a/d/s/ iSeries manual Auto PID Submenu, Anti Integral Submenu

Page 39

If “ON/OFF” was selected in the Control Type, the display skips to the Dead Band Submenu.

AUTO PID SUBMENU:

Press d 21) Display flashes ENBL or DSBL.

Press b 22) Scroll through the available selections: “Enable” or “Disable”. Press d 23) Display shows STRD stored message momentarily and then advances to ANTL only, if it was changed, otherwise press a to

advance to ANTL Anti Integral Submenu.

If “Enabled”, the controller can determine, by enabling Start PID, the optimum values for the three adjustments — Proportional, Reset and Rate corresponding to P, I, and D. These values may be changed once the Auto Tuning is complete.

If “Disabled” is selected, the user will manually enter these three adjustment values. If you want the instrument to do the Auto PID and the P , PI or PID, first select Auto Disable and enter 0000 for unwanted parameter. i.e. for PI enter 0000 for the rate.

ANTI INTEGRAL SUBMENU:

Press d 24) Display flashes ENBL or DSBL.

Press b 25) Scroll through the available selections: “Enable” or “Disable”. Press d 26) Display shows STRD stored message momentarily and then advances to STRT only, if it was changed, otherwise press a to advance to STRT to Start Auto Tune PID Submenu (If Auto PID

was Enabled).

If Auto PID was disabled display advances to PRoP

Proportional Band Submenu.

If Anti Integral (Anti Windup) Submenu “Enabled”, this feature allows the error term outside the proportional band to be calculated and accumulated for integration. This may be an important feature in applications where fast response time is desirable.

35

Image 39
Contents Newport Electronics,Inc Newport Electronics,Inc Table of Contents List of Tables Flow Chart for Alarm 1 Menu Flow Chart for Alarm 2 MenuInput Properties Factory Preset Values List of FiguresTIP Description Part IntroductionEMC Considerations Safety ConsiderationsBefore You Begin Optional Remote Programmer Front Panel Part SetupOutput PowerFront Panel Connections InputMain Power Connections Fuse Requirement see specifications Electrical Installation Power ConnectionsThermocouple Input Thermocouple Wiring Hookup TC Wire Color ChartOhm Wiring Hookup 3 Two/Three/Four-Wire RTDProcess Voltage Process CurrentIsolated Analog Output Wiring Hookup Wiring Outputs10 Snubber Circuits Wiring Hookup 13 Excitation Output Operation Configuration Mode Introduction Button Function in Configuration ModePart Flow Chart for ID and Set Points Menu ConfigurationEntering Your NON-DEFAULT Full Security ID Number Entering Your NON-DEFAULT SETPOINT/ID Security ID NumberID Number Setpoint Set PointsConfiguration Menu Enter Configuration MenuInput Type Menu Thermocouple Types Input Type ThermocoupleEnter Input Type Menu Thermocouple SubmenuRTD Value Submenu Input Type RTDRTD Submenu RTD TypesProcess Types Reading Configuration MenuInput Type Process Process SubmenuFilter Constant Submenu Enter Reading Configuration MenuTemperature Unit Submenu Decimal Point SubmenuINPUT/READING Scale and Offset Submenu Reading Configuration If Process was selectedRange Conversion Number Conversion TableEnter Alarm 1 Menu AlarmAlarm 1 ENABLE/DISABLE Submenu Alarm 1 ABSOLUTE/DEVIATION SubmenuAlarm 1 LATCH/UNLATCH Submenu Active Submenu Contact Closure SubmenuAlarm ENABLE/DISABLE AT Power on Alarm 1 LOW Value SubmenuAlarm 1 HI Value Submenu Enter Alarm 2 Menu Loop Break Time Value Submenu Loop Break ENABLE/DISABLE SubmenuLoop Break Time/Field Calibration Enter Loop Break Time MenuReading Adjust Submenu Setpoint Deviation ENABLE/DISABLE SubmenuThermocouple Field Calibration Submenu Output Flow Chart for OutputEnter Output 1 Menu Self SubmenuMINIMUM/PERCENT LOW Submenu MAXIMUM/PERCENT High Submenu Control Type Output Relay, SSR, or PulseAction Type Submenu Anti Integral Submenu Auto PID SubmenuProportional Band Submenu Start Auto Tune PIDReset Setup Submenu Rate Setup SubmenuCycle Time Submenu Deadband Submenu Damping Factor SubmenuAnalog Output Retransmission Enter Analog Output MenuCURRENT/VOLTAGE Submenu OUT ReadingEnter Ramp and Soak Menu Ramp ENABLE/DISABLE SubmenuSoak ENABLE/DISABLE Submenu Ramp & SoakSoak Value Submenu Ramp Value SubmenuEntering or Changing Your NON-DEFAULT ID Code ID CodeEnter ID Code Menu Entering or Changing Your Default ID Code Full Security Level SubmenuSETPOINT/ID Security Level Submenu Communication Option 12 Flow Chart for Communication OptionParity Submenu Enter Communication Option MenuCommunication Parameters Submenu Baud SubmenuLine Feed Submenu Stop BIT SubmenuBUS Format Submenu Modbus Protocol SubmenuData Flow Mode Submenu Communication Interface Standard SubmenuData Separation Character Submenu Peak Value Submenu Alarm Status SubmenuData Format Submenu Main Reading SubmenuTransmit Time Interval Value Submenu Address Setup SubmenuAddress Value Submenu Transmit Time Interval SubmenuNormal Color Display Submenu Alarm 1 Display Color SubmenuDisplay Color Selection Enter Display Color Selection MenuGreen RED Amber Alarm 2 Display Color SubmenuExample Display Colors change sequencesAmber RED Green Part Specifications Communications ControlControl Output SSRExcitation InsulationGeneral Input Type Range Accuracy Input PropertiesFactory preset value Part 5 Factory Preset ValuesDisplay Color Colr Measurement Category Part CE Approvals InformationPage Page Page Warranty/Disclaimer M4165/N/0206