American Power Conversion MX28B2400 Sys HV Alm, Sys HV Thr, Sys LT Alm, Sys LT Thr, Sys LV Alm

Page 49

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

System High Voltage alarm

The output relay energized if the System Voltage

Sys HV Alm

m+

Security Level {1}

is above the System High Voltage threshold.

Minor

 

[SYSTEM/SET-ALM]

 

 

 

System High Voltage

System Voltage is bus voltage measured by the

Sys HV Thr

m+

Threshold

controller. An alarm will be reported if voltage is

-58.00 V

Security Level {1}

higher than the voltage entered.

 

 

[SYSTEM/SET-ALM]

 

 

 

System Low Temperature

The output relay energized if the System

Sys LT Alm

m+

Alarm

Temperature is below the System Low

Minor

 

Security Level {1}

Temperature threshold.

 

 

[SYSTEM/SET-ALM]

 

 

 

System Low Temperature

System Temperature is ambient temperature

Sys LT Thr

m+

Threshold

measured inside the controller. An alarm will be

0.0 C

Security Level {1}

reported if temperature is lower than the

 

 

[SYSTEM/SET-ALM]

temperature entered.

 

 

System Low Voltage Alarm

The output relay energized if the System Voltage

Sys LV Alm

m+

Security Level {1}

is below the System Low Voltage threshold.

Minor

 

[SYSTEM/SET-ALM]

 

 

 

System Low Voltage Threshold

System Voltage is bus voltage measured by the

Sys LV Thr

m+

Security Level {1}

controller. An alarm will be reported if voltage is

-50.00 V

[SYSTEM/SET-ALM]

lower than the voltage entered.

 

 

System Temperature

System temperature measured within the control

Sys Temp

+

{Status Only}

unit.

26.7 C

[STATUS]

 

 

 

System Voltage

System output voltage measured between the

Sys Voltage

+

{Status Only}

MX28B DC power plant -48V and return buses.

-54.00 V

[STATUS]

 

 

 

Test Major Relay

Setting this parameter to “ON” de-energizes the

Test Maj Rly

m+

Security Level {1}

Major Relay and turns on the “MAJ” LED on the

OFF

 

[SYSTEM/DIAG]

control unit front panel. In normal operation Major

 

 

 

Relay is energized so that when a loss of –48

 

 

 

VDC power occurs, the relay will change state.

 

 

Test Minor Relay

Setting this parameter to “ON” energizes the Minor

Test Min Rly

m+

Security Level {1}

Relay and turns on the “MIN” LED on the control

OFF

 

[SYSTEM/DIAG]

unit front panel.

 

 

Test Relay 1

Setting this parameter to “ON” energizes Relay 1

Test Relay 1

m+

Security Level {1}

and turns on the “ALM1” LED on the control unit

OFF

 

[SYSTEM/DIAG]

front panel.

 

 

 

 

 

 

Test Relay 6

Setting this parameter to “ON” energizes Relay 6

Test Relay 6

m+

Security Level {1}

and turns on the “ALM6” LED on the control unit

OFF

 

[SYSTEM/DIAG]

front panel.

 

 

 

 

 

Test Relay Enable

This parameter must be set to “Enable” to permit

Test Relay En m+

Security Level {1}

the eight output relays to be manually tested;

Disable

 

[SYSTEM/DIAG]

otherwise, the state of the relays will be per

 

 

 

system conditions.

 

 

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 44

Image 49
Contents VDC Power Systems Table of Contents Commissioning and Preventive Maintenance APC Worldwide Customer Support Limited Product Warranty Revision Date Description Revision HistoryGeneral Precautions Safety FirstIntroduction How to Use This ManualGeneral Information 1 MX28B-1200 -48 VDC Power Plant Rectifier Bay 2 MX28B Block Diagram Mechanical Installation InstallationUnpacking Equipment Room / LocationMounting Power Bus Connections2 MX28B-1200-2400 has a maximum 5 Circuit Breaker / LVD Expansion Board Circuit Breaker/LVD Ribbon Cable ConnectionsFuse Alarm Ribbon Cable Connections AC Power ConnectionsVentilation 1 AC Input Wiring Planning the Battery Installation Battery Connections1 Battery Cable Connection Locations Connecting the Battery CablesDC System Grounding 2 Battery Probe ConnectionDC Plug-in Circuit Breakers DC Power Output Over-Current ProtectionBreaker Part Number Rating 2 Plug-in Circuit Breakers 4 Bolt-in Circuit Breakers DC Bolt-in Circuit Breakers5 Telecom Fuses Telecom FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and Fuses2 Circuit Breaker Alarm Wiring Bolt-in Circuit Breaker InstallationGMT Fuse Installation Telecom Fuse InstallationCable Size Considerations Load ConnectionsCircuit Breaker Connections 1 to 50 Amps Circuit Breaker Connections 60-100 AmpsGMT Fuse Connections Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Smart Cable DB9 ConnectionRelay Output Connections RJ45 Ethernet ConnectorNO-NC-C External Alarm Input ConnectionsRectifier Module Installation Electrical Installation Commissioning and Preventive MaintenanceBattery Visual and Safety Inspection Pre-Commissioning InspectionCommissioning AC Power UpInitial Set-up Battery Power Up DC Power UpRectifier Test LVD TestCircuit Breaker/ Fuse Test Battery Temperature CompensationUser Inputs Output RelaysFinal Inspection Technical Description OperationRectifier Management System Output Capacity System ManagementSystem Voltage Control System CurrentSystem Status and Alarm Reporting Battery ManagementBattery Charging and Protection DC DistributionBattery/Load Low Voltage Disconnect Controls and IndicatorsFront Panel User Interface Parameter Locations, Descriptions, and Default Values Status Alarms System Modules Batt PIN OEMNo Alarms Alarm ItemAddress SwitzerBatt HT Thr Batt HT Alm70.0 C Batt HV AlmMajor Cir Bkr 1 Alm m+Cir Bkr 72 Almm+ Comp HkneeFuse 16 Alm Fuse 1 AlmHw Batt C Almm+ MinorLVD Option LVD Reset48.00 LVD TripSec Out-Rly 1 Dly m+Out-Rly 6 Dly m+ Relay MajorRect 1 Desc DisableMRF28H54 Rect 1ofN Almm+Sys HV Thr Sys HV AlmSys LT Alm Sys LT Thr90025 TimeControl Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin Modrec AM Info Modfuse LM Alias Fuse MOD Modlvd Modlvd LM Param Front Panel LED Indicators Alarm Outputs Output RelaysSection External Alarm Inputs Input Relays Remote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsSystem Visual and Safety Inspection Preventive MaintenanceEquipment InspectionSystem Voltage Test TestRectifier Current Test System Temperature Test Rectifier Alarm TestBattery Current Test Rectifier Current Share TestBattery Preventive Maintenance Procedure Battery Temperature TestFinal Inspection AC Input Specifications1MRF28H54BV Rectifiers 1MRF28H54BV50 RectifiersRectifiers VDCPower Shelf Control Unit Environmental MechanicalCompliance US and Canada APC Worldwide Customer SupportToll Free WorldwideLimited Product Warranty