Vermont Casting RADVTCMB, RADVTMB, RADVTSG Fuel Conversion Instructions, Conversion Precautions

Page 36

Radiance Direct Vent Gas Heater

Fuel Conversion Instructions

WARNING! This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruc- tions is not followed exactly, a fire, explosion

or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is respon- sible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.

CAUTION: The gas supply shall be shut off prior to disconnecting the electrical power, before pro- ceeding with the conversion.

 

OFF

I

N

H O

O

 

TPILOJAD

 

Main

 

Gas Line

Gas Supply Inlet

 

ST226a

Fig. 60 Attach the gas line to the right side of the valve.

2.Allow the valve to cool to room temperature.

3.Remove the black protection cap by hand. (Fig. 61)

4.Insert a 5/32” or 4 mm Allen wrench into the hexagonal key-way of the screw (Fig. 62), rotate it counter- clockwise until it is free and extract it.

5.Check that the screw is clean and if necessary remove dirt.

6.Flip the screw. (Fig. 63)

7.Using the Allen wrench as shown in Figure 64, rotate the screw clockwise and tighten until snug.

Figure 61

Figure 63

� �

Figure 62

� �

Figure 64

� �

Conversion Precautions

Before proceeding, turn control knob on valve to OFF and turn gas supply OFF. Turn OFF any electricity that may be going to the appliance.

Conversion Procedure

1.Remove stove front. Lift stove front up and then swing bottom out and away to disengage from the stove body. (Page 25, Fig. 46)

2.Undo the right and left latches at the top of the glass frame. (Page 25, Fig. 47)

3.Pull the top edge of the glass and frame assembly away from the firebox face. Place the assembly out of the way on a flat, padded surface such as a coun- ter protected by a towel.

4.Remove the logset from the firebox.

Valve Conversion

RADVT Series Models

1.Turn control knob to the OFF position, and shut off the gas supply to the valve.

WARNING: Do not overtighten the

screw. Recommended to grip the wrench by the short side.

8.Verify that if the conversion is from NG to LP, the screw must be reassembled with the red o-ring vis- ible. (Fig. 65)

Figure 65

 

Natural Gas

LP Configuration

Configuration

 

 

 

 

 

 

 

 

 

 

 

Red O-ring Visible

 

 

 

Red O-ring NOT Visible

CO141

9. Replace the black protection cap.

WARNING: Check that also the pilot and main burner injectors are appropriate for the gas type.

RADVTC Series Models

1. Follow procedure for pilot type 2 to replace pilot orifice.

3636

20012697

Image 36
Contents Radiance Direct Vent Gas Heater Table of Contents Installation & Operating Instructions Commonwealth of MassachusettsRadiance Direct Vent Stove Dimensions Centerline DimensionsInstallation Requirements Locating The StoveClearance Requirements Direct Vent System OnlyParallel Installation Minimum Clearance and Flue Centerline Corner Installation Minimum Clearance and Flue CenterlineWall Centerline from Floor Wall and Ceiling ClearancesGas Specifications Gas Inlet and Manifold PressuresHigh Elevations Horizontal TerminationRestrictor Plate Adjustment For Extended Pipe Runs Restictor Plate is used on Direct Vent installations onlyRestrictor Plate Adjustment Examples for Extended Run/Restrictor Plate SettingsVent Termination Clearances Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationTermination Clearances Venting Requirements and Options Approved Vent System ComponentsMinimum Horizontal Vent Kit 2792 Non-adjustable Pipe Twist Lock 12 18 Adjustable Pipe 12 18 Adjustable Pipe Twist Lock 24 Straight Pipe CGNon-adjustable Pipe Twist Lock 48 Straight Pipe CG Nonadjustable Pipe Twist Lock 45-Degree Elbow CGAssembly Procedures Parts Bag ContentsTools Required Unpack and Assemble LegsInstall the Optional Fan Remove rear shroudVenting System Assembly General Information Install the Vent Adapter PipeFor Canadian installations The venting system must Install Vent Adapter Pipe Side Wall Termination AssemblySelkirk Corporation Vent Components Measure the horizontal length Vertical Through the Roof Vent Assembly Vent Termination Below GradeCut the opening CFM System 9³⁄₈ x 9³⁄₈ 240 x 240 mmSelkirk Direct-Temp Metalbestos Direct Vent System Vertical Venting Horizontal VentingInlet End Outlet End To TerminationAdjustable Length AJ Supporting DIRECT-TEMP Horizontal SupportFire Stopping OffsetsBelow grade installation Vertical Installation Fig Install Log Set Minimum Height Above Roof Requirements2626 Connect the Gas Supply Line Burner InformationOperation Flame & Temperature Adjustment Flame CharacteristicsSIT Pilot Radvt Series Pilot Radvtc SeriesTo Turn Off Gas To Heater HoneywellTroubleshooting the Gas Control System Radvt Series SIT Nova 820 Millivolt ValveShut Off Procedure Transmitter Operation Off ModeOn Manual Mode Delay Timer ModeAuto Mode Fan Override During Auto ModeChange Between F/C Temperature Units Disable Thermostat FunctionLocal Path On Path Auto Path Conversion Precautions Conversion ProcedureFuel Conversion Instructions Pilot Orifice Conversion Pilot Type 1 SIT PilotPilot type 2 Honeywell Pilot Burner Orifice Conversion All ModelsAir Shutter Adjustment Injector Orifice Size MatrixHigh Altitude Orifice Conversion to LP Input BTU/hMaintenance Gasket Replacement Inspect the Vent System AnnuallyCheck the Gas Flame Regularly Wiring Diagrams On/Off Switch WiringSchematic Diagram Optional ThermostatRadiance Direct Vent Gas Heater Radiance Direct Vent Gas Heater DescriptionFuel Conversion Kits Shell Enamel Parts Radiance Direct Vent Optional Accessories 4848 Radiance Direct Vent Gas Heater 5050 Limited Lifetime Warranty CFM Corporation