INSTALLATION REQUIREMENTS
NOTE
Because of potentially inconsistent voltage capabilities, the use of this dryer with power created by gas powered generators, solar powered generators, wind powered generators or any other generator other than the local utility company is not recommended.
Electrical requirements for electric dryer
CIRCUIT - Individual 30 amp. branch circuit fused with 30 amp. time delay fuses or circuit breakers. Use separately fused circuits for washer and dryer. DO NOT operate a washer and a dryer on the same circuit.
POWER SUPPLY -
IMPORTANT
This dryer is internally grounded to neutral unless it was manufactured for sale in Canada. Grounding through the neutral link is prohibited for: (1) new branch circuit installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where local codes do not permit grounding through the neutral.
OUTLET RECEPTACLE - NEMA
GROUNDING CONNECTION - See “Grounding requirements” in Electrical Installation section.
3-wire receptacle
(NEMA type 10-30R)
The dryer MUST employ a
ELECTRICAL CONNECTIONS FOR A
4-wire receptacle
(NEMA type 14-30R)
The dryer MUST employ a
ELECTRICAL CONNECTIONS FOR A 4-WIRE SYSTEM.
NOTE
Dryers manufactured for sale in Canada have factory- installed,