Installing the NetAXS-123 Panels

Installation

Note: The power source selected by the jumper settings shown above configure the power source for the relay. It does not configure the power source for the panel.

• Setting the jumpers to configure the relay contact type:

Normally Open

Normally Closed

3.6.2 Add-On Board DIP Switch and Jumper Settings

Figure 8 locates the NetAXS-123 Add-On Board DIP switch panel and the output 1 and output 3 relay jumpers.

Figure 8: Add-On Board DIP Switch and Jumper Location

Note: The figure above shows a one-door Add-On Board configuration. If you are instead using a two-door Add-On Board, you will see an additional two relays (and their corresponding jumper sets) to the right of the relays shown. The additional relays and jumpers will configure output 11 and output 13, and all of the jumpers are configured in the same manner.

The NetAXS-123 Controller Board provides two jumper sets, one each for output relay 1 and output relay 3. Each relay has two 3-pin jumpers associated with it. One jumper selects either self-whetted (on-board, +12V) or external power (EXT) to be applied to the relay contact load. The other jumper is

40www.honeywell.com

Image 48
Contents NetAXS-123 Page Contents RS-485 Connection via PCI-3 RS-485 Connection via NetAXS-123 List of Figures Page List of Tables Page Installing the NetAXS-123 Panels Access Control Overview IntroductionNetAXS-123 Overview NetAXS-123 Compact Enclosure Wiring and Components Panel Components and DescriptionsNetAXS-123 Standard Enclosure Panel Wiring and Components Supervised Input Wiring Board Configuration Terminal BlockSupervised Input Terminal Blocks Typical Supervised Input Wiring Diagram Supervised Tamper Terminal BlocksNetAXS-123 Access Control Unit NetAXS-123 Add-On BoardNetAXS-123 Input/Output Options Board Readers Inputs/OutputsSupported Readers Readers Supported by NetAXS-123Series Reader Model Honeywell Part Number Power Supply Real-Time Clock ProtectionBattery SuppressorsInstallation Installing the Compact Enclosure PanelInstalling on a Wall Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing over a Gang Box Installing on a Flat Surface Installing the Standard Enclosure Panel Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the Add-On Board Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Wiring the Readers Wiring Readers to the Controller BoardFactory Default Configuration Settings for Door IN9 REX IO-TB5 Wiring Door Strikes Or S4 Setting DIP Switches and Jumpers Controller Board DIP Switch and Jumper SettingsNetAXS-123 SW1 DIP Switch Settings S7 a S8 b S9 b S10 Selection OFF NetAXS-123 SW2 DIP Switch Settings S1a S2a SelectionNetAXS-123 Controller Board Jumpers ExternalAdd-On Board DIP Switch and Jumper Settings Normally Open Normally ClosedSetting the jumpers to configure the relay position 12V ExternalCommunications USB CommunicationsInstalling the NetAXS-123 Panels 2 RS-485 Communications RS-485 Configuration via N-485-PCI-3 RS-485 Configuration via NetAXS-123 Gateway Ethernet TCP/IP Configuration Ethernet TCP/IP CommunicationsSystem Configuration Ethernet ConnectionUSB Connection NetAXS-123 USB ConnectionRS-485 Connection via PCI-3 RS-485 Connection via PCI-3RS-485 Connection via NetAXS-123 Installing the NetAXS-123 Panels PCI3 M-56K Dial-up Modem, RS-485 Connection via Hub PCI-3 56K Dial-up Modem, RS-485 Connection via HubFiber Converter to RS-485 Connection via PCI-3 Fiber Converter to RS-485 Connection via PCI-3Fiber Converter to RS-485 Connection via NetAXS-123 Fiber Converter to RS-485 Connection via NetAXS-123Installing the NetAXS-123 Panels Ground only one Mixed Loops Hardware Specifications PoE Power LimitationsRelay Contacts Reader InterfaceMechanical Device Element CurrentReader Wiring EnvironmentCable Basic Standalone Operation Card Read / Door Lock OperationDoor Egress / Door Lock / Door Status Operation Maintenance Troubleshooting Troubleshooting Problems and SolutionsProblem Solution Technical Support Normal Support HoursWeb This page is left blank for printing purposes Honeywell Access Systems