Press the down arrow key once; the cursor will be cycling below “RLY-MAP”.

5.Press the down arrow key (repeatedly if necessary) until the desired parameter screen is displayed (there are eight parameter screens in this category).

After making any desired changes, return to the main menu press the up arrow key repeatedly. If a parameter requires a level 1 or level 2 security access to permit changes to it, the security level will be found in braces, i.e. Security Level {2}, in the “PARAMETER” column of the table.

Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Address 1

Power plant address or identification - first line.

Address 1

m+

Security Level {1}

 

APC DCNS, Inc.

 

[SYSTEM/SETUP]

 

 

 

Address 2

Power plant address or identification - second line.

Address 2

m+

Security Level {1}

 

11035 Switzer

Av

[SYSTEM/SETUP]

 

 

 

Address 3

Power plant address or identification - third line.

Address 3

m+

Security Level {1}

 

Dallas, TX.

 

[SYSTEM/SETUP]

 

 

 

Alarms Item 1

Display of up to 16 active alarms (a typical alarm

Alarm Item 1

+

{Status Only}

screen is shown).

Batt LV Alm Onm

[ALARMS]

 

 

 

 

 

 

 

Alarms Item 16

Display of up to 16 active alarms (a typical alarm

Alarm Item 16

+

[ALARMS]

screen is shown).

No Alarms

 

Battery Current

Battery current measured by the system controller

Batt Current

+

{Status Only}

at the battery current shunt.

-15.0 A

[STATUS]

 

 

 

Battery Discharge Alarm

The output relay energized if the battery discharge

Batt Disc Alm m+

Security Level {1}

current exceeds the programmed battery

Minor

 

[BATT/SET-ALM]

discharge threshold.

 

 

Battery Discharge Threshold

An alarm is generated if the battery discharge

Batt Disc Thr m+

Security Level {1}

current exceeds this value.

10 A

[BATT/SET-ALM]

 

 

 

Battery Float Voltage

One of three parameters that control the DC

Batt Float

m+

Security Level {1}

output voltage. Set the Float Voltage at 25°C

-54.00 V

[BATT/PARAM]

battery temperature per the battery manufacturers

 

 

 

recommendations.

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 37

Image 42
Contents VDC Power Systems Table of Contents Commissioning and Preventive Maintenance APC Worldwide Customer Support Limited Product Warranty Revision History Revision Date DescriptionSafety First General PrecautionsHow to Use This Manual IntroductionGeneral Information 1 MX28B-1200 -48 VDC Power Plant Rectifier Bay 2 MX28B Block Diagram Unpacking Equipment InstallationMechanical Installation Room / LocationPower Bus Connections Mounting2 MX28B-1200-2400 has a maximum Circuit Breaker/LVD Ribbon Cable Connections 5 Circuit Breaker / LVD Expansion BoardAC Power Connections Fuse Alarm Ribbon Cable ConnectionsVentilation 1 AC Input Wiring Battery Connections Planning the Battery InstallationConnecting the Battery Cables 1 Battery Cable Connection Locations2 Battery Probe Connection DC System GroundingDC Power Output Over-Current Protection DC Plug-in Circuit BreakersBreaker Part Number Rating 2 Plug-in Circuit Breakers DC Bolt-in Circuit Breakers 4 Bolt-in Circuit BreakersTelecom Fuses 5 Telecom FusesInstallation of Circuit Breakers and Fuses Plug-in Circuit Breaker InstallationBolt-in Circuit Breaker Installation 2 Circuit Breaker Alarm WiringTelecom Fuse Installation GMT Fuse InstallationCircuit Breaker Connections 1 to 50 Amps Load ConnectionsCable Size Considerations Circuit Breaker Connections 60-100 AmpsFront Panel DB9 Connection Monitoring and Relay Output ConnectionsGMT Fuse Connections Smart Cable DB9 ConnectionRJ45 Ethernet Connector Relay Output ConnectionsExternal Alarm Input Connections NO-NC-CRectifier Module Installation Battery Visual and Safety Inspection Commissioning and Preventive MaintenanceElectrical Installation Pre-Commissioning InspectionAC Power Up CommissioningInitial Set-up Rectifier Test DC Power UpBattery Power Up LVD TestUser Inputs Battery Temperature CompensationCircuit Breaker/ Fuse Test Output RelaysFinal Inspection Operation Technical DescriptionRectifier Management System Voltage Control System ManagementSystem Output Capacity System CurrentBattery Charging and Protection Battery ManagementSystem Status and Alarm Reporting DC DistributionControls and Indicators Battery/Load Low Voltage DisconnectFront Panel User Interface Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default ValuesAddress Alarm ItemNo Alarms Switzer70.0 C Batt HT AlmBatt HT Thr Batt HV AlmCir Bkr 72 Almm+ Cir Bkr 1 Alm m+Major Comp HkneeHw Batt C Almm+ Fuse 1 AlmFuse 16 Alm Minor48.00 LVD ResetLVD Option LVD TripOut-Rly 6 Dly m+ Out-Rly 1 Dly m+Sec Relay MajorMRF28H54 DisableRect 1 Desc Rect 1ofN Almm+Sys LT Alm Sys HV AlmSys HV Thr Sys LT ThrTime 90025SYS MS System Module SET-ALM Setup DA Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin Modrec AM Info Modfuse LM Alias Fuse MOD Modlvd Modlvd LM Param Alarm Outputs Output Relays Front Panel LED IndicatorsSection External Alarm Inputs Input Relays Description Command and Monitoring ProtocolRemote Monitoring Physical ConnectionsEquipment Preventive MaintenanceSystem Visual and Safety Inspection InspectionTest System Voltage TestRectifier Current Test Battery Current Test Rectifier Alarm TestSystem Temperature Test Rectifier Current Share TestBattery Temperature Test Battery Preventive Maintenance ProcedureFinal Inspection 1MRF28H54BV Rectifiers SpecificationsAC Input 1MRF28H54BV50 RectifiersVDC RectifiersPower Shelf Control Unit Mechanical EnvironmentalCompliance Toll Free APC Worldwide Customer SupportUS and Canada WorldwideLimited Product Warranty