Vermont Casting RADVTCCB Fan Override During Auto Mode, Change Between F/C Temperature Units

Page 33

Auto Mode

In the AUTO mode, the room temperature, set tem- perature, flame and fan levels will be shown. AUTO will appear next to both the flame and fan icons.

When the control is in the AUTO mode, the main burner will turn on/off or modulate based on the heat needed to maintain the set temperature. The flame level will change automatically to optimize the heat output needed to maintain the set temperature. To change the set temperature, press the up or down key. Pushing a key once will change the temperature by one degree.

In the AUTO mode, the fan speed will increase with increasing flame height or decrease with decreasing flame height. “AUTO” is displayed next to the flame and fan icons.

Fan Override During Auto Mode

If a lower or higher fan speed is desired when operating in the AUTO mode, the fan speed can be overridden by pushing the fan button followed by the up or down key. Pushing a key once will change the fan level by one unit. In this mode “AUTO” is displayed next to the flame icon and “MANUAL” is displayed next to the fan icon.

Change Between F/C Temperature Units

Push the up and down arrow keys simultaneously for at least 3 seconds to toggle between Fahrenheit and Celsius units.

Disable Thermostat Function

To disable the thermostat function in the AUTO mode, push the time and down keys simultaneously for at least 3 seconds.

To Change Batteries

1.Remove cover on the backside of the transmitter. Install 3 AAA batteries as shown and reattach cover.

2.Once steps 1-3 in OPERATION are completed, receiver/valve and transmitter are now ready. Press any button on transmitter for recognition process to occur between the receiver/valve and transmitter.

3.Use functions as described in TRANSMITTER sec- tion.

Troubleshooting

1.Locate LED light on valve.

2.LED will blink after every valid command received by the transmitter; this is not an error.

3.Failure codes may occur anytime after pilot burner is lit.

4.Sequence is failure code followed by light not blink- ing for 30 seconds.

Radiance Direct Vent Gas Heater

 

 

Pilot As-

 

 

 

sembly

 

 

 

 

Blower

 

 

Red

FAN

 

 

 

 

Red

White

 

 

 

 

 

White

 

 

 

 

White Dots

 

 

Antenna

 

FP1038

 

Comfort Control Valve

 

(Bottom View)

 

Fig. 59 Comfort Valve wiring diagram.

 

5.In the event of multiple failure codes, next failure code follows previous failure code by approximately 3 seconds.

If an Error Code 3 is observed while performing the testing, complete the following:

1.Make sure the spade connectors are pushed all the way on. If rhe Error Code 3 is still showing, then go to the next step.

2.Switch the front two thermopile leads with the back two. Be sure the white lead is connected to the spade with the white dot next to it. If the Error Code 3 is still showing, replace the thermopiles.

If an Error Code 8 is observed while performing the testing, complete the following:

1.Confirm the valve is not in REMOTE mode.

If the valve is producing Error Code 8 and in RE- MOTE mode, the valve is defective and should be replaced.

If the valve is in LOCAL mode and producing Error Code 8, then go to the next step.

2.Slide the Remote/Local switch to REMOTE and teach the valve a transmitter. The Error Code will clear itself after approximately 1.5 minutes and re- turn to normal operation.

LED Count

Service Action

8Replace valve

7Confirm stepper motor connection exists

5 Confirm fan connection exists and works

4 Confirm gas type; jumper in place

3 Replace thermopiles

2 Turn fan ON

NOTE: Some keys are not active.

20012697

33

Image 33
Contents Radiance Direct Vent Gas Heater Table of Contents Commonwealth of Massachusetts Installation & Operating InstructionsCenterline Dimensions Radiance Direct Vent Stove DimensionsLocating The Stove Installation RequirementsClearance Requirements Direct Vent System OnlyCorner Installation Minimum Clearance and Flue Centerline Parallel Installation Minimum Clearance and Flue CenterlineWall Centerline from Floor Wall and Ceiling ClearancesGas Inlet and Manifold Pressures Gas SpecificationsHigh Elevations Horizontal TerminationRestictor Plate is used on Direct Vent installations only Restrictor Plate Adjustment For Extended Pipe RunsRestrictor Plate Adjustment Examples for Extended Run/Restrictor Plate SettingsLocation of Vent Termination Vent Termination ClearancesGeneral Venting Information Termination Location Canadian Installations1 US Installations2Termination Clearances Venting Requirements and Options Approved Vent System ComponentsMinimum Horizontal Vent Kit 2792 12 18 Adjustable Pipe Twist Lock 24 Straight Pipe CG Non-adjustable Pipe Twist Lock 12 18 Adjustable PipeNon-adjustable Pipe Twist Lock 48 Straight Pipe CG Nonadjustable Pipe Twist Lock 45-Degree Elbow CGParts Bag Contents Assembly ProceduresTools Required Unpack and Assemble LegsRemove rear shroud Install the Optional FanVenting System Assembly General Information Install the Vent Adapter PipeFor Canadian installations The venting system must Install Vent Adapter Pipe Side Wall Termination AssemblySelkirk Corporation Vent Components Measure the horizontal length Vent Termination Below Grade Vertical Through the Roof Vent AssemblyCut the opening CFM System 9³⁄₈ x 9³⁄₈ 240 x 240 mmSelkirk Direct-Temp Metalbestos Direct Vent System Horizontal Venting Vertical VentingInlet End Outlet End To TerminationSupporting DIRECT-TEMP Horizontal Support Adjustable Length AJFire Stopping OffsetsBelow grade installation Vertical Installation Fig Minimum Height Above Roof Requirements Install Log Set2626 Burner Information Connect the Gas Supply LineOperation Flame Characteristics Flame & Temperature AdjustmentSIT Pilot Radvt Series Pilot Radvtc SeriesHoneywell To Turn Off Gas To HeaterSIT Nova 820 Millivolt Valve Troubleshooting the Gas Control System Radvt SeriesTransmitter Operation Off Mode Shut Off ProcedureOn Manual Mode Delay Timer ModeFan Override During Auto Mode Auto ModeChange Between F/C Temperature Units Disable Thermostat FunctionLocal Path On Path Auto Path Conversion Precautions Conversion ProcedureFuel Conversion Instructions Pilot Orifice Conversion Pilot Type 1 SIT PilotPilot type 2 Honeywell Pilot All Models Burner Orifice ConversionInjector Orifice Size Matrix Air Shutter AdjustmentHigh Altitude Orifice Conversion to LP Input BTU/hMaintenance Gasket Replacement Inspect the Vent System AnnuallyCheck the Gas Flame Regularly On/Off Switch Wiring Wiring DiagramsSchematic Diagram Optional ThermostatRadiance Direct Vent Gas Heater Description Radiance Direct Vent Gas HeaterFuel Conversion Kits Shell Enamel Parts Radiance Direct Vent Optional Accessories 4848 Radiance Direct Vent Gas Heater 5050 Limited Lifetime Warranty CFM Corporation