American Power Conversion MX28B2400, MX28B4800 manual Commissioning, Initial Set-up, AC Power Up

Page 33

b.Case leaks.

c.Post- seal leaks.

d.Pressure relief valve leaks (VRLA only).

e.Case swelling (VRLA only).

f.Case swelling (VRLA only).

10.Check the torque of all battery inter- cell connector in accordance with the battery manufacturer’s specifications.

4.2. Commissioning

Initial Set-up

1.Remove all rectifiers. Ensure that the float/equalise switch is on float.

2.Disconnect battery by removing a link in each string or opening the battery disconnects.

3.Check that battery voltage does not appear on the system bus.

4.Disconnect all loads.

AC Power Up

WARNING: The DC power plant is supplied from a nominal high voltage AC voltage source. Keep the AC input enclosure cover in place when the system is operational or energized

1.Verify that AC voltage is present for each rectifier at the back- plane position (Blue J2 of 0P-9131) inside the rectifier compartment. The AC input breaker for each rectifier should be switched on and off to ensure that you have power at every rectifier and that the breaker disconnects the rectifier.

2.Verify that all of the circuit breaker positions are labeled to the corresponding rectifier correctly.

3.Insert all rectifiers.

4.Turn all rectifier circuit breakers on.

5.The main screen should appear on the control unit display (see Figure 5.6-1). The display on the control unit is a 2-lines by 16-characters display. The cursor cycles below the characters of the active selection on the display. Information shown in the second line of Figure 5.6-1 that extends beyond 16 characters (to the right of the “S” in “ALARMS”) can viewed on the control unit display by using the scrolling controls (refer to Section 5.6 for operation of the control unit).

NOTE: When AC power is initially applied, there is a 60-second period during which no alarms are reported.

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 28

Image 33
Contents VDC Power Systems Table of Contents Commissioning and Preventive Maintenance APC Worldwide Customer Support Limited Product Warranty Revision Date Description Revision HistoryGeneral Precautions Safety FirstHow to Use This Manual IntroductionGeneral Information 1 MX28B-1200 -48 VDC Power Plant Rectifier Bay 2 MX28B Block Diagram Mechanical Installation InstallationUnpacking Equipment Room / LocationMounting Power Bus Connections2 MX28B-1200-2400 has a maximum 5 Circuit Breaker / LVD Expansion Board Circuit Breaker/LVD Ribbon Cable ConnectionsAC Power Connections Fuse Alarm Ribbon Cable ConnectionsVentilation 1 AC Input Wiring Planning the Battery Installation Battery Connections1 Battery Cable Connection Locations Connecting the Battery CablesDC System Grounding 2 Battery Probe ConnectionDC Plug-in Circuit Breakers DC Power Output Over-Current ProtectionBreaker Part Number Rating 2 Plug-in Circuit Breakers 4 Bolt-in Circuit Breakers DC Bolt-in Circuit Breakers5 Telecom Fuses Telecom FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and Fuses2 Circuit Breaker Alarm Wiring Bolt-in Circuit Breaker InstallationGMT Fuse Installation Telecom Fuse InstallationCable Size Considerations Load ConnectionsCircuit Breaker Connections 1 to 50 Amps Circuit Breaker Connections 60-100 AmpsGMT Fuse Connections Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Smart Cable DB9 ConnectionRelay Output Connections RJ45 Ethernet ConnectorNO-NC-C External Alarm Input ConnectionsRectifier Module Installation Electrical Installation Commissioning and Preventive MaintenanceBattery Visual and Safety Inspection Pre-Commissioning InspectionAC Power Up CommissioningInitial Set-up Battery Power Up DC Power UpRectifier Test LVD TestCircuit Breaker/ Fuse Test Battery Temperature CompensationUser Inputs Output RelaysFinal Inspection Operation Technical DescriptionRectifier Management System Output Capacity System ManagementSystem Voltage Control System CurrentSystem Status and Alarm Reporting Battery ManagementBattery Charging and Protection DC DistributionControls and Indicators Battery/Load Low Voltage DisconnectFront Panel User Interface Parameter Locations, Descriptions, and Default Values Status Alarms System Modules Batt PIN OEMNo Alarms Alarm ItemAddress SwitzerBatt HT Thr Batt HT Alm70.0 C Batt HV AlmMajor Cir Bkr 1 Alm m+Cir Bkr 72 Almm+ Comp HkneeFuse 16 Alm Fuse 1 AlmHw Batt C Almm+ MinorLVD Option LVD Reset48.00 LVD TripSec Out-Rly 1 Dly m+Out-Rly 6 Dly m+ Relay MajorRect 1 Desc DisableMRF28H54 Rect 1ofN Almm+Sys HV Thr Sys HV AlmSys LT Alm Sys LT Thr90025 TimeControl Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin Modrec AM Info Modfuse LM Alias Fuse MOD Modlvd Modlvd LM Param Alarm Outputs Output Relays Front Panel LED IndicatorsSection External Alarm Inputs Input Relays Remote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsSystem Visual and Safety Inspection Preventive MaintenanceEquipment InspectionTest System Voltage TestRectifier Current Test System Temperature Test Rectifier Alarm TestBattery Current Test Rectifier Current Share TestBattery Preventive Maintenance Procedure Battery Temperature TestFinal Inspection AC Input Specifications1MRF28H54BV Rectifiers 1MRF28H54BV50 RectifiersRectifiers VDCPower Shelf Control Unit Mechanical EnvironmentalCompliance US and Canada APC Worldwide Customer SupportToll Free WorldwideLimited Product Warranty