Installing the NetAXS-123 Panels

Installation

3.4 Wiring the Readers

Each reader port supports one or two readers (entry and exit readers) with Wiegand output format. The maximum power draw is 500 mA for readers and AUX Power combined.

To fully utilize each reader port, a shielded 7-conductor cable (18-22 AWG) is required. If you don’t need the HOLD LINE feature, you can use the standard 6-conductor cable (HAS part number NC186-BL).

Note: If you are using additional HOLD lines for readers, you will need an 8-conductor cable.

The cable shield should be grounded at the panel only. Grounding at both ends can cause ground loops which can be disruptive. The maximum recommended length of wiring is 500 feet per reader.

Figure 5 shows a one-door panel, with the readers wired to terminal blocks C-TB3 and C-TB4 on the Controller Board, and to terminal blocks IO-TB3, IO-TB4, IO-TB7, and IO-TB8 on the Add-On Board. The wires are color-coded to their labeled terminals. If this were a two-door panel, the two additional readers would be wired to terminal blocks C-TB1 and C-TB2 on the Controller Board, and to terminal blocks IO-TB1 and IO-TB2 on the Add-On Board.

Figure 5: Wiring Readers to the Controller Board

Note: Reader A and Reader B share LED, DO, D1, GND, and +12V connections. Each reader has its own Tamper and Hold.

The following three tables list the factory controller board I/O default settings for door-1, door-2, and door-3 configurations. These are the mappings for readers, inputs, and outputs. Reader A and Reader B share many common connections.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

29

Image 37
Contents NetAXS-123 Page Contents RS-485 Connection via PCI-3 RS-485 Connection via NetAXS-123 List of Figures Page List of Tables Page Installing the NetAXS-123 Panels Introduction Access Control OverviewNetAXS-123 Overview Panel Components and Descriptions NetAXS-123 Compact Enclosure Wiring and ComponentsNetAXS-123 Standard Enclosure Panel Wiring and Components Board Configuration Terminal Block Supervised Input WiringSupervised Input Terminal Blocks Supervised Tamper Terminal Blocks Typical Supervised Input Wiring DiagramNetAXS-123 Add-On Board NetAXS-123 Access Control UnitNetAXS-123 Input/Output Options Board Readers Inputs/OutputsReaders Supported by NetAXS-123 Supported ReadersSeries Reader Model Honeywell Part Number Real-Time Clock Protection Power SupplySuppressors BatteryInstalling the Compact Enclosure Panel InstallationInstalling on a Wall Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing over a Gang Box Installing on a Flat Surface Installing the Standard Enclosure Panel Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the Add-On Board Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Wiring Readers to the Controller Board Wiring the ReadersFactory Default Configuration Settings for Door IN9 REX IO-TB5 Wiring Door Strikes Or S4 Controller Board DIP Switch and Jumper Settings Setting DIP Switches and JumpersS7 a S8 b S9 b S10 Selection NetAXS-123 SW1 DIP Switch SettingsOFF S1a S2a Selection NetAXS-123 SW2 DIP Switch SettingsExternal NetAXS-123 Controller Board JumpersNormally Open Normally Closed Add-On Board DIP Switch and Jumper Settings12V External Setting the jumpers to configure the relay positionUSB Communications CommunicationsInstalling the NetAXS-123 Panels 2 RS-485 Communications RS-485 Configuration via N-485-PCI-3 RS-485 Configuration via NetAXS-123 Gateway Ethernet TCP/IP Communications Ethernet TCP/IP ConfigurationEthernet Connection System ConfigurationNetAXS-123 USB Connection USB ConnectionRS-485 Connection via PCI-3 RS-485 Connection via PCI-3RS-485 Connection via NetAXS-123 Installing the NetAXS-123 Panels PCI3 56K Dial-up Modem, RS-485 Connection via Hub M-56K Dial-up Modem, RS-485 Connection via Hub PCI-3Fiber Converter to RS-485 Connection via PCI-3 Fiber Converter to RS-485 Connection via PCI-3Fiber Converter to RS-485 Connection via NetAXS-123 Fiber Converter to RS-485 Connection via NetAXS-123Installing the NetAXS-123 Panels Ground only one Mixed Loops PoE Power Limitations Hardware SpecificationsRelay Contacts Reader InterfaceDevice Element Current MechanicalEnvironment Reader WiringCable Card Read / Door Lock Operation Basic Standalone OperationDoor Egress / Door Lock / Door Status Operation Maintenance Troubleshooting Problems and Solutions TroubleshootingProblem Solution Normal Support Hours Technical SupportWeb This page is left blank for printing purposes Honeywell Access Systems