English
maintain a minimum of 12 inches (30.5cm) clearance between the vent hood and the ground or any other obstruction. The vent flap should be able to move freely, although vertical orientation of the exhaust system is acceptable. Certain extenuating circumstances could affect the performance of the dryer:
1.Only rigid metal duct work should be used.
2.Venting vertically through a roof may expose the exhaust system to down drafts causing an increase in vent restriction.
3.Running the exhaust system through an uninsulatedarea may cause condensation and faster accumulation of lint.
4.Compression of crimping of the exhaust system will cause an increase in vent restriction.
The exhaust system should be inspected and cleaned a minimum of every 12 months with normal usage. The more the dryer is used the more often you should check the exhaust system and vent hood for proper operation.
RECOMMENDED MAXIMUMM
Exhaust Hood Types
Recommended
Use only for short
run installations
No. of 90º | Rigid Metal | Flexible Metal | Rigid Metal | Flexible | ||||
elbows |
|
|
|
|
|
| Metal | |
0 | 90 | ft. | 55 | ft. | 60 | ft. | 45 | ft. |
1 | 60 | ft. | 40 | ft. | 45 | ft. | 30 | ft. |
2 | 45 | ft. | 30 | ft. | 35 | ft. | 20 | ft. |
3 | 35 | ft. | 20 | ft. | 25 | ft. | 15 | ft. |
8