APC AXFA11G N11 Test Output Value Setting for test output, Menu P Parameter Protection items

Page 62

(3)“Normal” will be restored when the power is turned off or when 30 minutes have elapsed since entry to Test Mode.

(4)In Test Mode, the warning 83: Fix Cur Wng will be displayed as a warning message. (For more details, refer to Section 6.5 Alarm Functions.)

[N11: Test Output Value] Setting for test output

values

During loop testing, current output (4 to 20mA), totalization, and pulse will be output in accordance with this parameter’s setting, and values can be set when “Test” has been selected for N10: Test Mode. With multiple ranges or when performing forward/ reverse flow measurements, setting should be done using a percentage of the maximum range.

[N20: Test SO1] Setting for SO1 output terminal condition during testing

This parameter sets the condition of the SO1 status output terminal during loop testing. Setting is possible when “Test” has been selected for N10: Test Mode.

Setting

Function

 

 

Open (Off)

SO1 output terminal in Open (Off) condition

 

 

Closed (On)

SO1 output terminal in Closed (On) condition

 

 

 

T0645.EPS

[N21: Test SO2] Setting for SO2 output terminal condition during testing

This parameter sets the condition of the SO2 status output terminal during loop testing. Setting is possible when “Test” has been selected for N10: Test Mode.

Setting

Function

Open (Off)

SO2 output terminal in Open (Off) condition

 

 

Closed (On)

SO2 output terminal in Closed (On) condition

 

 

 

T0645-2.EPS

[N22: Test Alarm Out] Setting for alarm terminal condition during testing

This parameter sets the condition of the alarm output terminal (AL) during loop testing.

Setting

Function

Open (Off)

AL output terminal in Open (Off) condition

 

 

Closed (On)

AL output terminal in Closed (On) condition

 

 

 

T0645-3.EPS

[N23: Test SI1] Display for SI1 status input terminal condition during testing

This parameter is used to display the condition of the SI1 status input terminal during loop testing.

 

6. PARAMETER DESCRIPTION

 

 

 

Setting

Function

 

Open

SI1 input terminal in Open condition

 

 

 

 

Short

SI1 input terminal in Short condition

 

 

 

 

 

T0646.EPS

[N24: Test SI2] Display for SI2 status input terminal condition during testing

This parameter is used to display the condition of the SI2 status input terminal during testing.

Setting

Function

 

 

Open

SI2 input terminal in Open condition

 

 

Short

SI2 input terminal in Short condition

 

 

 

T0646-2.EPS

(12) Menu P: Parameter Protection items

Menu P contains items that are relevant to write protection and passwords.

[P10: Key Code] Parameter of the display restriction This parameter restricts access to the Service Mode.

NOTE

Write Protect function

￿The parameters P20 through P23 are set when using the write protect function. Specifi- cally, this function responds to a hardware switch or the setting of a software password, and it protects parameters from being over- written.

￿If the hardware switch is set to “Protect”, it will not be possible to overwrite parameters; furthermore, this condition will be maintained until the switch is set to “Enable”.

￿For more details regarding hardware switch settings, refer to Section 10.2.2: Setting of Write Protect Switch.

[P20: Write Protect] Status indication for write protection

This parameter is used to indicate whether or not write protection is currently on.

Default setting (Enable)

P20:Write Protect

No

F0620.EPS

Write protection (Protect)

