a/d/s/ iSeries manual Contact Closure Submenu, Active Submenu

Page 31
Press d

CONTACT CLOSURE SUBMENU:

Press d 11) Display flashes previous selection. Press b to N.ç. Normally Closed or N.o. Normally Open.

12) Display shows STRD stored message momentarily and then advances to AçTV only, if it was changed, otherwise press a to advance to AçTV Active Submenu.

Normally Open: If this feature is selected, then the relay is "energized" only when an alarm condition occurs.

Normally Closed: "Fail Safe" Mode. Relay is energized under "normal" conditions and becomes de-energized during alarm or power failure.

ACTIVE SUBMENU:

Press d 13) Display flashes previous selection. Press b to scroll through the available selections: ABoV Above, BELo Below, HI.Lo HI/Low and BAND Band. (Band is active if _DEV Deviation was selected).

Press d 14) Display shows STRD stored message momentarily and then advances to A.P.oN only, if it was changed, otherwise press a to

advance to A.P.oN Alarm Enable/Disable at Power On Submenu.

Above: Alarm 1 condition triggered when the process variable is greater than the Alarm Hi Value (Low value ignored).

Below: Alarm 1 condition triggered when the process variable is less than the Alarm Low Value (Hi value ignored).

Hi/Low: Alarm 1 condition triggered when the process variable is less than the Alarm Low Value or above the Hi Value.

Band: Alarm 1 condition triggered when the process variable is above or below the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A "band" is set around the Setpoint by the instrument only in the "Deviation" Mode.

The Band for the AL 1 would be following the Setpoint 1 value The Band for the AL 2 would be following the Setpoint 2 value. The Band or the Deviation Value should be entered under:

AL1 High (if they want Alarm 1) AL2 High (if they want Alarm 2)

AL Low value is ignored in the Band mode.

Example: if customer requires a Deviation Value of ±10 degrees around a setpoint (using Output 2 as alarm)

Alarm 2: - Deviation

Contact Closure type: Deviation---Band

AL2 High: 10 (Band they want around Setpoint 2)

Then the Band Value is to be entered under AL2 HI: 10 not 80+10 = 90

27

Image 31
Contents Newport Electronics,Inc Newport Electronics,Inc Table of Contents List of Tables Flow Chart for Alarm 1 Menu Flow Chart for Alarm 2 MenuInput Properties Factory Preset Values List of FiguresTIP Description Part IntroductionEMC Considerations Safety ConsiderationsBefore You Begin Optional Remote Programmer Front Panel Part SetupOutput PowerFront Panel Connections InputMain Power Connections Fuse Requirement see specifications Electrical Installation Power ConnectionsThermocouple Input Thermocouple Wiring Hookup TC Wire Color ChartOhm Wiring Hookup 3 Two/Three/Four-Wire RTDProcess Voltage Process CurrentIsolated Analog Output Wiring Hookup Wiring Outputs10 Snubber Circuits Wiring Hookup 13 Excitation Output Button Function in Configuration Mode Operation Configuration Mode IntroductionPart Flow Chart for ID and Set Points Menu ConfigurationEntering Your NON-DEFAULT SETPOINT/ID Security ID Number Entering Your NON-DEFAULT Full Security ID NumberID Number Setpoint Set PointsEnter Configuration Menu Configuration MenuInput Type Menu Thermocouple Types Input Type ThermocoupleEnter Input Type Menu Thermocouple SubmenuRTD Value Submenu Input Type RTDRTD Submenu RTD TypesProcess Types Reading Configuration MenuInput Type Process Process SubmenuFilter Constant Submenu Enter Reading Configuration MenuTemperature Unit Submenu Decimal Point SubmenuINPUT/READING Scale and Offset Submenu Reading Configuration If Process was selectedRange Conversion Number Conversion TableEnter Alarm 1 Menu AlarmAlarm 1 ABSOLUTE/DEVIATION Submenu Alarm 1 ENABLE/DISABLE SubmenuAlarm 1 LATCH/UNLATCH Submenu Active Submenu Contact Closure SubmenuAlarm 1 LOW Value Submenu Alarm ENABLE/DISABLE AT Power onAlarm 1 HI Value Submenu Enter Alarm 2 Menu Loop Break Time Value Submenu Loop Break ENABLE/DISABLE SubmenuLoop Break Time/Field Calibration Enter Loop Break Time MenuSetpoint Deviation ENABLE/DISABLE Submenu Reading Adjust SubmenuThermocouple Field Calibration Submenu Output Flow Chart for OutputSelf Submenu Enter Output 1 MenuMINIMUM/PERCENT LOW Submenu Control Type Output Relay, SSR, or Pulse MAXIMUM/PERCENT High SubmenuAction Type Submenu Anti Integral Submenu Auto PID SubmenuProportional Band Submenu Start Auto Tune PIDRate Setup Submenu Reset Setup SubmenuCycle Time Submenu Deadband Submenu Damping Factor SubmenuEnter Analog Output Menu Analog Output RetransmissionCURRENT/VOLTAGE Submenu OUT ReadingEnter Ramp and Soak Menu Ramp ENABLE/DISABLE SubmenuSoak ENABLE/DISABLE Submenu Ramp & SoakSoak Value Submenu Ramp Value SubmenuID Code Entering or Changing Your NON-DEFAULT ID CodeEnter ID Code Menu Full Security Level Submenu Entering or Changing Your Default ID CodeSETPOINT/ID Security Level Submenu Communication Option 12 Flow Chart for Communication OptionParity Submenu Enter Communication Option MenuCommunication Parameters Submenu Baud SubmenuLine Feed Submenu Stop BIT SubmenuBUS Format Submenu Modbus Protocol SubmenuCommunication Interface Standard Submenu Data Flow Mode SubmenuData Separation Character Submenu Peak Value Submenu Alarm Status SubmenuData Format Submenu Main Reading SubmenuTransmit Time Interval Value Submenu Address Setup SubmenuAddress Value Submenu Transmit Time Interval SubmenuNormal Color Display Submenu Alarm 1 Display Color SubmenuDisplay Color Selection Enter Display Color Selection MenuGreen RED Amber Alarm 2 Display Color SubmenuExample Display Colors change sequencesAmber RED Green Part Specifications Communications ControlControl Output SSRInsulation ExcitationGeneral Input Type Range Accuracy Input PropertiesFactory preset value Part 5 Factory Preset ValuesDisplay Color Colr Measurement Category Part CE Approvals InformationPage Page Page Warranty/Disclaimer M4165/N/0206