APC AXFA11G Function or, Determining rate limit value and dead time, Example 1 Step input

Page 59

[J20: Flow Direction] Setting of the flow direction Upon shipment from the manufacturing plant, the system is setup such that flow in the same direction, as shown by the direction of the arrow mark on the flowtube, will be measured as forward flow; however, this parameter can be used to set “Reverse” so that flow in the opposite direction to the arrow mark will be treated as forward.

Note: This function does not apply to measurement in both the forward and reverse directions, al- though this can be setup using by selecting “Fwd/Rev Ranges” from either F10: SO1

Function or

.

Setting

 

Function

 

 

Forward

Forward direction corresponds with arrow mark

 

 

Reverse

Forward direction is opposite to arrow mark

 

 

 

T0638.EPS

[J21: Rate Limit] Setting of the rate limit value

￿This parameter is used in situations where sudden noise cannot be eliminated by increasing the damping time constant.

￿In situations where step signals or sudden noise signals caused by slurries or the like are entered, this parameter is used to set the standard for determining whether an input corresponds to a flow measurement or noise. Specifically, this determination is made using upper and lower rate limits and using the dead time.

￿Rate limit values are set using a percentage of the smallest range. The range of deviation per one calculation cycle should be input.

[J22: Dead Time] Setting of dead time

This parameter sets the time for application of the rate limit, and if a value of 0 is set, the rate limit function will be terminated.

NOTE

Determining rate limit value and dead time

Rate limit value:

Dead time (T0):

Determines the level for output

This is to be determined using the

fluctuation cutoff. For example,

output fluctuation width. If noise

if this is set to 2%, noise above

exceeds the dead time as shown in

2% will be eliminated as shown

the diagram below, the dead time

in the diagram.

should be made longer.

 

 

 

 

 

 

 

 

 

 

 

 

T0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F0616.EPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.PARAMETER DESCRIPTION

￿Signal processing method:

A fixed upper and lower limit value is setup with respect to the primary delay response value for the flow rate value obtained during the previous sam- pling, and if the currently sampled flow rate is outside these limits, then the corresponding limit is adopted as the current flow rate value. In addition, if signals which breach the limits in the same direction occur over multiple samples (i.e., within the dead time), it is concluded that the corresponding signal is a flow rate signal.

Example 1: Step input

 

 

 

 

 

 

Input: 0 to 10%

 

 

 

 

Damping time constant: 3 s

 

 

 

 

Dead time: 3 s

Step signal

 

 

Rate limit value: 1%

 

 

 

10%

 

 

 

 

 

Flow rate value

63.2%

 

after rate limit

 

 

 

 

 

processing

 

 

 

(a)

(b)

(c)

(d)Flow rate value after

 

 

1%

 

 

 

damping

 

100

 

225

Number of signal samples

 

Dead time: 3 s

 

 

F0617.EPS

(1)In comparison with the previous value at (a), it is determined that the signal is in excess of the rate limit value and the response becomes 1%. How- ever, the actual output applies damping, and therefore the output turns out to be as indicated by the solid line.

(2)Subsequent flow values within the dead time zone correspond to signals of post-damping flow value + rate limit value (1%).

(3)Since input signals do not return to within the rate limit value during the dead time, it is determined at

(c) that this signal is a flow rate signal.

(4)The output signal becomes a damped curve and compliance with the step signal begins.

Three seconds after determination of a flow rate signal in the above figure, a level of 63.2% is reached.

Example 2: Slurry noise

 

 

 

Input: 0 to 10%

 

Slurry noise

Damping time constant: 1 s

 

Flow rate value

Dead time: 1 s

 

Rate limit value: 1%

 

after rate limit

 

 

+1%

processing

 

-1%

 

In the figure on the left, it is

 

determined that the slurries

 

 

 

Flow rate value after damping

noise signal is not a flow rate

 

signal.

