APC AXFA11G user manual AXFA11 Operation Using a BT200, 1 BT200 Connection

Page 70

7.2AXFA11 Operation Using a BT200

This section describes procedures for setting parameters using a BRAIN Terminal (BT200). For more details regarding AXFA11 functions, refer to Chapter 6: Parameter Description; and for more details regarding BT200 operation methods, refer to the BT200 User’s Manual (IM IC0A11-01E).

7.2.1BT200 Connection

Connection to a 4 to 20 mA DC signal line

The communication signal of the AXFA11 is superim- posed onto the 4 to 20mA DC analog signals to be transmitted.

AXFA11 terminals

 

 

 

4 to 20mA

Control room

 

 

 

DC signal

 

Receiving

I

Relaying

transmission

Terminal instrument

terminals

line

board

 

I

 

 

 

 

 

 

 

 

 

Receiving

 

 

 

 

resistance:

 

 

 

 

250 to 600 

 

BT200

BT200 BT200

BT200

F0705.EPS

Figure 7.2 Connecting the BT200

IMPORTANT

Restrictions exist with regard to the distance over which communication is possible. (See Chapter 11: Outline.)

IMPORTANT

If the power of flowmeter is turned off within 30 seconds after parameters have been set, these settings will be canceled. Accordingly, please keep the power on for at least 30 seconds after setting parameters.

IMPORTANT

After approximately 5 minutes of inactivity, the Auto Power-Off function will operate to turn your BT200 off.

7. OPERATION VIA BRAIN TERMINAL (BT200)

IMPORTANT

Be sure to set parameters as “Protect” on the write protect function after the finish of param- eter setting. Refer to the “Menu P: Parameter Protection Items” and section “10.2.2” in detail.

NOTE

In case of BT200, the parameters are displayed in English only.

Even if the language with the exception of English is selected at B10/H30: Language, the param- eters are displayed in English upon BT200.

7.2.2The data update and upload/ download function of BT200

(1) The data update of BT200

When the following parameters are displayed, the mea- sured data is updated automatically every seven seconds.

Item

Name (BRAIN)

Item

Name (BRAIN)

 

 

 

 

A10

FLOW RATE (%)

G43

ALM RECORD2

 

 

 

 

A20

FLOW RATE

G44

ALM TIME 2

 

 

 

 

A21

FLW RATE (mA)

G45

ALM RECORD3

 

 

 

 

A30

TOTAL

G46

ALM TIME 3

 

 

 

 

A31

REV TOTAL

G47

ALM RECORD4

 

 

 

 

A32

DIF TOTAL

G48

ALM TIME 4

 

 

 

 

C44

VELOCITY CHK

N20

TEST SI1

 

 

 

 

G22

4-20 BURNOUT

N21

TEST SI2

 

 

 

 

G40

OPERATE TIME

P20

W PROTECT

 

 

 

 

G41

ALM RECORD1

P23

SOFT SEAL

 

 

 

 

G42

ALM TIME 1

 

 

T0703.EPS

(2) Upload/download function of BT200

Upload function is used when the parameters of one AXFA11 are copied to the BT200. And download function is used when the parameters copied to the BT200 are set to another AXFA11.

For details, refer to BT200 User’s Manual (IM 1C0A11-01E). The targeted parameters for upload and download are following.

Item

Name (BRAIN)

Item

Name (BRAIN)

 

 

 

 

C11/B20

FLOW DAMPING

D10/B30

TOTAL UNIT

 

 

 

 

C31

SIZE UNIT

D11/B31

TOTAL SCALE

 

 

 

 

C32

NOMINAL SIZE

E10/B32

PULSE UNIT

 

 

 

 

C40/B21

FLOW UNIT

E11/B33

PULSE SCALE

 

 

 

 

C41/B22

TIME UNIT

H10/B40

DISP SELECT1

 

 

 

 

C42/B23

FLOW SPAN

H11/B41

DISP SELECT2

 

 

 

 

