a/d/s/ iSeries manual MAXIMUM/PERCENT High Submenu, Control Type Output Relay, SSR, or Pulse

Page 38

MAXIMUM/PERCENT HIGH SUBMENU:

Specify in percent, the maximum value (99) for control output. If the output is time proportional (Relay, SSR, or Pulse), then the maximum duty-cycle, in percent, is specified.

Press d 12) Display flashes 1st digit of previous “Percent High” setting. Press b & c 13) Use b and c buttons to enter a new value for “Percent High”. Press d 14) Display shows STRD stored message momentarily and then

advances to CTRL Control Type Submenu.

Example: On an Analog Output of 0~10 Vdc, a setting of %LO = 10 and %HI = 90, cause the minimum on the control output to be 1 V and the maximum on the control output to be 9 V. The same setting on a time proportional output, will cause 10% duty cycle for the minimum control output and 90% duty cycle for maximum control output. To disable %LO/HI, set LO to 00 and HI to 99. If %LO/HI is at other values than the default (%LO = 00, %HI = 99), SOAK is disabled.

*CONTROL TYPE OUTPUT: (Relay, SSR, or Pulse)

Press d 15) Display flashes ON.OF On/Off or PID Proportional, Integral, Derivative.

Press b 16) Scroll through the available selections: “ON/OFF” or “PID”. Press d 17) Display flashes STRD stored message momentarily and

then advances to AçTN only, if it was changed, otherwise press a to advance to AçTN Action Type Submenu.

The ON/OFF control is a coarse way of controlling the process. The “Dead Band” improves the cycling associated with the On/Off control. The PID control is best for processes where the set point is continuously changing and/or a tight control of the process variable is required. PID control requires tuning and adjustment of the "Proportional", "Integral or Reset" and "Derivative or Rate" terms by a trial-and-error method. The instrument provides an "Auto Tuning" feature making the tuning process automatic, possibly optimum.

ACTION TYPE SUBMENU:

The error that results from the measurement of the Process Variable may be positive or negative since it may be greater or smaller than the Setpoint. If a positive error should cause the instrument output to increase (i.e. cooling), it would be called Direct Acting. If a negative error should cause the output to increase (i.e. heating), it would be called Reverse Acting.

Press

d

18)

Display flashes DRçT Direct or RVRS Reverse.

Press

b

19)

Scroll through the available selections: “Direct” or “Reverse”.

Press d

20)

Display shows STRD stored message momentarily and then

advances to AUTo only, if it was changed, otherwise press a to advance to AUTo Auto PID Submenu (if PID Control Type was selected).

34

Image 38
Contents Newport Electronics,Inc Newport Electronics,Inc Table of Contents List of Figures Flow Chart for Alarm 1 Menu Flow Chart for Alarm 2 MenuInput Properties Factory Preset Values List of TablesTIP Part Introduction DescriptionSafety Considerations EMC ConsiderationsBefore You Begin Part Setup Optional Remote Programmer Front PanelInput PowerFront Panel Connections OutputElectrical Installation Power Connections Main Power Connections Fuse Requirement see specificationsThermocouple Wiring Hookup TC Wire Color Chart Thermocouple Input3 Two/Three/Four-Wire RTD Ohm Wiring HookupProcess Current Process VoltageWiring Outputs Isolated Analog Output Wiring Hookup10 Snubber Circuits Wiring Hookup 13 Excitation Output Part Operation Configuration Mode IntroductionButton Function in Configuration Mode Menu Configuration Flow Chart for ID and Set PointsID Number Entering Your NON-DEFAULT Full Security ID NumberEntering Your NON-DEFAULT SETPOINT/ID Security ID Number Set Points SetpointInput Type Menu Configuration MenuEnter Configuration Menu Thermocouple Submenu Input Type ThermocoupleEnter Input Type Menu Thermocouple TypesRTD Types Input Type RTDRTD Submenu RTD Value SubmenuProcess Submenu Reading Configuration MenuInput Type Process Process TypesDecimal Point Submenu Enter Reading Configuration MenuTemperature Unit Submenu Filter Constant SubmenuReading Configuration If Process was selected INPUT/READING Scale and Offset SubmenuConversion Table Range Conversion NumberAlarm Enter Alarm 1 MenuAlarm 1 LATCH/UNLATCH Submenu Alarm 1 ENABLE/DISABLE SubmenuAlarm 1 ABSOLUTE/DEVIATION Submenu Contact Closure Submenu Active SubmenuAlarm 1 HI Value Submenu Alarm ENABLE/DISABLE AT Power onAlarm 1 LOW Value Submenu Enter Alarm 2 Menu Enter Loop Break Time Menu Loop Break ENABLE/DISABLE SubmenuLoop Break Time/Field Calibration Loop Break Time Value SubmenuThermocouple Field Calibration Submenu Reading Adjust SubmenuSetpoint Deviation ENABLE/DISABLE Submenu Flow Chart for Output OutputMINIMUM/PERCENT LOW Submenu Enter Output 1 MenuSelf Submenu Action Type Submenu MAXIMUM/PERCENT High SubmenuControl Type Output Relay, SSR, or Pulse Auto PID Submenu Anti Integral SubmenuStart Auto Tune PID Proportional Band SubmenuCycle Time Submenu Reset Setup SubmenuRate Setup Submenu Damping Factor Submenu Deadband SubmenuCURRENT/VOLTAGE Submenu Analog Output RetransmissionEnter Analog Output Menu Reading OUTRamp & Soak Ramp ENABLE/DISABLE SubmenuSoak ENABLE/DISABLE Submenu Enter Ramp and Soak MenuRamp Value Submenu Soak Value SubmenuEnter ID Code Menu Entering or Changing Your NON-DEFAULT ID CodeID Code SETPOINT/ID Security Level Submenu Entering or Changing Your Default ID CodeFull Security Level Submenu 12 Flow Chart for Communication Option Communication OptionBaud Submenu Enter Communication Option MenuCommunication Parameters Submenu Parity SubmenuModbus Protocol Submenu Stop BIT SubmenuBUS Format Submenu Line Feed SubmenuData Separation Character Submenu Data Flow Mode SubmenuCommunication Interface Standard Submenu Main Reading Submenu Alarm Status SubmenuData Format Submenu Peak Value SubmenuTransmit Time Interval Submenu Address Setup SubmenuAddress Value Submenu Transmit Time Interval Value SubmenuEnter Display Color Selection Menu Alarm 1 Display Color SubmenuDisplay Color Selection Normal Color Display SubmenuDisplay Colors change sequences Alarm 2 Display Color SubmenuExample Green RED AmberAmber RED Green Part Specifications SSR ControlControl Output CommunicationsGeneral ExcitationInsulation Input Properties Input Type Range AccuracyPart 5 Factory Preset Values Factory preset valueDisplay Color Colr Part CE Approvals Information Measurement CategoryPage Page Page Warranty/Disclaimer M4165/N/0206