[D20: Total Execution] Operation setting for the totalization function

This parameter sets “Start” and “Stop” of the totaliza- tion function, in addition to performing the preset function for the forward totalized value and the reverse totalized value.

*: The preset function starts the count for totalization from the set value.

Item

Description

 

 

Start (initial value)

Starts totalization

 

 

Stop

Stop totalization

 

 

Preset Total

Sets the preset value for totalization display that has

 

been specified as the forward totalized value. Preset

 

value are determined using D21: Ttl Set Val Lower

 

and D22: Ttl Set Val Upper.

 

In case that “Start” is sellected, the count for

 

totalization starts from the preset value. Setting of zero

 

as the preset value allows the zero-reset function to be

 

implemented.

 

 

Preset Rev Total

Sets the preset value for totalization display that has

 

been specified as the reverse totalized value. Preset

 

value are determined using D21: Ttl Set Val Lower

 

and D22: Ttl Set Val Upper.

 

In case that “Start” is sellected, the count for

 

totalization starts from the preset value. Setting of zero

 

as the preset value allows the zero-reset function to be

 

implemented.

 

 

 

T0620.EPS

NOTE

Totalization presets can also be set up by using status input. For details regarding the setting method, refer to the descriptions of F12 and

F13.

[D21: Ttl Set Val Lower] Setting of the totalization preset value (lower 6 digits)

This parameter sets a totalization preset value in the lower 6 digits of the 8-digit totalized value. If zero is to be set as the preset value, “000000” should be set here.

[D22: Ttl Set Val Upper] Setting of the totalization preset value (upper 2 digits)

This parameter sets a totalization preset value in the upper 2 digits of the 8-digit totalized value. If zero is to be set as the preset value, “00” should be set here.

Lower 6 digits

Upper 2 digits

F0602.EPS

6. PARAMETER DESCRIPTION

[D23: Ttl Switch Lower] Setting of the totalization switch value (lower 6 digits)

The totalization switch function operates to set the status output terminal (i.e., SO1 or SO2) to “Closed (On)” when the forward internal totalized value reaches or exceeds the totalization switch value. (For details regarding the setting method for the status output, refer to the descriptions of parameters F10 and F11.)

If this function is set up, the totalization count will stop at 99999999.

D23 sets the lower 6 digits of the 8-digit totalization switch value.

[D24: Ttl Switch Upper] Setting of the totalization switch value (upper 2 digits)

This parameter sets the upper 2 digits of the 8-digit totalization switch value.

[D30: Ttl User Select] Selection of the use of special totalization unit

This parameter specifies whether or not special units are used for totalized units. Actual setting of these units is carried out using D31: Ttl User Unit.

[D31: Ttl User Unit] Setting of special totalization units

Units of up to maximum 8 characters in length can be specified using this parameter. The units set with this parameter are displayed whenever totalization (i.e., FTL, RTL, DTL) is selected in the Display Mode, and they are displayed for A30: TOTAL, A31: REV

TOTAL, and A32: DIF TOTAL when BRAIN

communication is being carried out.

NOTE

Example:

To count in 1 dl (deci-liter) steps

 

with flow rate span=10 l/s.

 

Since 1 dl (deci-liter) = 0.1 l (liter),

 

“l (Liter)” is set forB21/C40: Base

 

Flow Unit,

 

“/s” is set forB22/C41: Base Time

 

Unit,

 

“10” is set forB23/C42: Flow

 

Span,

 

“Unit/P” is set forB30/D10: Total

 

Unit,

 

“0.1” is set forB31/D11: Total

 

Scale,

 

“Yes” is set forD30: Ttl User

 

