RESET SETUP SUBMENU:
Press d 33) Display flashes 1st digit of the previous I REST Reset value. Press b & c 34) Press b and c buttons to enter a new “Reset” value. Press d 35) Display shows STRD stored message momentarily and then
advances to RATE only, if it was changed, otherwise press a to advance to RATE Rate Setup Submenu.
Reset unit is in seconds
RATE SETUP SUBMENU:
Press d 36) Display flashes 1st digit of previous D RATE Rate value. Press b & c 37) Press b and c buttons to enter a new RATE value.
Press d 38) Display shows STRD stored message momentarily and then
advances to the CYCL only, if it was changed, otherwise press a to advance to CYCL Cycle Time submenu for RTD and
Thermocouple types.
Rate unit is in seconds
CYCLE TIME SUBMENU:
Press d 39) Display flashes 1st digit of the previous CYCL Cycle Time value.
Press b & c 40) Press b and c buttons to enter a new “Cycle Time” value. (1 to 199 seconds)
Press d 41) Display shows STRD stored message momentarily and then advances to DPNG only, if it was changed, otherwise press a to advance to DPNG Damping Factor Submenu.
A Cycle Time selected between 1 and 199 seconds determines the total On/Off time of each proportional cycle. For example, a 15 second cycle time means that every 15 seconds the output will turn on for part or all of the cycle. For Relay control outputs, do not select a cycle time of less than 7 seconds or the relays’ lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or DC pulse. Use an external SSR with the DC pulse option for higher currents (higher than 1 Amp).
37