This parameter selects the display content of the second line for display unit.
[H12: Display Select3] Setting of the third line for display unit
→Refer to the description for parameter B42
This parameter selects the display content of the third line for display unit.
[H20: Display Cycle] Setting of the display cycle This parameter sets the cycle for the
6. PARAMETER DESCRIPTION
value is required for the lower limit.
The indications of the instantaneous flow rates (%, Actual instantaneous flow rate, mA, Bar graph) on the display unit are the same action.
Example: Situation where low limit is set to 10%
Output
5.6mA(10%)
speed of display unit. Settings should be made in accordance with the measurement environment by, for example, setting a longer display cycle when using the equipment in low temperatures.
4mA
NOTE
Input
F0655.EPS
[H30: Language] Selection of language used for the display unit.
→Refer to the description for parameter B10
This parameter can be used to select the language for display unit.
If “2.4mA or less” has been set
NOTE
(8) Menu J: Auxiliary Function Setting items
Menu J contains setting items such as the flow direc- tion, rate limits, and current output limits.
[J10:
This parameter is used to force current output to 0%(i.e., 4mA) in the vicinity of 0% and setting for the current (4 to 20mA) output low cut is made using a percentage of the smallest flow rate span. However, the low cut function will be terminated if this parameter is set to 0%.
The indications of the instantaneous flow rates (%, Actual instantaneous flow rate, mA, Bar graph) on the display unit are the same action.
Example: Situation where low cut is set to 10%
•If the setting value for the low limit is not less than the high limit value (as set using J12: 4- 20mA High Lmt), the setting alarm
•This parameter has no effect on pulse output or the totalization function.
[J12:
This parameter is used to restrict high current portions of current (4 to 20mA) output, and it is initially set to 120%. Setting should be performed when a lower value is required for the higher limit.
The indications of the instantaneous flow rates (%, Actual instantaneous flow rate, mA, Bar graph) on the display unit are the same action.
Output | Setting value |
5.6mA(10%) |
|
|
4mA | 0.5% | 0.5% |
Input | ||
Setting range: 0 to 10% |
| Hysteresis |
|
| fixed at 1% |
|
| F0615.EPS |
[J11:
This parameter is used to restrict low current portions of current (4 to 20mA) output, and it is initially set to
Example: Situation where high limit is set to 90%
Output |
18.4mA(90%) |
4mA |
Input |
F0656.EPS |
NOTE |
If “21.6mA or more” has been set
IM |