APC BC300 Series manual 69A

Page 16

Installation

Utility Source (provided by others)

480V 3 or 4 Wire + Ground

MIB 90AT

69A

Service

F4, 5, 6

Bypass

UIF

Panel

Q001

 

 

UIS

69A

48A

UPS

300A

400AT

48A

F1, 2, 3

UOF

Q002

Q003

UOS

BS

48A

UPS System Output

40kW

480V 3 or 4 Wire + Ground

Notes:

1.Must be 3- or 4-wire + Ground

2.Must be 3- or 4-wire + Ground cabling provided by others.

3.Input overcurrent protection is based on 80% rating - any deviation, please contact APC.

4.F1, F2, F3 = 55A

5.F4, F5, F6 = 75A

6.All AC power cabling is 3- or 4-wire + Ground at 480VAC 3-phase.

7.UPS output cables and input cables must be in separate conduits.

8.Power wiring and control wiring must be in separate conduits.

9.See installation manual for battery information.

10.Installation must comply with all applicable national and local codes.

Figure 9 Single Line Diagram 480V

NOTICE!

Size utility input overcurrent protection device as per applicable codes. See below table for utility input voltage and current ratings.

990-1401

16

Installation Guide APC BC300 Series 40kW 208/450/480V UPS

Image 16
Contents APC BC300 Series 40kW 208/450/480V Installation Guide Copyright 2002 APC Denmark ApSSafety Symbols used in this manual Installation Guide APC BC300 Series 40kW 208/450/480V UPSThank You Contents Introduction IntroductionTools and Equipment Needed Insulated Tools and Other Equipment NeededReceiving, Unpacking and Moving to Site Please RecycleInstallation InstallationRequirements on Site UPS Footprint measurements in inches & mm Footprint Installing the Conduit Connection KitInsulated and other tools required Installing Pedestals Conduit Connection Kit ContentsInstalling Conduit Box and Base Covers Installing the Maintenance Bypass Panel and UPS SBP Electrical Schematic Component Overview door open Component OverviewWire Terminals Wire TerminalsWiring Diagram for BC300 Utility inputSingle Line Diagram for BC300 Single Line DiagramSingle Line Diagram 40kW 69A UPS Model Input Output Recom DC Voltage DC Current Mended MIBExternal Connection Board External Connection BoardCommunication Interface Board Option Communication Interface BoardSmart Slot and Connection of Triple Chassis Communication InterfaceSafety Warnings APC BC300 Triple ChassisProduct Description Monitoring PortPower Input Installing Management ProductsInstalling Management Cards To UPS PortCascading setup of the APC BC300 Triple Chassis Powering the APC BC300 Triple ChassisPower Considerations Power AdaptersTriple Chassis Power Considerations Determining Power RequirementsTroubleshooting Problem Possible Cause SolutionProduct Specifications Monitoring Port Pin Assignments Monitoring Port Pin Assignment Installation of External Batteries and Battery Breaker Power, Physical, and Environmental SpecificationsBattery Installation PhysicalBattery Installation Guidelines Do not connect the negative cables to the UPS yet Battery Replacement Initial Start-up and Phase Check Initial Start-up and Phase CheckInitial Start-up and Phase Check External Batteries Clearing the Events Log Clearing the Events LogStart-up and Shutdown Procedure Start-up and Shutdown ProcedureStart-up from Maintenance Bypass Shutdown ProcedureIf you have shut the loads down Move on to step Technical Specifications Technical SpecificationsAPC BC300 Series 40 kW Technical Data Battery Specifications Dimensions/WeightHow to Contact APC How to Contact APCAPC Corporate Fairgrounds Road West Kingston, RIHow to Contact APC