Honeywell NETAXS-123 manual IN9 REX

Page 39

Installing the NetAXS-123 Panels

Installation

Notes:

The Controller Board includes Inputs 7 and 8 but they are reserved for system use.

The Controller Board also includes Output 5, a general-purpose output, and Output 6, which is reserved by the system to control the boards’ RUN LEDs and thus is unavailable for user control.

Reader LED, while it is an output, should never be used to control anything other than its associated reader’s LED.

Table 6 lists the factory I/O board default settings for a door 2. These mappings should be used for the readers, inputs, and outputs when either a 1- or 2-door Add-On Board is attached to the board-to-board connector on the Controller Board.

Table 6: Factory Default Configuration Settings for Door 2

Type

Purpose

Web

Terminal

Reader A

Reader B

Other

 

 

Default

Block

 

 

 

 

 

Name

Label

 

 

 

 

 

 

 

 

 

 

Input

Egress/

Input 9:

IO-TB2

Input 9a

Input 9a

 

 

Request to

Door 2

IN9 (REX)

 

 

 

 

Exit (REX)

Egress

 

 

 

 

 

 

 

 

 

 

 

 

Door Status

Input 10:

IO-TB2

Input 10a

Input 10a

 

 

 

Door 2

IN10 (STS)

 

 

 

 

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

Reader

Input 11:

IO-TB3

Input 11

 

 

 

Tamper

Door

TMPR A

 

 

 

 

 

TMPR-A

 

 

 

 

 

 

 

 

 

 

 

 

Reader

Input 12:

IO-TB4

 

Input 12

 

 

Tamper

Door

TMPR B

 

 

 

 

 

TMPR-B

 

 

 

 

 

 

 

 

 

 

 

Output

Lock Relay

Output #7

IO-TB1

Output 7a

Output 7a

 

 

 

 

LOCK

 

 

 

 

 

 

 

 

 

 

 

Reader LED

Output #8

IO-TB3

Output 8a

Output 8a

 

 

 

 

LED

 

 

 

 

 

 

 

 

 

 

 

AUX Relay

Output #9

IO-TB1

 

 

Output 9

 

 

 

AUX

 

 

 

 

 

 

 

 

 

 

 

Reader

Future

IO-TB3

Output 10a

Output 10a

 

 

Buzzer

Feature

BZR

 

 

 

 

 

 

 

 

 

 

aReaders A and B share the same connection.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

31

Image 39
Contents NetAXS-123 Page Contents RS-485 Connection via PCI-3 RS-485 Connection via NetAXS-123 List of Figures Page List of Tables Page Installing the NetAXS-123 Panels Access Control Overview IntroductionNetAXS-123 Overview Panel Components and Descriptions NetAXS-123 Compact Enclosure Wiring and ComponentsNetAXS-123 Standard Enclosure Panel Wiring and Components Supervised Input Wiring Board Configuration Terminal BlockSupervised Input Terminal Blocks Supervised Tamper Terminal Blocks Typical Supervised Input Wiring DiagramBoard Readers Inputs/Outputs NetAXS-123 Access Control UnitNetAXS-123 Add-On Board NetAXS-123 Input/Output OptionsSupported Readers Readers Supported by NetAXS-123Series Reader Model Honeywell Part Number Real-Time Clock Protection Power SupplySuppressors BatteryInstallation Installing the Compact Enclosure PanelInstalling on a Wall Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing over a Gang Box Installing on a Flat Surface Installing the Standard Enclosure Panel Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Installing the Add-On Board Installing the NetAXS-123 Panels Installing the NetAXS-123 Panels Wiring Readers to the Controller Board Wiring the ReadersFactory Default Configuration Settings for Door IN9 REX IO-TB5 Wiring Door Strikes Or S4 Controller Board DIP Switch and Jumper Settings Setting DIP Switches and JumpersS7 a S8 b S9 b S10 Selection NetAXS-123 SW1 DIP Switch SettingsOFF S1a S2a Selection NetAXS-123 SW2 DIP Switch SettingsExternal NetAXS-123 Controller Board JumpersNormally Open Normally Closed Add-On Board DIP Switch and Jumper Settings12V External Setting the jumpers to configure the relay positionUSB Communications CommunicationsInstalling the NetAXS-123 Panels 2 RS-485 Communications RS-485 Configuration via N-485-PCI-3 RS-485 Configuration via NetAXS-123 Gateway Ethernet TCP/IP Communications Ethernet TCP/IP ConfigurationEthernet Connection System ConfigurationNetAXS-123 USB Connection USB ConnectionRS-485 Connection via PCI-3 RS-485 Connection via PCI-3RS-485 Connection via NetAXS-123 Installing the NetAXS-123 Panels PCI3 56K Dial-up Modem, RS-485 Connection via Hub M-56K Dial-up Modem, RS-485 Connection via Hub PCI-3Fiber Converter to RS-485 Connection via PCI-3 Fiber Converter to RS-485 Connection via PCI-3Fiber Converter to RS-485 Connection via NetAXS-123 Fiber Converter to RS-485 Connection via NetAXS-123Installing the NetAXS-123 Panels Ground only one Mixed Loops Reader Interface Hardware SpecificationsPoE Power Limitations Relay ContactsDevice Element Current MechanicalReader Wiring EnvironmentCable Basic Standalone Operation Card Read / Door Lock OperationDoor Egress / Door Lock / Door Status Operation Maintenance Troubleshooting Troubleshooting Problems and SolutionsProblem Solution Technical Support Normal Support HoursWeb This page is left blank for printing purposes Honeywell Access Systems