Installation
Utility Source (provided by others)
480V 3 or 4 Wire + Ground
MIB 90AT
69A
Service | F4, 5, 6 | |
Bypass | ||
UIF | ||
Panel | ||
Q001 | ||
| ||
| UIS | |
69A | 48A |
UPS
300A
400AT
48A
F1, 2, 3
UOF
Q002 | Q003 |
UOS | BS |
48A
UPS System Output
40kW
480V 3 or 4 Wire + Ground
Notes:
1.Must be 3- or
2.Must be 3- or
3.Input overcurrent protection is based on 80% rating - any deviation, please contact APC.
4.F1, F2, F3 = 55A
5.F4, F5, F6 = 75A
6.All AC power cabling is 3- or
7.UPS output cables and input cables must be in separate conduits.
8.Power wiring and control wiring must be in separate conduits.
9.See installation manual for battery information.
10.Installation must comply with all applicable national and local codes.
Figure 9 Single Line Diagram 480V
NOTICE!
Size utility input overcurrent protection device as per applicable codes. See below table for utility input voltage and current ratings.
16 | Installation Guide APC BC300 Series 40kW 208/450/480V UPS |