P20:Write Protect

Yes

F0621.EPS

6-34

IM 01E20C01-01E

Image 62
Contents Users ManualAXFA11G Contents Operation VIA Hart Communicator Revision Record Safety and Modification Precautions IntroductionGuarantee will not apply in the following cases Using the Magnetic Flowmeter SafelyWarranty Combination Remote Flowtubes Accessories Handling PrecautionsChecking Model and Specifications Storage PrecautionsMounting InstallationInstallation Location Surface Mounting Wall MountingInch pipe Mounting fixture Washer Clamp screw Inch Pipe MountingPanel Mounting Unit mm approx. inch Panel cutout 203 Mounting fixture 172Dedicated Signal Cable Axfc WiringWiring Precautions CablesUnit mm approx. inch Crimp Terminal Wiring PortsExcitation Cable/Power Cable/Output Cable On the converter sideConduit Wiring When there are no particular optional specificationsWiring using waterproof glands Plastic glandRemoving Cover Wiring ConnectionsTerminal Configuration Precautions for Wiring of Power Supply Cables DC Power ConnectionGrounding Wiring the Remote Flowtube with the AXFA11 ConverterAxfc Dedicated signal cable Excitation cable Protective grounding terminalsConnecting to External Instru- ments To 20 mA DC Current OutputPulse Output Status InputStatus Output / Alarm Output 13 Status Output ConnectionData display area Operating Panel Configuration and FunctionsSetting switch operations Reversed-character indication ContentDisplay items NoneDisplay Unit Setting Methods Display Mode → Setting ModeSetting Mode To Parameter Search Mode Setting Example for Selection-Type Data Flow rate units Parameter Setting ProcedureSetting Mode B21 Base Flow Unit Sub-item Current unit settingSub-item Parameter Search Mode Parameter Sub-itemMajor Item Parameter Search Mode Setting mode Setting Example for Numeric-Type Data Flow rate spanSetting Mode Condition B23 Flow SpanSub-item Parameter Search Mode Major item Setting Example for Alphanumeric-Type Data Tag numberSetting Mode Condition Incorrect settingModified value Search Mode Selection CSub-item Major item Parameter Description Item B Menu B Easy Setup items Item a Menu a Display itemsIndicated item Default value Units Description Display unitName Data range Item C Menu C Basic Setting items Name Data range Position Default value Units Display unitName Data range Position Default value Display unit Item D Menu D Total Setting itemsDefault value Units Display unit NameItem E Menu E Pulse Setting items Item F Menu F Status Functions Setting itemsItem G Menu G Alarm Setting items ALM OUT ACT ALM-SETTINGALM HYS ALM-SIG OverItem H Menu H Display Setting items Item J Menu J Auxiliary Function Setting itemsItem K Menu K Diagnostic Function Setting items Units Display unitItem N Menu N Loop Test Setting items Item P Menu P Parameter Protection itemsMenu B Easy Setup items Data RangeExample When 1000 m3/h is set for B23/C42 Flow Span Unit/P 10-9 FU u Unit/P 10-6 FU Pulse/sDescription Menu C Basic Setting items B41/H11 Display Select2 and B42/H12 DisplayMeter Factor Settings C49 Flow User Span Menu D Total Setting itemsC47 User Span Select Selection of the use Is set forB22/C41 Base Time UnitFlow Unit TOTAL, and A32 DIF Total when BrainF13 Is set forB22/C41 Base TimeE20 Pulse Active Mode Menu E Pulse Setting itemsSetting for E20 Pulse Active Mode Switch Lower and D24 Ttl Switch Upper Menu F Status Functions Setting itemsSetting Function Description G33 Alm-HH/LL to YesNo Function No input function Val UpperStatus Output for Automatic Multiple Ranges Switching Multiple ranges settingMultiple Ranges Setting Automatic multiple ranges switching 1 Status Output for Automatic Multiple Ranges SwitchingF14 SO1/2 Active Mode Parameter setting sequenceFor automatic multiple ranges switching F10 SO1 Function F11 SO2 Function2 Multiple Ranges Switching via External Status Input F15G11 High Alarm High alarm setting Menu G Alarm Setting itemsG10 Low Alarm Low alarm setting 100 High Alarm Instantaneous flow rate Low Low Alarm Time t