8. OPERATION VIA HART COMMUNICATOR
8.3.4.5Example 2 of Other Settings: Power Frequency (For DC version only)
IMPORTANT
In situation where a DC power supply is used for converters, set the local com- mercial power frequency in area where the converter is lnstalled. The flowmeter is set to 50.00 Hz at the factory.
Set “No” forPower“ Synch” and the local commercial power frequency for “Power Frequency”.
Open the “Power freq” setting display:
1. Device Setup 4. Detailed Setup 4. Function Set 5. Aux Power Frequency
⋅ 9
1 |
| AXFA11 : |
|
|
|
|
| Select “Power Frequency”. | |||||||
|
| Aux |
|
|
|
|
|
|
|
|
|
|
|
| |
| 6 | Dead Time | Os |
|
|
| |||||||||
| 7 | Pulsing Flow | No |
|
|
| |||||||||
|
|
|
| ||||||||||||
| 8 | T/P Damp Select |
|
|
|
|
|
| |||||||
| 9 | Power Synch | No |
|
|
| |||||||||
|
|
|
| Power Frequency |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| SAVE |
| HOME |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2AXFA11 :
50.00Hz
DEL ESC ENTER
3AXFA11 :
DEL ESC ENTER
4AXFA11 :
Aux |
|
| |
6 | Dead Time | Os | |
7 | Pulsing Flow | No | |
8 | T/P Damp Select |
| |
9 | Power Synch | No | |
|
| Power Frequency |
|
SAVE HOME
‘60.0’
F4
(ENTER)
F2
(SEND)
F3
(HOME)
Enter “60.00” with alphanumeric keys.
Press ENTER (F4).
Press SEND (F2) to set the data into the AXFA11.
Press HOME (F3), and return to the “Online” menu.
F0813.EPS