Technical Specifications
7.0Technical Specifications
7.1APC BC300 Series 40 kW Technical Data
| Voltage | 3 x 208Y/120 or | 450V Delta | 3 x 480Y/277 |
|
| 208V Delta |
|
|
|
|
|
|
|
Input | Rated input current | 146Amps | 75 Amps | 63Amps |
|
|
|
|
|
| Voltage tolerance |
|
|
|
| - Utility | +10 / | +10 / | +10 / |
| - Bypass | +/- 10 | +/- 10 | +/- 10 |
|
|
|
|
|
| Frequency | 60Hz | 60Hz | 60Hz |
|
| +/- 6% | +/- 6% | +/- 6% |
|
| (standard) | (standard) | (standard) |
|
|
|
|
|
| Current distortion | |||
|
|
|
|
|
| Bypass tolerance | +/- 10% | +/- 10% | +/- 10% |
|
|
|
|
|
Output | Voltage | 3 x 208Y/120 | 3 x 450Y/277 or | 3 x 480Y/277 or |
|
|
| 3 x 450 Delta | 3x 480 Delta |
|
|
|
|
|
| Voltage tolerance |
|
|
|
| - Static symmetrical load | +/- 1 | +/- 1 | +/- 1 |
| - Static asymmetrical load | +/- 3 | +/- 3 | +/- 3 |
| - Load step | +/- 5 | +/- 5 | +/- 5 |
|
|
|
|
|
| Voltage distortion | 0 - 3% (linear | 0 - 3% (linear | 0 - 3% (linear |
|
| load) | load) | load) |
|
|
|
|
|
| Frequency | 60Hz | 60Hz | 60Hz |
| - Utility synchronized | +/- 6% | +/- 6% | +/- 6% |
| - | +/- 0.1% | +/- 0.1% | +/- 0.1% |
|
|
|
|
|
| Overload capacity |
|
|
|
| - Utility operation 60 seconds | 250% | 250% | 250% |
| - Utility operation 10 minutes | 150% | 150% | 150% |
| - Battery operation 60 seconds | 150% | 150% | 150% |
| - Battery operation 10 minutes | 125% | 125% | 125% |
|
|
|
|
|
| Rated output current | 111 Amps | 51 Amps | 48 Amps |
|
|
|
|
|
General | Temperature |
|
|
|
| Ambient | 32 - 104 o F | 32 - 104 o F | 32 - 104 o F |
| Ideal | 77 o F | 77 o F | 77 o F |
| Humidity (non condensing) | Max 95% | Max 95% | Max 95% |
|
|
|
|
|
| Audible Noise (typical) | <65 dBa | <65 dBa | <65 dBa |
|
|
|
|
|
| Efficiency |
|
|
|
| AC to AC normal operation | 95% | 95% | 95% |
| AC to AC economy mode | 97% | 97% | 97% |
|
|
|
|
|
| Heat dissipation - kW (BTU) |
|
|
|
| Full rated load normal operation | 2.11 (7185) | 2.11 (7185) | 2.11 (7185) |
| Full rated load economy mode | 1.67 (5688) | 1.67 (5688) | 1.67 (5688) |
| 0.8 PF load, normal operation | 1.68 (5748) | 1.68 (5748) | 1.68 (5748) |
| 0.8 PF load, economy mode | 1.33 (4551) | 1.33 (4551 | 1.33 (4551) |
|
|
|
|
|
Installation Guide APC BC300 Series 40kW 208/450/480V UPS | 35 |