Select,

6-18

IM 01E20C01-01E

Image 46
Contents Users ManualAXFA11G Contents Operation VIA Hart Communicator Revision Record Safety and Modification Precautions IntroductionWarranty Using the Magnetic Flowmeter SafelyGuarantee will not apply in the following cases Combination Remote Flowtubes Accessories Handling PrecautionsChecking Model and Specifications Storage PrecautionsMounting InstallationInstallation Location Surface Mounting Wall MountingInch pipe Mounting fixture Washer Clamp screw Inch Pipe MountingPanel Mounting Unit mm approx. inch Panel cutout 203 Mounting fixture 172Dedicated Signal Cable Axfc WiringWiring Precautions CablesUnit mm approx. inch Crimp Terminal Wiring PortsExcitation Cable/Power Cable/Output Cable On the converter sideConduit Wiring When there are no particular optional specificationsWiring using waterproof glands Plastic glandTerminal Configuration Wiring ConnectionsRemoving Cover Precautions for Wiring of Power Supply Cables DC Power ConnectionGrounding Wiring the Remote Flowtube with the AXFA11 ConverterAxfc Dedicated signal cable Excitation cable Protective grounding terminalsConnecting to External Instru- ments To 20 mA DC Current OutputPulse Output Status InputStatus Output / Alarm Output 13 Status Output ConnectionSetting switch operations Operating Panel Configuration and FunctionsData display area Reversed-character indication ContentDisplay items NoneDisplay Unit Setting Methods Display Mode → Setting ModeSetting Mode To Parameter Search Mode Setting Mode Parameter Setting ProcedureSetting Example for Selection-Type Data Flow rate units B21 Base Flow Unit Sub-item Current unit settingSub-item Parameter Search Mode Parameter Sub-itemMajor Item Parameter Search Mode Setting mode Setting Example for Numeric-Type Data Flow rate spanSetting Mode Condition B23 Flow SpanSub-item Parameter Search Mode Major item Setting Example for Alphanumeric-Type Data Tag numberSetting Mode Condition Incorrect settingSub-item Major item Search Mode Selection CModified value Parameter Description Item B Menu B Easy Setup items Item a Menu a Display itemsName Data range Default value Units Description Display unitIndicated item Item C Menu C Basic Setting items Name Data range Position Default value Units Display unitName Data range Position Default value Display unit Item D Menu D Total Setting itemsDefault value Units Display unit NameItem E Menu E Pulse Setting items Item F Menu F Status Functions Setting itemsItem G Menu G Alarm Setting items ALM OUT ACT ALM-SETTINGALM HYS ALM-SIG OverItem H Menu H Display Setting items Item J Menu J Auxiliary Function Setting itemsItem K Menu K Diagnostic Function Setting items Units Display unitItem N Menu N Loop Test Setting items Item P Menu P Parameter Protection itemsMenu B Easy Setup items Data RangeExample When 1000 m3/h is set for B23/C42 Flow Span Unit/P 10-9 FU u Unit/P 10-6 FU Pulse/sDescription Menu C Basic Setting items B41/H11 Display Select2 and B42/H12 DisplayMeter Factor Settings C49 Flow User Span Menu D Total Setting itemsC47 User Span Select Selection of the use Is set forB22/C41 Base Time UnitFlow Unit TOTAL, and A32 DIF Total when BrainF13 Is set forB22/C41 Base TimeSetting for E20 Pulse Active Mode Menu E Pulse Setting itemsE20 Pulse Active Mode Switch Lower and D24 Ttl Switch Upper Menu F Status Functions Setting itemsSetting Function Description G33 Alm-HH/LL to YesNo Function No input function Val UpperStatus Output for Automatic Multiple Ranges Switching Multiple ranges settingMultiple Ranges Setting Automatic multiple ranges switching 1 Status Output for Automatic Multiple Ranges SwitchingF14 SO1/2 Active Mode Parameter setting sequenceFor automatic multiple ranges switching F10 SO1 Function F11 SO2 Function2 Multiple Ranges Switching via External Status Input F15G10 Low Alarm Low alarm setting Menu G Alarm Setting itemsG11 High Alarm High alarm setting 100 High Alarm Instantaneous flow rate Low Low Alarm Time t High High