a/d/s/ iSeries manual Thermocouple Input, Thermocouple Wiring Hookup TC Wire Color Chart

Page 12

2.3.2 Thermocouple Input

The figure below shows the wiring hookup for any thermocouple type.

For example, for Type K hookup, connect the yellow wire to the "2" terminal and the red wire to the "1(-)" terminal.

When configuring your controller, select Thermocouple and Thermocouple Type in the Input Type menu (see Part 3).

Figure 2.4 Thermocouple Wiring Hookup

Table 2.4 TC Wire Color Chart

TYPE

Input Connector

Jacket (external insulation)

 

Terminal 1 (-)

Terminal 2 (+)

Extension

Grade

J

Red

White

dark-Brown

Black

K

Red

Yellow

dark-Brown

Yellow

T

Red

Blue

dark-Brown

Blue

E

Red

Purple

dark-Brown

Purple

N

Red

Orange

dark-Brown

Brown

R

Red

Black

-

Green

S

Red

Black

-

Green

B

Red

Gray

-

Black

If the input wires of the meter get disconnected or broken, it will display +OPN “Input (+) Open” message. For safety purpose you may want to set up your alarm to be triggered when input is open. See Alarm 1 and 2 chapters for details.

8

Image 12
Contents Newport Electronics,Inc Newport Electronics,Inc Table of Contents Flow Chart for Alarm 1 Menu Flow Chart for Alarm 2 Menu Input Properties Factory Preset ValuesList of Figures List of TablesTIP Part Introduction DescriptionSafety Considerations EMC ConsiderationsBefore You Begin Part Setup Optional Remote Programmer Front PanelPower Front Panel ConnectionsInput OutputElectrical Installation Power Connections Main Power Connections Fuse Requirement see specificationsThermocouple Wiring Hookup TC Wire Color Chart Thermocouple Input3 Two/Three/Four-Wire RTD Ohm Wiring HookupProcess Current Process VoltageWiring Outputs Isolated Analog Output Wiring Hookup10 Snubber Circuits Wiring Hookup 13 Excitation Output Operation Configuration Mode Introduction Button Function in Configuration ModePart Menu Configuration Flow Chart for ID and Set PointsEntering Your NON-DEFAULT Full Security ID Number Entering Your NON-DEFAULT SETPOINT/ID Security ID NumberID Number Set Points SetpointConfiguration Menu Enter Configuration MenuInput Type Menu Input Type Thermocouple Enter Input Type MenuThermocouple Submenu Thermocouple TypesInput Type RTD RTD SubmenuRTD Types RTD Value SubmenuReading Configuration Menu Input Type ProcessProcess Submenu Process TypesEnter Reading Configuration Menu Temperature Unit SubmenuDecimal Point Submenu Filter Constant SubmenuReading Configuration If Process was selected INPUT/READING Scale and Offset SubmenuConversion Table Range Conversion NumberAlarm Enter Alarm 1 MenuAlarm 1 ENABLE/DISABLE Submenu Alarm 1 ABSOLUTE/DEVIATION SubmenuAlarm 1 LATCH/UNLATCH Submenu Contact Closure Submenu Active SubmenuAlarm ENABLE/DISABLE AT Power on Alarm 1 LOW Value SubmenuAlarm 1 HI Value Submenu Enter Alarm 2 Menu Loop Break ENABLE/DISABLE Submenu Loop Break Time/Field CalibrationEnter Loop Break Time Menu Loop Break Time Value SubmenuReading Adjust Submenu Setpoint Deviation ENABLE/DISABLE SubmenuThermocouple Field Calibration Submenu Flow Chart for Output OutputEnter Output 1 Menu Self SubmenuMINIMUM/PERCENT LOW Submenu MAXIMUM/PERCENT High Submenu Control Type Output Relay, SSR, or PulseAction Type Submenu Auto PID Submenu Anti Integral SubmenuStart Auto Tune PID Proportional Band SubmenuReset Setup Submenu Rate Setup SubmenuCycle Time Submenu Damping Factor Submenu Deadband SubmenuAnalog Output Retransmission Enter Analog Output MenuCURRENT/VOLTAGE Submenu Reading OUTRamp ENABLE/DISABLE Submenu Soak ENABLE/DISABLE SubmenuRamp & Soak Enter Ramp and Soak MenuRamp Value Submenu Soak Value SubmenuEntering or Changing Your NON-DEFAULT ID Code ID CodeEnter ID Code Menu Entering or Changing Your Default ID Code Full Security Level SubmenuSETPOINT/ID Security Level Submenu 12 Flow Chart for Communication Option Communication OptionEnter Communication Option Menu Communication Parameters SubmenuBaud Submenu Parity SubmenuStop BIT Submenu BUS Format SubmenuModbus Protocol Submenu Line Feed SubmenuData Flow Mode Submenu Communication Interface Standard SubmenuData Separation Character Submenu Alarm Status Submenu Data Format SubmenuMain Reading Submenu Peak Value SubmenuAddress Setup Submenu Address Value SubmenuTransmit Time Interval Submenu Transmit Time Interval Value SubmenuAlarm 1 Display Color Submenu Display Color SelectionEnter Display Color Selection Menu Normal Color Display SubmenuAlarm 2 Display Color Submenu ExampleDisplay Colors change sequences Green RED AmberAmber RED Green Part Specifications Control Control OutputSSR CommunicationsExcitation InsulationGeneral Input Properties Input Type Range AccuracyPart 5 Factory Preset Values Factory preset valueDisplay Color Colr Part CE Approvals Information Measurement CategoryPage Page Page Warranty/Disclaimer M4165/N/0206