READING ADJUST SUBMENU:

Press d 10) Display flashes 1st digit of previous reading adjust value. Press b & c 11) Press b and c buttons to enter a new Reading Adjust value

(-1999 to 9999).

Press d 12) Display shows STRD stored message momentarily and then advances to SP.DV Setpoint Deviation Menu.

Reading Offset Adjust allows the user to fine tune a minor error of the transducer, however some applications may require a large offset adjust.

(Displayed Process Value = Measured Process Value ± R.ADJ).

Reading Adjust is adjustable between -1999 to 9999. For Temperature reading only, not Process.

SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:

Press d 13) Display advances to Setpoint Deviation ENBL Enable or DSBL Disable Submenu and flashes the previous selection.

Press b 14) Scroll through the available selections: ENBL or DSBL. Press d 15) Display shows STRD stored message momentarily and then

advances to the CAL1° Menu.

Setpoint Deviation Submenu, if “enabled”, allows changes to Setpoint 1 to be made automatically to Setpoint 2. This mode is very helpful if the Process Value changes often. In Setpoint Deviation Mode, set SP2 a certain number of degrees or counts away from SP1 - this relation remains fixed when SP1 is changed. For instance: Setting SP1=200 and SP2=20 and enabling SP.DV means that the absolute value of SP2=20. Moving SP1 to 300, the absolute value of SP2 becomes 320.

THERMOCOUPLE FIELD CALIBRATION SUBMENU:

CAUTION: Do not perform the following steps until you fully understand this entire section.

RTD and Process are perfectly calibrated. This section is applicable to Thermocouple (TC) calibration only.

Be sure that the TC being used to calibrate the meter is of the type selected in the TC submenu. Place the TC in an ice-bath (or other

0°C / 32°F environment). In ambient temperature conditions: connect the TC to the meter, apply power to the meter.

CAUTION: Do not proceed with TC calibration unless the above conditions have been in effect for at least one hour.

Press

a

16)

Display shows CAL

1

.

 

 

 

 

°

 

Press

d

17)

Display shows flashing 0000 .

Press

a

18)

Display will still show flashing 0000 .

Press

d

19)

Display shows OUT1 (meaning Calibration is complete)

*If you accidently engage the flashing 0000 (CAL° alert) simply re-press the last button you pressed, to avoid unintentionally mis-calibrating your meter.

31

Image 35
Contents Newport Electronics,Inc Newport Electronics,Inc Table of Contents List of Tables Flow Chart for Alarm 1 Menu Flow Chart for Alarm 2 MenuInput Properties Factory Preset Values List of FiguresTIP Description Part IntroductionEMC Considerations Safety ConsiderationsBefore You Begin Optional Remote Programmer Front Panel Part SetupOutput PowerFront Panel Connections InputMain Power Connections Fuse Requirement see specifications Electrical Installation Power ConnectionsThermocouple Input Thermocouple Wiring Hookup TC Wire Color ChartOhm Wiring Hookup 3 Two/Three/Four-Wire RTDProcess Voltage Process CurrentIsolated Analog Output Wiring Hookup Wiring Outputs10 Snubber Circuits Wiring Hookup 13 Excitation Output Part Operation Configuration Mode IntroductionButton Function in Configuration Mode Flow Chart for ID and Set Points Menu ConfigurationID Number Entering Your NON-DEFAULT Full Security ID NumberEntering Your NON-DEFAULT SETPOINT/ID Security ID Number Setpoint Set PointsInput Type Menu Configuration MenuEnter Configuration Menu Thermocouple Types Input Type ThermocoupleEnter Input Type Menu Thermocouple SubmenuRTD Value Submenu Input Type RTDRTD Submenu RTD TypesProcess Types Reading Configuration MenuInput Type Process Process SubmenuFilter Constant Submenu Enter Reading Configuration MenuTemperature Unit Submenu Decimal Point SubmenuINPUT/READING Scale and Offset Submenu Reading Configuration If Process was selectedRange Conversion Number Conversion TableEnter Alarm 1 Menu AlarmAlarm 1 LATCH/UNLATCH Submenu Alarm 1 ENABLE/DISABLE SubmenuAlarm 1 ABSOLUTE/DEVIATION Submenu Active Submenu Contact Closure SubmenuAlarm 1 HI Value Submenu Alarm ENABLE/DISABLE AT Power onAlarm 1 LOW Value Submenu Enter Alarm 2 Menu Loop Break Time Value Submenu Loop Break ENABLE/DISABLE SubmenuLoop Break Time/Field Calibration Enter Loop Break Time MenuThermocouple Field Calibration Submenu Reading Adjust SubmenuSetpoint Deviation ENABLE/DISABLE Submenu Output Flow Chart for OutputMINIMUM/PERCENT LOW Submenu Enter Output 1 MenuSelf Submenu Action Type Submenu MAXIMUM/PERCENT High SubmenuControl Type Output Relay, SSR, or Pulse Anti Integral Submenu Auto PID SubmenuProportional Band Submenu Start Auto Tune PIDCycle Time Submenu Reset Setup SubmenuRate Setup Submenu Deadband Submenu Damping Factor SubmenuCURRENT/VOLTAGE Submenu Analog Output RetransmissionEnter Analog Output Menu OUT ReadingEnter Ramp and Soak Menu Ramp ENABLE/DISABLE SubmenuSoak ENABLE/DISABLE Submenu Ramp & SoakSoak Value Submenu Ramp Value SubmenuEnter ID Code Menu Entering or Changing Your NON-DEFAULT ID CodeID Code SETPOINT/ID Security Level Submenu Entering or Changing Your Default ID CodeFull Security Level Submenu Communication Option 12 Flow Chart for Communication OptionParity Submenu Enter Communication Option MenuCommunication Parameters Submenu Baud SubmenuLine Feed Submenu Stop BIT SubmenuBUS Format Submenu Modbus Protocol SubmenuData Separation Character Submenu Data Flow Mode SubmenuCommunication Interface Standard Submenu Peak Value Submenu Alarm Status SubmenuData Format Submenu Main Reading SubmenuTransmit Time Interval Value Submenu Address Setup SubmenuAddress Value Submenu Transmit Time Interval SubmenuNormal Color Display Submenu Alarm 1 Display Color SubmenuDisplay Color Selection Enter Display Color Selection MenuGreen RED Amber Alarm 2 Display Color SubmenuExample Display Colors change sequencesAmber RED Green Part Specifications Communications ControlControl Output SSRGeneral ExcitationInsulation Input Type Range Accuracy Input PropertiesFactory preset value Part 5 Factory Preset ValuesDisplay Color Colr Measurement Category Part CE Approvals InformationPage Page Page Warranty/Disclaimer M4165/N/0206