4. OPERATING MODES

English

4.6 Closed Loop Control

4.6.1 General Description

The MICROMASTER provides a PI control function for closed loop control (see Figure 11). PI control is ideal for temperature or pressure control, or other applications where the controlled variable changes slowly or where transient errors are not critical. This control loop is not suitable for use in systems where fast response times are required.

Note: The closed loop function is not designed for speed control, but can be used for this provided that fast response times are not required.

When closed loop PI control is enabled (P201 = 002), all setpoints are calibrated between zero and 100%, i.e. a setpoint of 50.0 = 50%. This allows general purpose control of any process variable that is actuated by motor speed and for which a suitable transducer is available.

Setpoint

Low Pass

 

Filter

Scaling

 

P206

P211, P212

Feedback

Sample

Rate

P205

P

Acceleration/

 

 

 

 

 

P202

Deceleration

 

 

+

Ramp

Motor

 

 

M

Process

 

 

e.g. fan

 

 

 

 

P002, P003

 

Feedback

 

 

(e.g. duct pressure)

I

 

 

Transducer

 

 

 

P203, P207

P208

Closed Loop Mode Disabled

 

P201 = 000

 

Closed Loop Mode Enabled

Feedback

Monitor

 

P201 = 002

P210

Figure 11: Closed Loop Control

4.6.2 Hardware Setup

Connect the outputs from the external feedback transducer to control terminals 3 and 4. This analogue input accepts a 0/2 - 10 V signal, has 10-bit resolution and permits a differential (floating) voltage. Ensure that the values of parameters P023 and P024 are set to 000 and that P006 is set to 000 or 002.

15 V dc power for the feedback transducer can be supplied from terminals 8 and 9 on the control block.

4.6.3 Parameter Settings

Closed loop control cannot be used unless P201 is first set to 002. Most of the parameters associated with closed loop control are shown in Figure 11. Other parameters which are also associated with closed loop control are as follows:

P001 (value = 007)

P061 (value = 012 or 013)

P210

P220

Descriptions of all closed loop control parameters are provided in section 5. For further detailed information about PI operation refer to the Siemens DA 64 Catalogue.

© Siemens plc 1997G85139-H1750-U049-B

19

26/09/97

 

Image 19
Contents Micromaster Safety Instructions Overview Wiring Guidelines to Minimise the Effects of EMI InstallationExample of an RFI Suppression Filter Installation Ideal Installation Mechanical InstallationHazard 141 160 175 184 149 172 174 138 215 185 195 204 232 MMxxx MMxxx/2 ModelMMxxx/3 500 Frame Sizes All measurements in mmPower and Motor Connections Frame Size a Electrical InstallationPower Connections Single PhasePower Connections Access Diagram Frame Size B Power and Motor Connections Frame Size BPower Connections Access Diagram Frame Size C Power and Motor Connections Frame Size CFront Panel RS485 D-type Control ConnectionsControl Terminal Block Motor Overload Protection Block DiagramFront Panel Controls Front Panel Controls & Basic OperationRefer to for a full description of each parameter Initial TestingBasic Operation GeneralStep /Action Basic Operation 10 Step GuideButton Display Analogue Control Operating Modes 4.1 Digital ControlStopping the Motor Local and Remote ControlIf the Motor Does Not Start Up General Description Hardware SetupParameter Settings Closed Loop ControlSystem Parameters Description / Notes P000Function Range Operating displayFunction P004 ∙P005 ∙ P006 P007 P009 ∙P017 ∙ P018 ∙ P011P012 ∙ P013 ∙ P014 ∙ P015 ∙ P016 ∙See P014 P022 ∙P023 ∙ P024 ∙ P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙P046 ∙ P047 ∙ P048 ∙ P050 P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045P050 = P050 = 6 or P056 P051P052 P053P064 P061P062 P063P073 ∙ P066P074 ∙ P076 ∙ P077 Inverter output terminals with power offP079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ P112 P111P113 P124 P121P122 P123P944 P971 ∙ Eeprom storage control P947 P958 P963 P967 P968 P970Cause Fault CodesFault Code F151 F15316-8BB40 21-0BC40 SpecificationsSiemens sales office for Options / AccessoriesAppropriate manner see .1 Please contact your localUSS Status Codes Setup procedure for a simple applicationSupplementary Information Application ExampleStandard Electro-Magnetic Compatibility EMCClass 1 General Industrial EMC PhenomenonIEC 1000-2-4 ENV 50 Class 2 Filtered IndustrialStandard Level Filter Class Filter Part No Environmental AspectsModel No EMC ClassP947 P958 P963 P967 P968 P970 P971 User’s Parameter SettingsP702 P880 P910 P918 P922 P923 P927 P928 P930 P931 P944Bestell-Nr SE9286-4AA86