Vermont Casting RADVTCEB, RADVTMB, RADVTSG, RADVTCB, RADVTCG Burner Orifice Conversion, All Models

Page 38

Radiance Direct Vent Gas Heater

Pilot

Orifice

CO1044

Fig. 71 Remove pilot orifice.

Burner Orifice Conversion

1.Remove three (3) 3/8” nuts on bottom side of burner pan. (Fig. 72)

2.Carefully remove ember bed by tilting the right side up and lifting out toward the right side of the unit. (Fig. 73)

Remove Nut

Bottom View

3.Remove injector orifice from left burner bracket with a 1/2” wrench. Use a back up wrench to prevent damage to the manifold. (Fig. 74)

CO145

Fig. 74 Use two wrenches to avoid damage to manifold.

4.Install conversion orifice. (Refer to Table 2)

5.The air shutter is factory set according to Table 3 and should not need adjustment. The air shutter opening may be verified by measuring as shown in Figure 75.

Orifice

Orifice

Air Shutter

 

Bracket

 

 

ST918

Remove Nuts

Fig. 72 Remove three (3) nuts securing ember bed in place.

Orifice

Venturi Bracket

Bracket

 

Pem Studs

ST919

Fig. 73 Tilt ember bed slightly to correctly place on venturi and air shutter.

CO142

Fig. 75 The air shutter setting is 1/2” (13 mm) from the orifice bracket to the edge of the air shutter.

All Models

1.Replace burner making sure venturi on bottom of ember bed aligns with orifice and is seated properly on air shutter assembly. (Fig. 73) Make sure burner is slid into place at a slight angle and opposite to how it was removed. When burner is slid into place, the three (3) pem studs should slide down through clearance holes into the bottom of the control panel.

2.Thread and tighten 3/8” nuts back onto pem studs on underneath side of control panel, reversing Step 1 shown in Figure 72.

3.Reinstall logs as per instructions on Page 26.

4.Place conversion label on valve.

3838

20012697

Image 38
Contents Radiance Direct Vent Gas Heater Table of Contents Installation & Operating Instructions Commonwealth of MassachusettsRadiance Direct Vent Stove Dimensions Centerline DimensionsClearance Requirements Installation RequirementsLocating The Stove Direct Vent System OnlyWall Centerline from Floor Parallel Installation Minimum Clearance and Flue CenterlineCorner Installation Minimum Clearance and Flue Centerline Wall and Ceiling ClearancesHigh Elevations Gas SpecificationsGas Inlet and Manifold Pressures Horizontal TerminationRestrictor Plate Adjustment Restrictor Plate Adjustment For Extended Pipe RunsRestictor Plate is used on Direct Vent installations only Examples for Extended Run/Restrictor Plate SettingsVent Termination Clearances Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationTermination Clearances Minimum Horizontal Vent Kit 2792 Venting Requirements and OptionsApproved Vent System Components Non-adjustable Pipe Twist Lock 48 Straight Pipe CG Non-adjustable Pipe Twist Lock 12 18 Adjustable Pipe12 18 Adjustable Pipe Twist Lock 24 Straight Pipe CG Nonadjustable Pipe Twist Lock 45-Degree Elbow CGTools Required Assembly ProceduresParts Bag Contents Unpack and Assemble LegsInstall the Optional Fan Remove rear shroudFor Canadian installations The venting system must Venting System Assembly General InformationInstall the Vent Adapter Pipe Selkirk Corporation Vent Components Install Vent Adapter PipeSide Wall Termination Assembly Measure the horizontal length Cut the opening Vertical Through the Roof Vent AssemblyVent Termination Below Grade CFM System 9³⁄₈ x 9³⁄₈ 240 x 240 mmSelkirk Direct-Temp Metalbestos Direct Vent System Inlet End Outlet End Vertical VentingHorizontal Venting To TerminationFire Stopping Adjustable Length AJSupporting DIRECT-TEMP Horizontal Support OffsetsBelow grade installation Vertical Installation Fig Install Log Set Minimum Height Above Roof Requirements2626 Connect the Gas Supply Line Burner InformationOperation SIT Pilot Radvt Series Flame & Temperature AdjustmentFlame Characteristics Pilot Radvtc SeriesTo Turn Off Gas To Heater HoneywellTroubleshooting the Gas Control System Radvt Series SIT Nova 820 Millivolt ValveOn Manual Mode Shut Off ProcedureTransmitter Operation Off Mode Delay Timer ModeChange Between F/C Temperature Units Auto ModeFan Override During Auto Mode Disable Thermostat FunctionLocal Path On Path Auto Path Fuel Conversion Instructions Conversion PrecautionsConversion Procedure Pilot type 2 Honeywell Pilot Pilot Orifice ConversionPilot Type 1 SIT Pilot Burner Orifice Conversion All ModelsHigh Altitude Orifice Air Shutter AdjustmentInjector Orifice Size Matrix Conversion to LP Input BTU/hMaintenance Check the Gas Flame Regularly Gasket ReplacementInspect the Vent System Annually Schematic Diagram Wiring DiagramsOn/Off Switch Wiring Optional ThermostatRadiance Direct Vent Gas Heater Radiance Direct Vent Gas Heater DescriptionFuel Conversion Kits Shell Enamel Parts Radiance Direct Vent Optional Accessories 4848 Radiance Direct Vent Gas Heater 5050 Limited Lifetime Warranty CFM Corporation