8. OPERATION VIA HART COMMUNICATOR
NOTE
Data changed with the HART Communicator is sent to the AXFA11 by pressing
SEND (F2) of the HART Communicator.
8.3.3Checking for Problems
The
* Open the “Test/Status” setting display.
1.Device Setup 2. Diag/Service 3. Test/Status
8.3.4Setting Parameters
As mentioned in Section 5.2.2 “Setting Mode,” the AXFA11’s parameters are divided into three types:
i.Selection type
ii.Numeric type
iii.Alphanumeric type
This section describes how to set these parameters using a HART communicator.
NOTE
All three parameters must be set to obtain a correct signal.
Nominal size, flow rate span and meter factor must be set.
8.3.4.1Example of Setting Selection-Type Data: Base Flow Unit
This example describes the setting of the flow rate units for the
Open the “Base Flow Unit” setting display.
1. Device Setup 3. Easy Setup 3. Base Flow Unit
1AXFA11 :
m3
m3
K1(Kiloliter)
l(Liter)
cm3
ESC ENTER
2AXFA11 :
1 Language
2 | PV | Damping |
| |
3 | Base | Flow Unit | l | |
4 | Base | Time Unit | /h | |
5 | PV | Span |
|
SEND HOME
⋅Select “1(Liter)”.
2
F4 | Press ENTER (F4). |
|
|
(ENTER)
3AXFA11 :
Easy Setup
1Language
2PV Damp
F2
Press SEND (F2) to set the data into the AXFA11.
3 | Base | Flow Unit | l |
4 | Base | Time Unit | /h |
5 | PV Span |
|
SAVE HOME
(SEND)
F0807.EPS
IM |