6. PARAMETER DESCRIPTION
(3) Item C (Menu C): Basic Setting items
Menu C principally contains the basic setting items for the flowtube.
| Name |
| Data range |
| Position | Default value |
| |
|
|
|
| Units |
| |||
Item | Display unit | R/W | Display unit | of decimal | Description | |||
(*): Indicated item | ||||||||
| ||||||||
| (BRAIN) |
| /BRAIN |
| point |
|
| |
C00 | Basic Setup |
|
|
|
|
|
| |
| (BASIC SETUP) |
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
C10 | Tag No | W | ASCII 16 characters |
|
|
| Sets Tag number up to 16 | |
| (TAG NO) |
|
|
|
|
| characters. | |
|
|
|
|
|
|
|
| |
C11 | Flow Damping | W | 0.1 to 200.0 | s | 1 | 3.0 s | Sets damping time. Linked with | |
| (FLOW DAMPING) |
|
|
|
|
| B20. | |
C20 | Measure Mode | W | Standard DF |
|
| Standard DF | Selects measurement mode for | |
| (MEASURE MODE) |
| Enhanced DF |
|
|
| dual frequency excitation | |
C21 | Low MF | W | 0.0100 to 3.0000 |
| 4 | 1.0000 (*) | Sets | |
| (LOW MF) |
|
|
|
|
| standard dual frequency excitation | |
C22 | High MF | W | 0.0100 to 3.0000 |
| 4 | 1.0000 (*) | Sets | |
| (HIGH MF) |
|
|
|
|
| standard dual frequency excitation | |
C23 | Low MF(EDF) | W | 0.0000 to 3.0000 |
| 4 | 1.0000 (*) | Sets | |
| (LOW MF(EDF)) |
|
|
|
|
| enhanced dual frequency excitation | |
C24 | High MF(EDF) | W | 0.0000 to 3.0000 |
| 4 | 1.0000 (*) | Sets | |
| (HIGH MF(EDF)) |
|
|
|
|
| enhanced dual frequency excitation | |
C30 | Select Flow Tube | W | ADMAG AXF |
|
| ADMAG AXF | Selects the flowtube's model | |
| (FLOW TUBE) |
| ADMAG |
|
|
| name. | |
|
|
| ADMAG AE |
|
|
|
| |
|
|
| ADMAG SE |
|
|
|
| |
|
|
| YEWMAG |
|
|
|
| |
|
|
| Calibrator |
|
|
|
| |
|
|
| Other |
|
|
|
| |
C31 | Nominal Size Unit | W | mm |
|
| mm | Selects the nominal size units for | |
| (SIZE UNIT) |
| inch |
|
| inch | the flowtube. | |
C32 | Nominal Size | W | 0.99 to 3000.1 | mm | 0 to 2 | 100 (*) | Sets flowtube nominal size in | |
| (NOMINAL SIZE) |
| 0.01 to 120.1 | inch |
|
| selected unit at C31. | |
C40 | Base Flow Unit | W | Ml(Megaliter) |
|
| m (*) | Selects flow units for the flow | |
| (FLOW UNIT) |
| m3 |
|
|
| rate span. Linked with B21. | |
|
|
| kl(Kiloliter) |
|
|
|
| |
|
|
| l(Liter) |
|
|
|
| |
|
|
| cm3 |
|
|
|
| |
|
|
| m |
|
|
|
| |
|
|
| t |
|
|
|
| |
|
|
| kg |
|
|
|
| |
|
|
| g |
|
|
|
| |
|
|
| kcf |
|
|
|
| |
|
|
| cf |
|
|
|
| |
|
|
| mcf |
|
|
|
| |
|
|
| Mgal (US) |
|
|
|
| |
|
|
| kgal (US) |
|
|
|
| |
|
|
| gal (US) |
|
|
|
| |
|
|
| mgal (US) |
|
|
|
| |
|
|
| kbbl (US Oil) |
|
|
|
| |
|
|
| bbl (US Oil) |
|
|
|
| |
|
|
| mbbl (US Oil) |
|
|
|
| |
|
|
| ubbl (US Oil) |
|
|
|
| |
|
|
| kbbl (US Beer) |
|
|
|
| |
|
|
| bbl (US Beer) |
|
|
|
| |
|
|
| mbbl (US Beer) |
|
|
|
| |
|
|
| ubbl (US Beer) |
|
|
|
| |
|
|
| ft |
|
|
|
| |
|
|
| klb (US) |
|
|
|
| |
|
|
| lb (US) |
|
|
|
| |
C41 | Base Time Unit | W | /d |
|
| /s (*) | Selects time units for the flow | |
| (TIME UNIT) |
| /h |
|
|
| rate span. Linked with B22. | |
|
|
| /min |
|
|
|
| |
|
|
| /s |
|
|
|
| |
|
|
|
|
|
|
|
| |
C42 | Flow Span | W | 0.0001 to 32000 | C40/C41 | 0 to 4 | 1 m/s (*) | Sets flow rate span (with units | |
| (FLOW SPAN) |
|
| (B21 |
|
| from C40 and C41). Linked with | |
|
|
|
| /B22) |
|
| B23. | |
|
|
|
|
|
|
|
| |
C43 | Flow Decimal Pnt | W | Auto |
|
| Auto (*) | Selects decimal point position for | |
| (FLOW DECIMAL) |
| 0 |
|
|
| the display unit's instantaneous | |
|
|
| 1 |
|
|
| flow rate. Linked with B24. | |
|
|
| 2 |
|
|
|
| |
|
|
| 3 |
|
|
|
| |
|
|
|
|
|
|
|
IM |