 

 

 

Dead time: 1 s

Time

 

F0618.EPS

6-31

IM 01E20C01-01E

Image 59
Contents Users ManualAXFA11G Contents Operation VIA Hart Communicator Revision Record Introduction Safety and Modification PrecautionsGuarantee will not apply in the following cases Using the Magnetic Flowmeter SafelyWarranty Combination Remote Flowtubes Storage Precautions Handling PrecautionsChecking Model and Specifications AccessoriesSurface Mounting Wall Mounting InstallationInstallation Location MountingUnit mm approx. inch Panel cutout 203 Mounting fixture 172 Inch Pipe MountingPanel Mounting Inch pipe Mounting fixture Washer Clamp screwCables WiringWiring Precautions Dedicated Signal Cable AxfcOn the converter side Wiring PortsExcitation Cable/Power Cable/Output Cable Unit mm approx. inch Crimp TerminalPlastic gland When there are no particular optional specificationsWiring using waterproof glands Conduit WiringRemoving Cover Wiring ConnectionsTerminal Configuration DC Power Connection Precautions for Wiring of Power Supply CablesProtective grounding terminals Wiring the Remote Flowtube with the AXFA11 ConverterAxfc Dedicated signal cable Excitation cable GroundingTo 20 mA DC Current Output Connecting to External Instru- mentsStatus Input Pulse Output13 Status Output Connection Status Output / Alarm OutputData display area Operating Panel Configuration and FunctionsSetting switch operations None ContentDisplay items Reversed-character indicationDisplay Mode → Setting Mode Display Unit Setting MethodsSetting Mode To Parameter Search Mode Setting Example for Selection-Type Data Flow rate units Parameter Setting ProcedureSetting Mode Parameter Sub-item Sub-item Current unit settingSub-item Parameter Search Mode B21 Base Flow UnitB23 Flow Span Setting Example for Numeric-Type Data Flow rate spanSetting Mode Condition Major Item Parameter Search Mode Setting modeIncorrect setting Setting Example for Alphanumeric-Type Data Tag numberSetting Mode Condition Sub-item Parameter Search Mode Major itemModified value Search Mode Selection CSub-item Major item Parameter Description Item a Menu a Display items Item B Menu B Easy Setup itemsIndicated item Default value Units Description Display unitName Data range Name Data range Position Default value Units Display unit Item C Menu C Basic Setting itemsName Item D Menu D Total Setting itemsDefault value Units Display unit Name Data range Position Default value Display unitItem F Menu F Status Functions Setting items Item E Menu E Pulse Setting itemsItem G Menu G Alarm Setting items ALM-SIG Over ALM-SETTINGALM HYS ALM OUT ACTItem J Menu J Auxiliary Function Setting items Item H Menu H Display Setting itemsUnits Display unit Item K Menu K Diagnostic Function Setting itemsItem P Menu P Parameter Protection items Item N Menu N Loop Test Setting itemsData Range Menu B Easy Setup itemsUnit/P 10-9 FU u Unit/P 10-6 FU Pulse/s Example When 1000 m3/h is set for B23/C42 Flow SpanDescription B41/H11 Display Select2 and B42/H12 Display Menu C Basic Setting itemsMeter Factor Settings Is set forB22/C41 Base Time Unit Menu D Total Setting itemsC47 User Span Select Selection of the use C49 Flow User SpanIs set forB22/C41 Base Time TOTAL, and A32 DIF Total when BrainF13 Flow UnitE20 Pulse Active Mode Menu E Pulse Setting itemsSetting for E20 Pulse Active Mode G33 Alm-HH/LL to Yes Menu F Status Functions Setting itemsSetting Function Description Switch Lower and D24 Ttl Switch UpperVal Upper No Function No input function1 Status Output for Automatic Multiple Ranges Switching Multiple ranges settingMultiple Ranges Setting Automatic multiple ranges switching Status Output for Automatic Multiple Ranges SwitchingF10 SO1 Function F11 SO2 Function Parameter setting sequenceFor automatic multiple ranges switching F14 SO1/2 Active ModeF15 2 Multiple Ranges Switching via External Status InputG11 High Alarm High alarm setting Menu G Alarm Setting itemsG10 Low Alarm Low alarm setting Output Example High High Alarm100 High Alarm 100 High