Alarm100 High Alarm Output Example100 100 85% 75% High Alarm35% Low Alarm 25%G22 4-20mA Burn Out Display of the current Setting FunctionExample ClosedOn OpenOffG43 Alm Record2 Alarm record2 G41 Alm Record1 Alarm record1Alarm Items G45 Alm Record3 Alarm record3Menu J Auxiliary Function Setting items Setting range 0 to 10% HysteresisExample 1 Step input Function orDetermining rate limit value and dead time Example 2 Slurry noiseK10 Adhesion Check Setting of adhesion J31 Power FrequencyMenu K Diagnostic Function Setting items Power Supply Code 100 to 240 V AC or 100 to 120 V DCMenu N Loop Test Setting items Adhesion Diagnostic FunctionMenu M Automatic Zero Adjustment Function Setting items SO1 Function or F11 SO2 Function, thenMenu P Parameter Protection items N11 Test Output Value Setting for test outputDefault setting Enable Write Protect functionDefault setting After password settingDisplay and output condition for process alarms G20 Alm Out Act Mode Setting of the activeOut Act Mode Totali Pulse Display Alarm Display and output condition for setting alarm occurrencesAlarm description Selection Output UnitAlarms & Warning Messages K12, K13 and K14 are correct Key Descriptions Operation VIA Brain Terminal BT200BT200 Basic Operations Key Layout and DisplayFunction Keys Command FunctionKey-in Sequence Data update and upload/ download function of BT200 AXFA11 Operation Using a BT2001 BT200 Connection Parameter Setting Using a BT200 3 BT200 Screens & Flow Rate Data DisplayMoved to B Easy Setup 1 BT200 Setting of Selection-Type Data Flow rate unitsB21 Flow UNIT, press 2 BT200 Setting of Numeric-Type Data Flow rate span B23 Flow SPAN, pressTo C Basic Setup 3 BT200 Setting of Alphanumeric-Type Data Tag numberMoved to C Basic Setup Operation VIA Hart Communicator Interconnectwion between AXFA11 and Hart Communicator Specifications for Communication LineConditions of Communication Line Communication Line RequirementsBasic Operation of the Hart Communicator Model Keys and FunctionsCalling Up Menu Addresses DisplayKey Operation Parameters Entering, Setting and Sending DataParameter Configuration Data RenewingSetting Parameters Checking for ProblemsExample of Setting Selection-Type Data Base Flow Unit Example of Setting Numeric-Type Data PV Span PV SpanExample of Setting Alphanumeric-Type Data Tag Number DisplayExample 1 of Other Settings Meter Factor Select MF SetSelect Power Frequency Example 3 of Other Settings Trim Analog Output TrimReturning fld dev to original output appears Select the Scaled D/A trim Returning fld dev to original output appears Exiting Burst Mode Example 4 of Other Settings Burst ModeSetting of Burst Mode Example 5 of Other Settings Multidrop ModePolling Exiting Multidrop Mode Example 6 of Other Settings Write ProtectionSetting Password Open Wrt Protect Menu in the Hot key MenuChanging Password Enable Wrt 10minJoker password and Software Seal Other Functions and OperationsMenu Tree On nextE12 J24 J30 P22 P23 Pre-operation Zero Adjustment Actual OperationZero Adjustment Using Display Unit Switches Selection D Major item Sub- item selection DZero Adjustment via External Status Input Ext Auto Zero Display Unit Replacement MaintenanceComponents Replacement Fuse ReplacementSetting of Burnout Switch Setting of SwitchesAmplifier Replacement Output Setting Pins for BurnoutSetting of Write Protect Switch 4 Switch ConfigurationTroubleshooting No IndicationUnstable Zero StartDisagreement Between Indication and Actual Flow Outline 65 10 Cf 10,000How to Set Parameters FunctionsStandard Performance Power Supply Power supply code Maximum Power ConsumptionSafety Requirement Standards Size 2200 mm 88 in. to 2600 mm 104Accessories Optional Specifications for AXFA11 Remote Converter Terminal WiringRemote Converter AXFA11G Surface mountingRemote Converter AXFA11G /RK AM11 Replacement Bracket General tolerance in the dimensional outline drawingDedicated Signal Cable AXFC-4-L AXFC-0-LRevision Record Edition Date Revised item