C43/B24

FLOW DECIMAL

H12/B42

DISP SELECT3

T0704.EPS

7-3

IM 01E20C01-01E

Image 70
Contents Users ManualAXFA11G Contents Operation VIA Hart Communicator Revision Record Safety and Modification Precautions IntroductionWarranty Using the Magnetic Flowmeter SafelyGuarantee will not apply in the following cases Combination Remote Flowtubes Accessories Handling PrecautionsChecking Model and Specifications Storage PrecautionsMounting InstallationInstallation Location Surface Mounting Wall MountingInch pipe Mounting fixture Washer Clamp screw Inch Pipe MountingPanel Mounting Unit mm approx. inch Panel cutout 203 Mounting fixture 172Dedicated Signal Cable Axfc WiringWiring Precautions CablesUnit mm approx. inch Crimp Terminal Wiring PortsExcitation Cable/Power Cable/Output Cable On the converter sideConduit Wiring When there are no particular optional specificationsWiring using waterproof glands Plastic glandTerminal Configuration Wiring ConnectionsRemoving Cover Precautions for Wiring of Power Supply Cables DC Power ConnectionGrounding Wiring the Remote Flowtube with the AXFA11 ConverterAxfc Dedicated signal cable Excitation cable Protective grounding terminalsConnecting to External Instru- ments To 20 mA DC Current OutputPulse Output Status InputStatus Output / Alarm Output 13 Status Output ConnectionSetting switch operations Operating Panel Configuration and FunctionsData display area Reversed-character indication ContentDisplay items NoneDisplay Unit Setting Methods Display Mode → Setting ModeSetting Mode To Parameter Search Mode Setting Mode Parameter Setting ProcedureSetting Example for Selection-Type Data Flow rate units B21 Base Flow Unit Sub-item Current unit settingSub-item Parameter Search Mode Parameter Sub-itemMajor Item Parameter Search Mode Setting mode Setting Example for Numeric-Type Data Flow rate spanSetting Mode Condition B23 Flow SpanSub-item Parameter Search Mode Major item Setting Example for Alphanumeric-Type Data Tag numberSetting Mode Condition Incorrect settingSub-item Major item Search Mode Selection CModified value Parameter Description Item B Menu B Easy Setup items Item a Menu a Display itemsName Data range Default value Units Description Display unitIndicated item Item C Menu C Basic Setting items Name Data range Position Default value Units Display unitName Data range Position Default value Display unit Item D Menu D Total Setting itemsDefault value Units Display unit NameItem E Menu E Pulse Setting items Item F Menu F Status Functions Setting itemsItem G Menu G Alarm Setting items ALM OUT ACT ALM-SETTINGALM HYS ALM-SIG OverItem H Menu H Display Setting items Item J Menu J Auxiliary Function Setting itemsItem K Menu K Diagnostic Function Setting items Units Display unitItem N Menu N Loop Test Setting items Item P Menu P Parameter Protection itemsMenu B Easy Setup items Data RangeExample When 1000 m3/h is set for B23/C42 Flow Span Unit/P 10-9 FU u Unit/P 10-6 FU Pulse/sDescription Menu C Basic Setting items B41/H11 Display Select2 and B42/H12 DisplayMeter Factor Settings C49 Flow User Span Menu D Total Setting itemsC47 User Span Select Selection of the use Is set forB22/C41 Base Time UnitFlow Unit TOTAL, and A32 DIF Total when BrainF13 Is set forB22/C41 Base TimeSetting for E20 Pulse Active Mode Menu E Pulse Setting itemsE20 Pulse Active Mode Switch Lower and D24 Ttl Switch Upper Menu F Status Functions Setting itemsSetting Function Description G33 Alm-HH/LL to YesNo Function No input function Val UpperStatus Output for Automatic Multiple Ranges Switching Multiple ranges settingMultiple Ranges Setting Automatic multiple ranges switching 1 Status Output for Automatic Multiple Ranges SwitchingF14 SO1/2 Active Mode Parameter setting sequenceFor automatic multiple ranges switching F10 SO1 Function F11 SO2 Function2 Multiple Ranges Switching via External Status Input F15G10 Low Alarm Low alarm setting Menu G Alarm Setting itemsG11 High Alarm High alarm setting 100 High Alarm Instantaneous flow rate Low Low