a/d/s/ iSeries Enter Reading Configuration Menu, Decimal Point Submenu, Temperature Unit Submenu

Page 26

ENTER READING CONFIGURATION MENU:

Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu.

Press a 3) Display advances to RDG Reading Configuration Menu. Press d 4) Display advances to DEC Decimal Point.

DECIMAL POINT SUBMENU:

Press d 5) Display flashes previous selection for Decimal location.

Press b 6) Scroll though the available selections and choose Decimal location: FFFF or FFF.F (also FF.FF and F.FFF — if PROC

Process type was selected in the Input Type Menu).

Press d 7) Display shows STRD stored message momentarily and then advances to TEMP Temperature Unit.

Decimal Point for Process Input Type is passive.

TEMPERATURE UNIT SUBMENU:

Press d 8) Display flashes previous Temperature Unit selection.

Press b 9) Scroll though the available selections to the Temperature Unit of your choice: °F or °C.

Press d 10) Display shows STRD stored message momentarily and then advances to FLTR Filter Constant.

FILTER CONSTANT SUBMENU:

Press d 11) Display flashes previous selection for Filter Constant.

Press b 12) Scroll though the available selections: 0001, 0002, 0004, 0008, 0016, 0032, 0064, 0128. - Default is 0004

Press d 13) Display shows STRD stored message momentarily only, if a change was made, otherwise press a to advance to the next menu.

If Process was selected in the Input Type Menu the display will advance to IN.RD Input/Reading Submenu, otherwise the display advances to the ALR1 Alarm 1 Menu.

The Filter Constant Submenu allows the user to specify the number of readings stored in the Digital Averaging Filter.

For PID control select filter value 0001-0004. A filter value of 2 is approximately equal to 1 second RC low pass time constant.

22

Image 26
Contents Newport Electronics,Inc Newport Electronics,Inc Table of Contents List of Figures Flow Chart for Alarm 1 Menu Flow Chart for Alarm 2 MenuInput Properties Factory Preset Values List of TablesTIP Part Introduction DescriptionSafety Considerations EMC ConsiderationsBefore You Begin Part Setup Optional Remote Programmer Front PanelInput PowerFront Panel Connections OutputElectrical Installation Power Connections Main Power Connections Fuse Requirement see specificationsThermocouple Wiring Hookup TC Wire Color Chart Thermocouple Input3 Two/Three/Four-Wire RTD Ohm Wiring HookupProcess Current Process VoltageWiring Outputs Isolated Analog Output Wiring Hookup10 Snubber Circuits Wiring Hookup 13 Excitation Output Part Operation Configuration Mode IntroductionButton Function in Configuration Mode Menu Configuration Flow Chart for ID and Set PointsID Number Entering Your NON-DEFAULT Full Security ID NumberEntering Your NON-DEFAULT SETPOINT/ID Security ID Number Set Points SetpointInput Type Menu Configuration MenuEnter Configuration Menu Thermocouple Submenu Input Type ThermocoupleEnter Input Type Menu Thermocouple TypesRTD Types Input Type RTDRTD Submenu RTD Value SubmenuProcess Submenu Reading Configuration MenuInput Type Process Process TypesDecimal Point Submenu Enter Reading Configuration MenuTemperature Unit Submenu Filter Constant SubmenuReading Configuration If Process was selected INPUT/READING Scale and Offset SubmenuConversion Table Range Conversion NumberAlarm Enter Alarm 1 MenuAlarm 1 LATCH/UNLATCH Submenu Alarm 1 ENABLE/DISABLE SubmenuAlarm 1 ABSOLUTE/DEVIATION Submenu Contact Closure Submenu Active SubmenuAlarm 1 HI Value Submenu Alarm ENABLE/DISABLE AT Power onAlarm 1 LOW Value Submenu Enter Alarm 2 Menu Enter Loop Break Time Menu Loop Break ENABLE/DISABLE SubmenuLoop Break Time/Field Calibration Loop Break Time Value SubmenuThermocouple Field Calibration Submenu Reading Adjust SubmenuSetpoint Deviation ENABLE/DISABLE Submenu Flow Chart for Output OutputMINIMUM/PERCENT LOW Submenu Enter Output 1 MenuSelf Submenu Action Type Submenu MAXIMUM/PERCENT High SubmenuControl Type Output Relay, SSR, or Pulse Auto PID Submenu Anti Integral SubmenuStart Auto Tune PID Proportional Band SubmenuCycle Time Submenu Reset Setup SubmenuRate Setup Submenu Damping Factor Submenu Deadband SubmenuCURRENT/VOLTAGE Submenu Analog Output RetransmissionEnter Analog Output Menu Reading OUTRamp & Soak Ramp ENABLE/DISABLE SubmenuSoak ENABLE/DISABLE Submenu Enter Ramp and Soak MenuRamp Value Submenu Soak Value SubmenuEnter ID Code Menu Entering or Changing Your NON-DEFAULT ID CodeID Code SETPOINT/ID Security Level Submenu Entering or Changing Your Default ID CodeFull Security Level Submenu 12 Flow Chart for Communication Option Communication OptionBaud Submenu Enter Communication Option MenuCommunication Parameters Submenu Parity SubmenuModbus Protocol Submenu Stop BIT SubmenuBUS Format Submenu Line Feed SubmenuData Separation Character Submenu Data Flow Mode SubmenuCommunication Interface Standard Submenu Main Reading Submenu Alarm Status SubmenuData Format Submenu Peak Value SubmenuTransmit Time Interval Submenu Address Setup SubmenuAddress Value Submenu Transmit Time Interval Value SubmenuEnter Display Color Selection Menu Alarm 1 Display Color SubmenuDisplay Color Selection Normal Color Display SubmenuDisplay Colors change sequences Alarm 2 Display Color SubmenuExample Green RED AmberAmber RED Green Part Specifications SSR ControlControl Output CommunicationsGeneral ExcitationInsulation Input Properties Input Type Range AccuracyPart 5 Factory Preset Values Factory preset valueDisplay Color Colr Part CE Approvals Information Measurement CategoryPage Page Page Warranty/Disclaimer M4165/N/0206