Installation
UPS Model |
| Input |
| Output |
| Recom- |
| DC Voltage |
| DC Current |
| ||||||
|
|
| Current |
| Current |
| mended |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| MIB |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
40kW 208V | 161A | 111A | 200AT | 216V | 200A |
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 40 kW 450V |
| 75A |
| 51A |
| 95AT |
| 216V |
| 200A |
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 40kW 480V |
| 69A |
| 48A |
| 130AT |
| 216V |
| 200A |
|
Notes:
1.3- or
2.Cables not provided by APC.
3.Recommended input
4.All AC cables must be AC 3- or
5.Keep UPS input, output and control cables in separate conduits.
6.Installation must comply with all applicable national and local codes.
NOTICE!
See the “Technical Specifications” section in this Installation Guide for recommended UPS input and output
CAUTION!
UPS systems can be connected as
NOTICE!
Only authorized electricians may install the UPS and all applicable codes must be observed.
NOTICE!
Always keep AC, DC and communication cables separated.
NOTICE!
The grounding electrode conductor (Protective Earth - PE) must be the same size (ampacity) as the UPS input circuit conductors. Conduit is not an acceptable grounding electrode conductor - see National Electrical Code Section
NOTICE!
The unit is wired from the factory as a separately derived system. Output neutral is bonded to equipment ground through main bonding jumper inside the UPS. See National Electrical Code Article
NOTICE!
The maintenance bypass switch must be a
| |
|
|
Installation Guide APC BC300 Series 40kW 208/450/480V UPS | 17 |