DRYER START UP & OPERATION
matically shut down during the cooling and unloading cycles.
11.Turn the unload switch to the one speed position. The bottom auger and metering rolls will start automatically during the unload cycle of the
12.To control the length of the dry cycle using only the dry time
setting programmed into the system, turn the moisture con- trol setting to off. To use the au- tomatic moisture control so that the dry time is determined, not only by the dry time setting, but also by the moisture content of the drying grain, turn the mois- ture control switch to on, and set dial to a beginning setting of 135°F.
13.To start the drying operation push the dryer power start but- ton. The controller will start all the dryer components in their proper order. If any of the se- lected switches are improperly positioned for staged batch dry ing, the display will indicate the proper switch position, and will not allow the dryer to operate until
the position of the switch is cor- rected.
14.To shutdown the dryer, close the fuel supply valve at the fuel tank or fuel source. If the burners are operating, let the dryer run out of fuel causing an automatic shutdown due to a loss of flame. Close the fuel valve at the dryer, and press the dryer power stop button. Turn off the dryer's main circuit breaker located on the front of the power panel. Turn off the main power supply to the dryer.
15.In case of an emergency, press the dryer power stop button. The burners, fans and all augers will stop immediately.
STAGED BATCH FAN & HEATER SWITCH SETTINGS
Fan Setting | Heater Setting | Fan Function | Heater Function |
Auto | Auto | Fans stay on during dry and cool | Burners stay on during dry timer cycle |
|
| cycle only | only |
Auto | On | Fans stay on during dry and cool | Burners stay on during dry and cool |
|
| cycle only |
|
On | On | Fans are on continuously | Burners are on continuously |
On | Auto | Fans are on continuously | Burners shut down at the end of the |
|
|
| dry cycle |
At the end of the dry cycle in staged batch, the fans and heaters will continue running if in the
preset temperature on the moisture control thermostat is reached.
22