Pulse Output

4. WIRING

IMPORTANT

• As this is a transistor contact (insulated type),

give attention to proper voltage and polarity

when wiring.

• Do not apply a voltage larger than 30V DC or a

current larger than 0.2A in order to prevent

damage to the instrument.

• When input filter constant of the electronic

counter is large in relation to the pulse width,

AXFA11

P+

PULSE OUT P-

AXFA11 P+

 

 

 

 

PULSE OUT

P-

Load

 

 

 

Output voltage: 24 V DC 20%

Current: 30 to 150 mA

Pulse rate: 0.0001 to 2 pps

Pulse width: 20, 33, 50, 100 ms

Protective diode

Mechanical Counter

Electronic Counter

the signal will decrease and the count will not

be accurate.

• If the input impedance of the electronic counter

is large, an induction noise from the power

supply may result in inaccurate counts. Use a

shield cable or sufficiently reduce the input

impedance of the electronic counter within the

electromagnetic flowmeter pulse output specifi-

cation range.

• The active pulse output (Optional Code EM)

cannot be used in conjunction with the standard

pulse output.

• When the active pulse output (Optional Code

EM) is selected, do not be short-circuit between

the P+ and P– terminals to avoid damaging the

instrument.

• When the active pulse output (Optional code

EM) is selected, the range of pulse rate must

be set to 2 pps maximum.

• To avoid communication (BRAIN/ HART)

failure, it is recommended to use the shield

cable.

AXFA11

 

Protective diode

P+

 

PULSE OUT

P-

Mechanical Counter

 

 

AXFA11

P+

 

PULSE OUT

Load

Electronic Counter

 

P-

 

 

30V DC, 0.2A. max

 

 

F0418.EPS

Figure 4.4.10 Pulse Output Connection

F0419.EPS

Figure 4.4.11 Active Pulse Output (Optional code EM)

Status Input

IMPORTANT

Status inputs are designed for use with no- voltage (dry) contacts. Be careful not to connect the status to any signal source carrying voltage. Applying voltage may damage the input circuit.

