Whirlpool LI30LA/W10463244A installation instructions Check Operation, Makeup Air Kit Maintenance

Page 8

Make the Electrical Connection

1.Disconnect power.

2.Determine the location where the wiring conduit will be routed through the ceiling or wall between the makeup air switch duct and the motorized damper.

3.Drill a hole at this location.

4.Locate the electrical terminal boxes in the makeup air switch duct and the motorized damper.

Remove the terminal box covers and set the covers and screws aside.

5.Determine the knockouts in terminal boxes for motorized damper, makeup air switch duct and house junction box that will be used.

Remove knockouts and install a ½" (12.7 mm) UL listed or CSA approved strain relief at each location.

6.Run separate wiring between the house junction box and the terminal boxes for the motorized damper and the makeup air switch duct.

WARNING

Electrical Shock Hazard

Disconnect power before servicing.

Connect ground wire to green ground wire in terminal box.

Replace all parts and panels before operating.

Failure to do so can result in death, fire, or electrical shock.

7.Connect green (yellow/green) wires from makeup air switch duct and motorized damper to house ground using UL listed wire connectors.

8.Connect brown wire from makeup air switch duct to the black wire(s) from the motorized damper using UL listed wire connectors.

9.Connect black wire from makeup air switch duct to the house line black wire using a UL listed wire connector.

10.Connect the white wire(s) from the motorized damper to the house neutral white wire(s) using UL listed wire connectors.

NOTE: The 10" (25.4 cm) Makeup Air Kit must be installed with 2 motorized dampers. The lightest figure shown is the connection for the second motorized damper.

wall

House

 

House

 

 

 

ground

 

neutral

 

green

 

 

 

white

 

 

 

 

 

120VAC

 

black

 

House

 

black

line

 

 

 

 

 

 

black

yellow/

 

 

 

brown

green

 

black

 

House

 

 

 

 

 

 

ground

House

neutral

white

green

House ground

10" (25.4 cm) Makeup air installation

Check Operation

Once the make up air switch duct and the motorized damper(s) are installed, the installer should confirm that the motorized damper opens and closes in conjunction with signals from the hood.

The motorized damper should close or be closed when the range hood speed switch is Off or On at low speed.

The motorized damper should open when the range hood speed switch is set at medium speed or higher.

A qualified HVAC contractor should also ensure the proper operation and venting of all combustion equipment in the home.

Makeup Air Kit Maintenance

Regular maintenance is necessary to ensure the proper operation of the makeup air system. Failure to conduct routine maintenance can reduce the ability of the damper to introduce fresh air into the home. Regular maintenance should include the following activities:

Maintain a clear opening at the outdoor end cap, keeping snow, leaves or vegetation from building up at the end cap.

Clean or replace the interior filter(s) that serve to filter fresh air before it enters the home.

During regular HVAC maintenance, have the mechanical contractor inspect the damper system for proper operation.

8

Image 8
Contents Table of Contents/Índice/Table des matières DE Ventilación RectangularesTable of Contents Vent System SafetyÍndice Table DES MatièresImportant Safety Instructions Location Requirements Installation RequirementsTools and Parts Planning the Installation Typical InstallationsPlanning the Makeup Air Switch Duct installation Planning the Motorized Damper installationInstallation Instructions Install Makeup Air Switch Duct10 25.4 cm Round Makeup Air Switch Duct From kit W10446917 Prepare LocationInstall Motorized Damper To Remove and Install Motorized Damper Terminal Box CoverMake Electrical Connection Under-Cabinet Mount Range Hood ModelsMake the Electrical Connection Makeup Air Kit MaintenanceCheck Operation Wiring Diagram SE12R aCanada Assistance or ServiceU.S.A Year Limited Warranty Parts only Labor not Included Items Excluded from WarrantyThis warranty does not cover Date for in-warranty serviceSeguridad DEL Sistema DE Ventilación Su seguridad y la seguridad de los demás es muy importanteInstrucciones Importantes DE Seguridad Requisitos de ubicación Requisitos DE InstalaciónHerramientas y piezas Instalaciones típicas Requisitos eléctricosPlanificación de la instalación Instrucciones DE Instalación Preparación de la ubicaciónInstalación del conducto conmutador de Aire de complemento Modelos de campana de cocina para montaje en muro o islaInstalación del regulador de tiro Motorizado Modelos de campana de cocina para montaje debajo de armariosHaga la conexión del suministro eléctrico Haga la conexión del suministro eléctricoVerifique el funcionamiento Mantenimiento del juego de aire de ComplementoDiagrama DE Cableado Microinterruptor de activaciónEn los EE.UU Ayuda O Servicio TécnicoWhirlpool Sécurité DES Circuits DE Ventilation Exclusión DE Garantías ImplícitasImportantes Instructions DE Sécurité Exigences Dinstallation Exigences demplacementOutils et pièces Outils nécessairesPlanification de linstallation Installations typiquesPlanification de linstallation du clapet motorisé Spécifications électriquesModèles de hottes à installation murale ou en îlot Instructions D’INSTALLATIONPréparation de lemplacement Installation du clapet motorisé Modèles de hottes placardRaccordement électrique Effectuer le raccordement électriqueMaintenance de lensemble dair de Compensation Contrôle du fonctionnementSchéma DE Câblage Débit dair de compensationAssistance OU Service Au CanadaSi vous avez besoin de pièces de rechange Pour plus d’assistanceW10463244A Composer le