Raven Installation Guide | Servo Control Operation |
| |
|
|
4.8Status Indications
The following table lists the Raven amplifier status indications.
|
| Latch |
|
|
|
|
| Function | Option | AOK | SO1 | SO2 | SO3 |
1 | Amplifier OK | N/A | Low | Open collector | Open collector | Open collector |
| (AOK) |
|
|
|
|
|
2 | External disable | No | Low | Low | Open collector | Low |
3 | Current limit | No | Low | Open collector | Open collector | Low |
4 | Short | Yes | Open collector | Low | Open collector | Low |
5 | Over | Yes | Open collector | Open collector | Low | Low |
| temperature |
|
|
|
|
|
6 | Internal supplies | No | Open collector | Low | Low | Open collector |
| protection |
|
|
|
|
|
7 | Under voltage | No | Open collector | Low | Open collector | Open collector |
8 | Over voltage | No | Open collector | Open collector | Low | Open collector |
9 | Shunt* | No | Low | Open collector | Low | Open collector |
10 | Power Up Reset | No | Open collector | Open collector | Open collector | Open collector |
*This indication can be used as a digital input for activating an external shunt regulator.
Table 4-3: Raven Status Indications
Notes:
Without latch mode:
The status indications are reset when the fault disappears.
With latch mode:
The Short and Over Temperature Failure status indications are reset when the enable signal is temporarily removed from the enable input.
Multiple faults:
Only the reading of the first fault is reliable. Additional faults add on to the status outputs and the indication is therefore meaningless.