Closed: Less than 200

Open: More than 100 k

AXFA11

SI1+

SI2+

COM

No-voltage status input

F0420.EPS

Figure 4.4.12 Status Input Connection

4-8

IM 01E20C01-01E

Image 18
Contents Users ManualAXFA11G Contents Operation VIA Hart Communicator Revision Record Safety and Modification Precautions IntroductionUsing the Magnetic Flowmeter Safely WarrantyGuarantee will not apply in the following cases Combination Remote Flowtubes Accessories Handling PrecautionsChecking Model and Specifications Storage PrecautionsMounting InstallationInstallation Location Surface Mounting Wall MountingInch pipe Mounting fixture Washer Clamp screw Inch Pipe MountingPanel Mounting Unit mm approx. inch Panel cutout 203 Mounting fixture 172Dedicated Signal Cable Axfc WiringWiring Precautions CablesUnit mm approx. inch Crimp Terminal Wiring PortsExcitation Cable/Power Cable/Output Cable On the converter sideConduit Wiring When there are no particular optional specificationsWiring using waterproof glands Plastic glandWiring Connections Terminal ConfigurationRemoving Cover Precautions for Wiring of Power Supply Cables DC Power ConnectionGrounding Wiring the Remote Flowtube with the AXFA11 ConverterAxfc Dedicated signal cable Excitation cable Protective grounding terminalsConnecting to External Instru- ments To 20 mA DC Current OutputPulse Output Status InputStatus Output / Alarm Output 13 Status Output ConnectionOperating Panel Configuration and Functions Setting switch operationsData display area Reversed-character indication ContentDisplay items NoneDisplay Unit Setting Methods Display Mode → Setting ModeSetting Mode To Parameter Search Mode Parameter Setting Procedure Setting ModeSetting Example for Selection-Type Data Flow rate units B21 Base Flow Unit Sub-item Current unit settingSub-item Parameter Search Mode Parameter Sub-itemMajor Item Parameter Search Mode Setting mode Setting Example for Numeric-Type Data Flow rate spanSetting Mode Condition B23 Flow SpanSub-item Parameter Search Mode Major item Setting Example for Alphanumeric-Type Data Tag numberSetting Mode Condition Incorrect settingSearch Mode Selection C Sub-item Major itemModified value Parameter Description Item B Menu B Easy Setup items Item a Menu a Display itemsDefault value Units Description Display unit Name Data rangeIndicated item Item C Menu C Basic Setting items Name Data range Position Default value Units Display unitName Data range Position Default value Display unit Item D Menu D Total Setting itemsDefault value Units Display unit NameItem E Menu E Pulse Setting items Item F Menu F Status Functions Setting itemsItem G Menu G Alarm Setting items ALM OUT ACT ALM-SETTINGALM HYS ALM-SIG OverItem H Menu H Display Setting items Item J Menu J Auxiliary Function Setting itemsItem K Menu K Diagnostic Function Setting items Units Display unitItem N Menu N Loop Test Setting items Item P Menu P Parameter Protection itemsMenu B Easy Setup items Data RangeExample When 1000 m3/h is set for B23/C42 Flow Span Unit/P 10-9 FU u Unit/P 10-6 FU Pulse/sDescription Menu C Basic Setting items B41/H11 Display Select2 and B42/H12 DisplayMeter Factor Settings C49 Flow User Span Menu D Total Setting itemsC47 User Span Select Selection of the use Is set forB22/C41 Base Time UnitFlow Unit TOTAL, and A32 DIF Total when BrainF13 Is set forB22/C41 Base TimeMenu E Pulse Setting items Setting for E20 Pulse Active ModeE20 Pulse Active Mode Switch Lower and D24 Ttl Switch Upper Menu F Status Functions Setting itemsSetting Function Description G33 Alm-HH/LL to YesNo Function No input function Val UpperStatus Output for Automatic Multiple Ranges Switching Multiple ranges settingMultiple Ranges Setting Automatic multiple ranges switching 1 Status Output for Automatic Multiple Ranges SwitchingF14 SO1/2 Active Mode Parameter setting sequenceFor automatic multiple ranges switching F10 SO1 Function F11 SO2 Function2 Multiple Ranges Switching via External Status Input F15Menu G Alarm Setting items G10 Low Alarm Low alarm settingG11 High Alarm High alarm setting 100 High Alarm Instantaneous flow rate Low Low Alarm Time t High High Alarm100 High Alarm Output Example100 100 85% 75% High Alarm35% Low Alarm 25%G22 4-20mA Burn Out Display of the current Setting FunctionExample ClosedOn OpenOffG43 Alm Record2 Alarm record2 G41 Alm Record1 Alarm record1Alarm Items G45 Alm Record3 Alarm record3Menu J Auxiliary Function Setting items Setting range 0 to 10% HysteresisExample 1 Step input Function orDetermining rate limit value and dead time Example 2 Slurry noiseK10 Adhesion Check Setting of adhesion J31 Power FrequencyMenu K Diagnostic Function Setting items Power Supply Code 100 to 240 V AC or 100 to 120 V DCMenu N Loop Test Setting items Adhesion Diagnostic FunctionMenu M Automatic Zero Adjustment Function Setting items SO1 Function or F11 SO2 Function, thenMenu P Parameter Protection items N11 Test Output Value Setting for test outputDefault setting Enable Write Protect functionDefault setting After password settingG20 Alm Out Act Mode Setting of the active Display and output condition for process alarmsOut Act Mode Totali Pulse Display Alarm Display and output condition for setting alarm occurrencesAlarm description Selection Output UnitAlarms & Warning Messages K12, K13 and K14 are correct Key Descriptions Operation VIA Brain Terminal BT200BT200 Basic Operations Key Layout and DisplayCommand Function Function KeysKey-in Sequence AXFA11 Operation Using a BT200 Data update and upload/ download function of BT2001 BT200 Connection Parameter Setting Using a BT200 3 BT200 Screens & Flow Rate Data Display1 BT200 Setting of Selection-Type Data Flow rate units Moved to B Easy SetupB21 Flow UNIT, press 2 BT200 Setting of Numeric-Type Data Flow rate span B23 Flow SPAN, press3 BT200 Setting of Alphanumeric-Type Data Tag number To C Basic SetupMoved to C Basic Setup Operation VIA Hart Communicator Interconnectwion between AXFA11 and Hart Communicator Specifications for Communication LineConditions of Communication Line Communication Line RequirementsBasic Operation of the Hart Communicator Model Keys and FunctionsDisplay Calling Up Menu AddressesKey Operation Parameters Entering, Setting and Sending DataParameter Configuration Data RenewingChecking for Problems Setting ParametersExample of Setting Selection-Type Data Base Flow Unit Example of Setting Numeric-Type Data PV Span PV SpanExample of Setting Alphanumeric-Type Data Tag Number DisplayExample 1 of Other Settings Meter Factor Select MF SetSelect Power Frequency Example 3 of Other Settings Trim Analog Output TrimReturning fld dev to original output appears Select the Scaled D/A trim Returning fld dev to original output appears Exiting Burst Mode Example 4 of Other Settings Burst ModeSetting of Burst Mode Example 5 of Other Settings Multidrop ModePolling Exiting Multidrop Mode Example 6 of Other Settings Write ProtectionSetting Password Open Wrt Protect Menu in the Hot key MenuChanging Password Enable Wrt 10minJoker password and Software Seal Other Functions and OperationsMenu Tree On nextE12 J24 J30 P22 P23 Pre-operation Zero Adjustment Actual OperationZero Adjustment Using Display Unit Switches Selection D Major item Sub- item selection DZero Adjustment via External Status Input Ext Auto Zero Display Unit Replacement MaintenanceComponents Replacement Fuse ReplacementSetting of Burnout Switch Setting of SwitchesAmplifier Replacement Output Setting Pins for BurnoutSetting of Write Protect Switch 4 Switch ConfigurationTroubleshooting No IndicationUnstable Zero StartDisagreement Between Indication and Actual Flow Outline 65 10 Cf 10,000How to Set Parameters FunctionsStandard Performance Power Supply Power supply code Maximum Power ConsumptionSafety Requirement Standards Size 2200 mm 88 in. to 2600 mm 104Accessories Optional Specifications for AXFA11 Remote Converter Terminal WiringRemote Converter AXFA11G Surface mountingRemote Converter AXFA11G /RK AM11 Replacement Bracket General tolerance in the dimensional outline drawingDedicated Signal Cable AXFC-4-L AXFC-0-LRevision Record Edition Date Revised item