High High Alarm100 High Alarm Output Example100 100 85% 75% High Alarm35% Low Alarm 25%G22 4-20mA Burn Out Display of the current Setting FunctionExample ClosedOn OpenOffG43 Alm Record2 Alarm record2 G41 Alm Record1 Alarm record1Alarm Items G45 Alm Record3 Alarm record3Menu J Auxiliary Function Setting items Setting range 0 to 10% HysteresisExample 1 Step input Function orDetermining rate limit value and dead time Example 2 Slurry noiseK10 Adhesion Check Setting of adhesion J31 Power FrequencyMenu K Diagnostic Function Setting items Power Supply Code 100 to 240 V AC or 100 to 120 V DCMenu N Loop Test Setting items Adhesion Diagnostic FunctionMenu M Automatic Zero Adjustment Function Setting items SO1 Function or F11 SO2 Function, thenMenu P Parameter Protection items N11 Test Output Value Setting for test outputDefault setting Enable Write Protect functionDefault setting After password settingOut Act Mode G20 Alm Out Act Mode Setting of the activeDisplay and output condition for process alarms Totali Pulse Display Alarm Display and output condition for setting alarm occurrencesAlarm description Selection Output UnitAlarms & Warning Messages K12, K13 and K14 are correct Key Descriptions Operation VIA Brain Terminal BT200BT200 Basic Operations Key Layout and DisplayKey-in Sequence Command FunctionFunction Keys 1 BT200 Connection AXFA11 Operation Using a BT200Data update and upload/ download function of BT200 Parameter Setting Using a BT200 3 BT200 Screens & Flow Rate Data DisplayB21 Flow UNIT, press 1 BT200 Setting of Selection-Type Data Flow rate unitsMoved to B Easy Setup 2 BT200 Setting of Numeric-Type Data Flow rate span B23 Flow SPAN, pressMoved to C Basic Setup 3 BT200 Setting of Alphanumeric-Type Data Tag numberTo C Basic Setup Operation VIA Hart Communicator Interconnectwion between AXFA11 and Hart Communicator Specifications for Communication LineConditions of Communication Line Communication Line RequirementsBasic Operation of the Hart Communicator Model Keys and FunctionsKey Operation DisplayCalling Up Menu Addresses Parameters Entering, Setting and Sending DataParameter Configuration Data RenewingExample of Setting Selection-Type Data Base Flow Unit Checking for ProblemsSetting Parameters Example of Setting Numeric-Type Data PV Span PV SpanExample of Setting Alphanumeric-Type Data Tag Number DisplayExample 1 of Other Settings Meter Factor Select MF SetSelect Power Frequency Example 3 of Other Settings Trim Analog Output TrimReturning fld dev to original output appears Select the Scaled D/A trim Returning fld dev to original output appears Exiting Burst Mode Example 4 of Other Settings Burst ModeSetting of Burst Mode Example 5 of Other Settings Multidrop ModePolling Exiting Multidrop Mode Example 6 of Other Settings Write ProtectionSetting Password Open Wrt Protect Menu in the Hot key MenuChanging Password Enable Wrt 10minJoker password and Software Seal Other Functions and OperationsMenu Tree On nextE12 J24 J30 P22 P23 Pre-operation Zero Adjustment Actual OperationZero Adjustment Using Display Unit Switches Selection D Major item Sub- item selection DZero Adjustment via External Status Input Ext Auto Zero Display Unit Replacement MaintenanceComponents Replacement Fuse ReplacementSetting of Burnout Switch Setting of SwitchesAmplifier Replacement Output Setting Pins for BurnoutSetting of Write Protect Switch 4 Switch ConfigurationTroubleshooting No IndicationUnstable Zero StartDisagreement Between Indication and Actual Flow Outline 65 10 Cf 10,000How to Set Parameters FunctionsStandard Performance Power Supply Power supply code Maximum Power ConsumptionSafety Requirement Standards Size 2200 mm 88 in. to 2600 mm 104Accessories Optional Specifications for AXFA11 Remote Converter Terminal WiringRemote Converter AXFA11G Surface mountingRemote Converter AXFA11G /RK AM11 Replacement Bracket General tolerance in the dimensional outline drawingDedicated Signal Cable AXFC-4-L AXFC-0-LRevision Record Edition Date Revised item