2. INSTALLATION

2.3 Electrical Installation

The electrical connectors on the MICROMASTER are shown in Figure 3. Connect the cables to the power and control terminal blocks in accordance with the information supplied in sections 2.3.1 - 2.3.4. Ensure that the leads are connected correctly and the equipment is properly earthed as shown in Figure 3.

CAUTION

The control, power supply and motor leads must be laid separately. They must not be fed through the same cable conduit/trunking.

Use screened cable for the control lead. Use Class 1 60/75oC copper wire only (for UL compliance). Tightening torque for the power (mains input and motor) terminals is 1.1 Nm.

To tighten up the power/motor terminal screws use a 4 - 5 mm cross-tip screwdriver.

2.3.1 Power and Motor Connections - Frame Size A

Ensure that the power source supplies the correct voltage and is designed for the necessary current (see section 7). Ensure that the appropriate circuit-breakers/fuses with the specified current rating are connected between the power supply and inverter (see section 7).

Connect the power and motor connections as shown in Figure 3.

WARNING

Isolate the supply before making or changing connections.

Ensure that the motor is configured for the correct supply voltage. Single/three phase 230 V

MICROMASTERS must not be connected to a 400 V three phase supply.

When synchronous machines are connected or when coupling several motors in parallel, the inverter must be operated with voltage/frequency control characteristic (P077= 0 or 2).

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

8

 

Image 8
Contents Micromaster Safety Instructions Overview Installation Wiring Guidelines to Minimise the Effects of EMI Example of an RFI Suppression Filter Installation Hazard Mechanical InstallationIdeal Installation MMxxx MMxxx/2 Model MMxxx/3 500Frame Sizes All measurements in mm 141 160 175 184 149 172 174 138 215 185 195 204 232Electrical Installation Power and Motor Connections Frame Size aSingle Phase Power ConnectionsPower and Motor Connections Frame Size B Power Connections Access Diagram Frame Size BPower and Motor Connections Frame Size C Power Connections Access Diagram Frame Size CControl Terminal Block Control ConnectionsFront Panel RS485 D-type Block Diagram Motor Overload ProtectionFront Panel Controls & Basic Operation Front Panel ControlsInitial Testing Basic OperationGeneral Refer to for a full description of each parameterButton Display Basic Operation 10 Step GuideStep /Action Operating Modes 4.1 Digital Control Analogue ControlIf the Motor Does Not Start Up Local and Remote ControlStopping the Motor Hardware Setup Parameter SettingsClosed Loop Control General DescriptionSystem Parameters P000 Function RangeOperating display Description / NotesP004 ∙ P005 ∙ P006 P007P009 ∙ FunctionP011 P012 ∙ P013 ∙ P014 ∙ P015 ∙P016 ∙ P017 ∙ P018 ∙P022 ∙ P023 ∙ P024 ∙P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙ See P014P050 = P050 = 6 or P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045P046 ∙ P047 ∙ P048 ∙ P050 P051 P052P053 P056P061 P062P063 P064P074 ∙ P076 ∙ P066P073 ∙ P079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ Inverter output terminals with power offP077 P113 P111P112 P121 P122P123 P124P944 P947 P958 P963 P967 P968 P970 P971 ∙ Eeprom storage controlFault Codes Fault CodeF151 F153 CauseSpecifications 16-8BB40 21-0BC40Options / Accessories Appropriate manner see .1Please contact your local Siemens sales office forSetup procedure for a simple application Supplementary InformationApplication Example USS Status CodesElectro-Magnetic Compatibility EMC Class 1 General IndustrialEMC Phenomenon StandardStandard Level Class 2 Filtered IndustrialIEC 1000-2-4 ENV 50 Environmental Aspects Model NoEMC Class Filter Class Filter Part NoUser’s Parameter Settings P702 P880P910 P918 P922 P923 P927 P928 P930 P931 P944 P947 P958 P963 P967 P968 P970 P971Bestell-Nr SE9286-4AA86