a/d/s/ iSeries manual Loop Break Time/Field Calibration, Enter Loop Break Time Menu

Page 34

3.2.8 Loop Break Time/Field Calibration

It is required that you put the controller in the Standby Mode

for any configuration change other than Set Points & Alarms.

Figure 3.7 Flow Chart for Loop Break Time/Field Calibration

ENTER LOOP BREAK TIME MENU:

Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu.

Press a 3) Press a, if necessary, until Display advances to LOOP Loop Break Time Menu.

Press d 4) Display advances to Loop Break Time ENBL Enable or DSBL Disable Submenu and flashes the previous selection.

LOOP BREAK ENABLE/DISABLE SUBMENU:

Press b 5) Scroll through the available selections: ENBL or DSBL. Press d 6) Display shows STRD stored message momentarily and then

advances to B.TIM Loop Break Time Value Submenu.

Loop Break is an additional safety feature intended to monitor the rate of change of the process value, while approaching the SP1. It is strictly intended as an additional warning system, therefore its use is entirely optional. An active Loop Break will cause the Process Value digits to blink in a rotating pattern. If the process value reaches the set point the blinking will stop and B.TIM is completed successfully, otherwise BR.AL Break Alarm warning will flash, and Output 1 will be turned off.

LOOP BREAK TIME VALUE SUBMENU:

Press d 7) Display flashes 1st digit of previous Loop Value.

Press b & c 8) Press b and c buttons to enter a new Loop Value (0 to 99.59). Press d 9) Display shows STRD stored message momentarily and then

advances to R.ADJ Reading Adjust Submenu.

Loop Break Time Value allows the user to determine the time interval in MM:SS (from zero to 99 minutes and 59 seconds) that the Process Value changes at least 10 counts or if the Input Type is either RTD or Thermocouple, the value changes 4° Fahrenheit or 2° Celsius. At the specified time interval, if the process value change is less than the stated rate, flashing B.TIM will be displayed, the output 1 will be de-energized, and Alarm 1 energized. Loop break time will be disabled when the Process Value (PV) enters the control band.

30

Image 34
Contents Newport Electronics,Inc Newport Electronics,Inc Table of Contents List of Figures Flow Chart for Alarm 1 Menu Flow Chart for Alarm 2 MenuInput Properties Factory Preset Values List of TablesTIP Part Introduction DescriptionSafety Considerations EMC ConsiderationsBefore You Begin Part Setup Optional Remote Programmer Front PanelInput PowerFront Panel Connections OutputElectrical Installation Power Connections Main Power Connections Fuse Requirement see specificationsThermocouple Wiring Hookup TC Wire Color Chart Thermocouple Input3 Two/Three/Four-Wire RTD Ohm Wiring HookupProcess Current Process VoltageWiring Outputs Isolated Analog Output Wiring Hookup10 Snubber Circuits Wiring Hookup 13 Excitation Output Button Function in Configuration Mode Operation Configuration Mode IntroductionPart Menu Configuration Flow Chart for ID and Set PointsEntering Your NON-DEFAULT SETPOINT/ID Security ID Number Entering Your NON-DEFAULT Full Security ID NumberID Number Set Points SetpointEnter Configuration Menu Configuration MenuInput Type Menu Thermocouple Submenu Input Type ThermocoupleEnter Input Type Menu Thermocouple TypesRTD Types Input Type RTDRTD Submenu RTD Value SubmenuProcess Submenu Reading Configuration MenuInput Type Process Process TypesDecimal Point Submenu Enter Reading Configuration MenuTemperature Unit Submenu Filter Constant SubmenuReading Configuration If Process was selected INPUT/READING Scale and Offset SubmenuConversion Table Range Conversion NumberAlarm Enter Alarm 1 MenuAlarm 1 ABSOLUTE/DEVIATION Submenu Alarm 1 ENABLE/DISABLE SubmenuAlarm 1 LATCH/UNLATCH Submenu Contact Closure Submenu Active SubmenuAlarm 1 LOW Value Submenu Alarm ENABLE/DISABLE AT Power onAlarm 1 HI Value Submenu Enter Alarm 2 Menu Enter Loop Break Time Menu Loop Break ENABLE/DISABLE SubmenuLoop Break Time/Field Calibration Loop Break Time Value SubmenuSetpoint Deviation ENABLE/DISABLE Submenu Reading Adjust SubmenuThermocouple Field Calibration Submenu Flow Chart for Output OutputSelf Submenu Enter Output 1 MenuMINIMUM/PERCENT LOW Submenu Control Type Output Relay, SSR, or Pulse MAXIMUM/PERCENT High SubmenuAction Type Submenu Auto PID Submenu Anti Integral SubmenuStart Auto Tune PID Proportional Band SubmenuRate Setup Submenu Reset Setup SubmenuCycle Time Submenu Damping Factor Submenu Deadband SubmenuEnter Analog Output Menu Analog Output RetransmissionCURRENT/VOLTAGE Submenu Reading OUTRamp & Soak Ramp ENABLE/DISABLE SubmenuSoak ENABLE/DISABLE Submenu Enter Ramp and Soak MenuRamp Value Submenu Soak Value SubmenuID Code Entering or Changing Your NON-DEFAULT ID CodeEnter ID Code Menu Full Security Level Submenu Entering or Changing Your Default ID CodeSETPOINT/ID Security Level Submenu 12 Flow Chart for Communication Option Communication OptionBaud Submenu Enter Communication Option MenuCommunication Parameters Submenu Parity SubmenuModbus Protocol Submenu Stop BIT SubmenuBUS Format Submenu Line Feed SubmenuCommunication Interface Standard Submenu Data Flow Mode SubmenuData Separation Character Submenu Main Reading Submenu Alarm Status SubmenuData Format Submenu Peak Value SubmenuTransmit Time Interval Submenu Address Setup SubmenuAddress Value Submenu Transmit Time Interval Value SubmenuEnter Display Color Selection Menu Alarm 1 Display Color SubmenuDisplay Color Selection Normal Color Display SubmenuDisplay Colors change sequences Alarm 2 Display Color SubmenuExample Green RED AmberAmber RED Green Part Specifications SSR ControlControl Output CommunicationsInsulation ExcitationGeneral Input Properties Input Type Range AccuracyPart 5 Factory Preset Values Factory preset valueDisplay Color Colr Part CE Approvals Information Measurement CategoryPage Page Page Warranty/Disclaimer M4165/N/0206