APC manual Technical Specifications, APC BC300 Series 40 kW Technical Data

Page 35

Technical Specifications

7.0Technical Specifications

7.1APC BC300 Series 40 kW Technical Data

 

Voltage

3 x 208Y/120 or

450V Delta

3 x 480Y/277

 

 

208V Delta

 

 

 

 

 

 

 

Input

Rated input current

146Amps

75 Amps

63Amps

 

 

 

 

 

 

Voltage tolerance

 

 

 

 

- Utility

+10 / -15

+10 / -15

+10 / -15

 

- Bypass

+/- 10

+/- 10

+/- 10

 

 

 

 

 

 

Frequency

60Hz

60Hz

60Hz

 

 

+/- 6%

+/- 6%

+/- 6%

 

 

(standard)

(standard)

(standard)

 

 

 

 

 

 

Current distortion

0-5% THD

0-5% THD

0-5% THD

 

 

 

 

 

 

Bypass tolerance

+/- 10%

+/- 10%

+/- 10%

 

 

 

 

 

Output

Voltage

3 x 208Y/120

3 x 450Y/277 or

3 x 480Y/277 or

 

 

 

3 x 450 Delta

3x 480 Delta

 

 

 

 

 

 

Voltage tolerance

 

 

 

 

- Static symmetrical load

+/- 1

+/- 1

+/- 1

 

- Static asymmetrical load

+/- 3

+/- 3

+/- 3

 

- Load step

+/- 5

+/- 5

+/- 5

 

 

 

 

 

 

Voltage distortion

0 - 3% (linear

0 - 3% (linear

0 - 3% (linear

 

 

load)

load)

load)

 

 

 

 

 

 

Frequency

60Hz

60Hz

60Hz

 

- Utility synchronized

+/- 6%

+/- 6%

+/- 6%

 

- Free-running

+/- 0.1%

+/- 0.1%

+/- 0.1%

 

 

 

 

 

 

Overload capacity

 

 

 

 

- Utility operation 60 seconds

250%

250%

250%

 

- Utility operation 10 minutes

150%

150%

150%

 

- Battery operation 60 seconds

150%

150%

150%

 

- Battery operation 10 minutes

125%

125%

125%

 

 

 

 

 

 

Rated output current

111 Amps

51 Amps

48 Amps

 

 

 

 

 

General

Temperature

 

 

 

 

Ambient

32 - 104 o F

32 - 104 o F

32 - 104 o F

 

Ideal

77 o F

77 o F

77 o F

 

Humidity (non condensing)

Max 95%

Max 95%

Max 95%

 

 

 

 

 

 

Audible Noise (typical)

<65 dBa

<65 dBa

<65 dBa

 

 

 

 

 

 

Efficiency

 

 

 

 

AC to AC normal operation

95%

95%

95%

 

AC to AC economy mode

97%

97%

97%

 

 

 

 

 

 

Heat dissipation - kW (BTU)

 

 

 

 

Full rated load normal operation

2.11 (7185)

2.11 (7185)

2.11 (7185)

 

Full rated load economy mode

1.67 (5688)

1.67 (5688)

1.67 (5688)

 

0.8 PF load, normal operation

1.68 (5748)

1.68 (5748)

1.68 (5748)

 

0.8 PF load, economy mode

1.33 (4551)

1.33 (4551

1.33 (4551)

 

 

 

 

 

990-1401

Installation Guide APC BC300 Series 40kW 208/450/480V UPS

35

Image 35 Contents
Copyright 2002 APC Denmark ApS APC BC300 Series 40kW 208/450/480V Installation GuideThank You Installation Guide APC BC300 Series 40kW 208/450/480V UPSSafety Symbols used in this manual Contents Insulated Tools and Other Equipment Needed IntroductionIntroduction Tools and Equipment NeededPlease Recycle Receiving, Unpacking and Moving to SiteRequirements on Site InstallationInstallation Insulated and other tools required Installing the Conduit Connection KitUPS Footprint measurements in inches & mm Footprint Installing Conduit Box and Base Covers Conduit Connection Kit ContentsInstalling Pedestals Installing the Maintenance Bypass Panel and UPS SBP Electrical Schematic Component Overview Component Overview door openWire Terminals Wire TerminalsUtility input Wiring Diagram for BC300Single Line Diagram Single Line Diagram for BC300Single Line Diagram 40kW 69A MIB UPS Model Input Output Recom DC Voltage DC Current MendedExternal Connection Board External Connection BoardCommunication Interface Board Communication Interface Board OptionCommunication Interface Smart Slot and Connection of Triple ChassisMonitoring Port Safety WarningsAPC BC300 Triple Chassis Product DescriptionTo UPS Port Power InputInstalling Management Products Installing Management CardsPower Adapters Cascading setup of the APC BC300 Triple ChassisPowering the APC BC300 Triple Chassis Power ConsiderationsProblem Possible Cause Solution Triple Chassis Power ConsiderationsDetermining Power Requirements TroubleshootingProduct Specifications Monitoring Port Pin Assignments Monitoring Port Pin Assignment Physical Installation of External Batteries and Battery BreakerPower, Physical, and Environmental Specifications Battery InstallationBattery Installation Guidelines Do not connect the negative cables to the UPS yet Battery Replacement Initial Start-up and Phase Check External Batteries Initial Start-up and Phase CheckInitial Start-up and Phase Check Clearing the Events Log Clearing the Events LogShutdown Procedure Start-up and Shutdown ProcedureStart-up and Shutdown Procedure Start-up from Maintenance BypassIf you have shut the loads down Move on to step APC BC300 Series 40 kW Technical Data Technical SpecificationsTechnical Specifications Dimensions/Weight Battery SpecificationsFairgrounds Road West Kingston, RI How to Contact APCHow to Contact APC APC CorporateHow to Contact APC