Siemens G85139 operating instructions P121, P122, P123, P124, P125

Page 31

5. SYSTEM PARAMETERS

 

 

 

English

Parameter

 

Function

 

Range

 

Description / Notes

 

 

 

 

[Default]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P121

 

Enable/disable RUN button

0 - 1

 

0 = RUN button disabled.

 

 

 

 

[1]

 

1 = RUN button enabled (only possible if P007 = 1).

P122

 

Enable/disable

0 - 1

 

0 = FORWARD/REVERSE button disabled.

 

 

FORWARD/REVERSE button

 

[1]

 

1 = FORWARD/REVERSE button enabled (only possible if P007 = 1).

P123

 

Enable/disable JOG button

0 - 1

 

0 = JOG button disabled.

 

 

 

 

[1]

 

1 = JOG button enabled (only possible if P007 = 1).

P124

 

Enable/disable Δ and buttons

0 - 1

 

0 = Δ and buttons disabled.

 

 

 

[1]

 

1 = Δ and buttons enabled (only possible if P007 = 1).

 

 

 

 

 

 

Note: This applies for frequency adjustment only. The buttons can

 

 

 

 

 

 

still be used to change parameter values.

 

 

 

 

 

 

 

P125

 

Reverse direction inhibit

0 - 1

 

0 = Reverse direction disabled. Inhibits reverse commands from ALL

 

 

 

[1]

 

sources (reverse RUN commands result in forward rotation)

1 = Normal operation (FORWARD/REVERSE operation allowed)

P131

P132

P134

P135

P137

P140

P141

P142

P143

P201

P202

P203

P205

P206

P207

P208

Frequency setpoint (Hz)

Motor current (A)

DC link voltage (V)

Motor RPM

Output voltage (V)

Most recent fault code

Most recent fault code -1

Most recent fault code -2

Most recent fault code -3

Closed loop mode

P gain (%)

I gain (%)

Sample interval (x 25 ms)

Transducer filtering

Integral capture range (%)

Transducer type

0.00-400.00

[-]

0.0 - 99.9

 

 

 

[-]

 

Read-only parameters. These are copies of the values stored in

0

- 1000

 

 

P001 but can be accessed directly via the serial link.

 

[-]

 

 

 

 

0 - 9999

 

 

 

[-]

 

 

0

- 1000

 

 

 

[-]

 

 

0

- 9999

 

The last recorded fault code (see section 6) is stored in this parameter.

 

[-]

 

This is a copy of the code stored in P930.

 

 

 

 

 

 

 

0

- 9999

 

This parameter stores the last recorded fault code prior to that stored

 

[-]

 

in P140/P930.

 

 

 

 

0

- 9999

 

This parameter stores the last recorded fault code prior to that stored

 

[-]

 

in P141.

 

 

 

 

0

- 9999

 

This parameter stores the last recorded fault code prior to that stored

 

[-]

 

in P142.

 

 

 

 

 

0 - 2

 

0 = Normal operation (closed loop control disabled).

[0]1 = Not used.

2 = Closed loop control using analogue input for transducer feedback input.

0.0- 999.9 Proportional gain.

[1.0]

0.00 - 99.99

 

Integral gain.

[0.00]

 

0.01% corresponds to the longest integral action time.

1 - 2400

 

Sampling interval of feedback sensor.

[1]

 

 

 

0 - 255

0 =

Filter off.

[0]1 - 255 = Low pass filtering applied to sensor.

0 - 100 Percentage error above which integral term is reset to zero. [100]

0 - 1 0 = An increase in motor speed causes an increase in sensor

[0]voltage/current output.

1= An increase in motor speed causes a decrease in sensor voltage/current output.

© Siemens plc 1997G85139-H1750-U049-B

31

26/09/97

 

Image 31
Contents Micromaster Safety Instructions Overview Wiring Guidelines to Minimise the Effects of EMI InstallationExample of an RFI Suppression Filter Installation Ideal Installation Mechanical InstallationHazard 141 160 175 184 149 172 174 138 215 185 195 204 232 MMxxx MMxxx/2 ModelMMxxx/3 500 Frame Sizes All measurements in mmPower and Motor Connections Frame Size a Electrical InstallationPower Connections Single PhasePower Connections Access Diagram Frame Size B Power and Motor Connections Frame Size BPower Connections Access Diagram Frame Size C Power and Motor Connections Frame Size CFront Panel RS485 D-type Control ConnectionsControl Terminal Block Motor Overload Protection Block DiagramFront Panel Controls Front Panel Controls & Basic OperationRefer to for a full description of each parameter Initial TestingBasic Operation GeneralStep /Action Basic Operation 10 Step GuideButton Display Analogue Control Operating Modes 4.1 Digital ControlStopping the Motor Local and Remote ControlIf the Motor Does Not Start Up General Description Hardware SetupParameter Settings Closed Loop ControlSystem Parameters Description / Notes P000Function Range Operating displayFunction P004 ∙P005 ∙ P006 P007 P009 ∙P017 ∙ P018 ∙ P011P012 ∙ P013 ∙ P014 ∙ P015 ∙ P016 ∙See P014 P022 ∙P023 ∙ P024 ∙ P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙P046 ∙ P047 ∙ P048 ∙ P050 P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045P050 = P050 = 6 or P056 P051P052 P053P064 P061P062 P063P073 ∙ P066P074 ∙ P076 ∙ P077 Inverter output terminals with power offP079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ P112 P111P113 P124 P121P122 P123P944 P971 ∙ Eeprom storage control P947 P958 P963 P967 P968 P970Cause Fault CodesFault Code F151 F15316-8BB40 21-0BC40 SpecificationsSiemens sales office for Options / AccessoriesAppropriate manner see .1 Please contact your localUSS Status Codes Setup procedure for a simple applicationSupplementary Information Application ExampleStandard Electro-Magnetic Compatibility EMCClass 1 General Industrial EMC PhenomenonIEC 1000-2-4 ENV 50 Class 2 Filtered IndustrialStandard Level Filter Class Filter Part No Environmental AspectsModel No EMC ClassP947 P958 P963 P967 P968 P970 P971 User’s Parameter SettingsP702 P880 P910 P918 P922 P923 P927 P928 P930 P931 P944Bestell-Nr SE9286-4AA86