Alarm Time t High High Alarm100 High Alarm Output Example100 100 85% 75% High Alarm35% Low Alarm 25%G22 4-20mA Burn Out Display of the current Setting FunctionExample ClosedOn OpenOffG43 Alm Record2 Alarm record2 G41 Alm Record1 Alarm record1Alarm Items G45 Alm Record3 Alarm record3Menu J Auxiliary Function Setting items Setting range 0 to 10% HysteresisExample 1 Step input Function orDetermining rate limit value and dead time Example 2 Slurry noiseK10 Adhesion Check Setting of adhesion J31 Power FrequencyMenu K Diagnostic Function Setting items Power Supply Code 100 to 240 V AC or 100 to 120 V DCMenu N Loop Test Setting items Adhesion Diagnostic FunctionMenu M Automatic Zero Adjustment Function Setting items SO1 Function or F11 SO2 Function, thenMenu P Parameter Protection items N11 Test Output Value Setting for test outputDefault setting Enable Write Protect functionDefault setting After password settingDisplay and output condition for process alarms G20 Alm Out Act Mode Setting of the activeOut Act Mode Totali Pulse Display Alarm Display and output condition for setting alarm occurrencesAlarm description Selection Output UnitAlarms & Warning Messages K12, K13 and K14 are correct Key Descriptions Operation VIA Brain Terminal BT200BT200 Basic Operations Key Layout and DisplayFunction Keys Command FunctionKey-in Sequence Data update and upload/ download function of BT200 AXFA11 Operation Using a BT2001 BT200 Connection Parameter Setting Using a BT200 3 BT200 Screens & Flow Rate Data DisplayMoved to B Easy Setup 1 BT200 Setting of Selection-Type Data Flow rate unitsB21 Flow UNIT, press 2 BT200 Setting of Numeric-Type Data Flow rate span B23 Flow SPAN, pressTo C Basic Setup 3 BT200 Setting of Alphanumeric-Type Data Tag numberMoved to C Basic Setup Operation VIA Hart Communicator Interconnectwion between AXFA11 and Hart Communicator Specifications for Communication LineConditions of Communication Line Communication Line RequirementsBasic Operation of the Hart Communicator Model Keys and FunctionsCalling Up Menu Addresses DisplayKey Operation Parameters Entering, Setting and Sending DataParameter Configuration Data RenewingSetting Parameters Checking for ProblemsExample of Setting Selection-Type Data Base Flow Unit Example of Setting Numeric-Type Data PV Span PV SpanExample of Setting Alphanumeric-Type Data Tag Number DisplayExample 1 of Other Settings Meter Factor Select MF SetSelect Power Frequency Example 3 of Other Settings Trim Analog Output TrimReturning fld dev to original output appears Select the Scaled D/A trim Returning fld dev to original output appears Exiting Burst Mode Example 4 of Other Settings Burst ModeSetting of Burst Mode Example 5 of Other Settings Multidrop ModePolling Exiting Multidrop Mode Example 6 of Other Settings Write ProtectionSetting Password Open Wrt Protect Menu in the Hot key MenuChanging Password Enable Wrt 10minJoker password and Software Seal Other Functions and OperationsMenu Tree On nextE12 J24 J30 P22 P23 Pre-operation Zero Adjustment Actual OperationZero Adjustment Using Display Unit Switches Selection D Major item Sub- item selection DZero Adjustment via External Status Input Ext Auto Zero Display Unit Replacement MaintenanceComponents Replacement Fuse ReplacementSetting of Burnout Switch Setting of SwitchesAmplifier Replacement Output Setting Pins for BurnoutSetting of Write Protect Switch 4 Switch ConfigurationTroubleshooting No IndicationUnstable Zero StartDisagreement Between Indication and Actual Flow Outline 65 10 Cf 10,000How to Set Parameters FunctionsStandard Performance Power Supply Power supply code Maximum Power ConsumptionSafety Requirement Standards Size 2200 mm 88 in. to 2600 mm 104Accessories Optional Specifications for AXFA11 Remote Converter Terminal WiringRemote Converter AXFA11G Surface mountingRemote Converter AXFA11G /RK AM11 Replacement Bracket General tolerance in the dimensional outline drawingDedicated Signal Cable AXFC-4-L AXFC-0-LRevision Record Edition Date Revised item