Alarm Instantaneous flow rate Low Low Alarm Time t25% 100 85% 75% High Alarm35% Low Alarm 100ClosedOn OpenOff Setting FunctionExample G22 4-20mA Burn Out Display of the currentG45 Alm Record3 Alarm record3 G41 Alm Record1 Alarm record1Alarm Items G43 Alm Record2 Alarm record2Setting range 0 to 10% Hysteresis Menu J Auxiliary Function Setting itemsExample 2 Slurry noise Function orDetermining rate limit value and dead time Example 1 Step inputPower Supply Code 100 to 240 V AC or 100 to 120 V DC J31 Power FrequencyMenu K Diagnostic Function Setting items K10 Adhesion Check Setting of adhesionSO1 Function or F11 SO2 Function, then Adhesion Diagnostic FunctionMenu M Automatic Zero Adjustment Function Setting items Menu N Loop Test Setting itemsWrite Protect function N11 Test Output Value Setting for test outputDefault setting Enable Menu P Parameter Protection itemsAfter password setting Default settingOut Act Mode G20 Alm Out Act Mode Setting of the activeDisplay and output condition for process alarms Output Unit Display and output condition for setting alarm occurrencesAlarm description Selection Totali Pulse Display AlarmAlarms & Warning Messages K12, K13 and K14 are correct Key Layout and Display Operation VIA Brain Terminal BT200BT200 Basic Operations Key DescriptionsKey-in Sequence Command FunctionFunction Keys 1 BT200 Connection AXFA11 Operation Using a BT200Data update and upload/ download function of BT200 3 BT200 Screens & Flow Rate Data Display Parameter Setting Using a BT200B21 Flow UNIT, press 1 BT200 Setting of Selection-Type Data Flow rate unitsMoved to B Easy Setup B23 Flow SPAN, press 2 BT200 Setting of Numeric-Type Data Flow rate spanMoved to C Basic Setup 3 BT200 Setting of Alphanumeric-Type Data Tag numberTo C Basic Setup Operation VIA Hart Communicator Communication Line Requirements Specifications for Communication LineConditions of Communication Line Interconnectwion between AXFA11 and Hart CommunicatorKeys and Functions Basic Operation of the Hart Communicator ModelKey Operation DisplayCalling Up Menu Addresses Data Renewing Entering, Setting and Sending DataParameter Configuration ParametersExample of Setting Selection-Type Data Base Flow Unit Checking for ProblemsSetting Parameters PV Span Example of Setting Numeric-Type Data PV SpanDisplay Example of Setting Alphanumeric-Type Data Tag NumberSelect MF Set Example 1 of Other Settings Meter FactorSelect Power Frequency Trim Example 3 of Other Settings Trim Analog OutputReturning fld dev to original output appears Select the Scaled D/A trim Returning fld dev to original output appears Example 5 of Other Settings Multidrop Mode Example 4 of Other Settings Burst ModeSetting of Burst Mode Exiting Burst ModePolling Example 6 of Other Settings Write Protection Exiting Multidrop ModeOpen Wrt Protect Menu in the Hot key Menu Setting PasswordEnable Wrt 10min Changing PasswordOther Functions and Operations Joker password and Software SealOn next Menu TreeE12 J24 J30 P22 P23 Actual Operation Pre-operation Zero AdjustmentSelection D Major item Sub- item selection D Zero Adjustment Using Display Unit SwitchesZero Adjustment via External Status Input Ext Auto Zero Fuse Replacement MaintenanceComponents Replacement Display Unit ReplacementOutput Setting Pins for Burnout Setting of SwitchesAmplifier Replacement Setting of Burnout Switch4 Switch Configuration Setting of Write Protect SwitchNo Indication TroubleshootingStart Unstable ZeroDisagreement Between Indication and Actual Flow 65 10 Cf 10,000 OutlineFunctions How to Set ParametersStandard Performance Size 2200 mm 88 in. to 2600 mm 104 Maximum Power ConsumptionSafety Requirement Standards Power Supply Power supply codeAccessories Terminal Wiring Optional Specifications for AXFA11 Remote ConverterSurface mounting Remote Converter AXFA11GGeneral tolerance in the dimensional outline drawing Remote Converter AXFA11G /RK AM11 Replacement BracketAXFC-0-L Dedicated Signal Cable AXFC-4-LEdition Date Revised item Revision Record