Siemens G85139 P022 ∙, P023 ∙ P024 ∙, P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙, See P014

Page 24

English

 

 

 

 

 

 

 

5. SYSTEM PARAMETERS

Parameter

 

Function

 

Range

 

Description / Notes

 

 

 

 

[Default]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P022

 

Maximum analogue frequency

0 - 400.00

 

Frequency corresponding to the highest analogue input value, i.e.

 

 

(Hz)

[50.00]

 

10 V, determined by P023. This can be set to a lower value than P021

 

 

 

 

 

 

to give an inverse relationship between analogue input and frequency

 

 

 

 

 

 

output.

 

 

 

 

 

 

 

 

 

i.e.

f

 

 

 

 

 

 

 

 

P021

 

 

 

 

 

 

 

 

P022

 

 

 

 

 

 

 

 

P022

 

 

 

 

 

 

 

 

P021

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

 

 

 

Note:

The output frequency is limited by values entered for

 

 

 

 

 

 

 

P012/P013.

P023

P024

Analogue input function

Analogue setpoint addition

0 - 2

[0]

0 - 2

[0]

0 = 0 V to 10 V

1 = 2 V to 10 V

2 = 2 V* to 10 V

*The inverter will come to a controlled stop if V < 1 V.

WARNING: The motor can automatically run without a potentiometer or voltage source connected between pins 3 and 4.

WARNING: With P023=2, the inverter will automatically start when V goes above 1 V. This equally applies to analogue and digital control (i.e. P006 = 0 or 1).

If the inverter is not in analogue mode (P006 = 0 or 2), setting this parameter to ‘1’ causes the analogue input value to be added.

0 = No addition.

1 = Addition of the analogue setpoint (defined by P023) to the fixed frequency or the motor potentiometer frequency.

2 = Scaling of digital/fixed setpoint by analogue input (P023) in the range 0 - 100%.

Note: By selecting a combination of reversed negative fixed frequency settings and analogue setpoint addition, it is possible to configure the inverter for ‘centre zero’ operation with a +/-5 V supply or a 0 - 10 V potentiometer so that the output frequency can be 0 Hz at any position, including the centre position.

P027

P028

P029

P031

P032

Skip frequency 2 (Hz)

Skip frequency 3 (Hz)

Skip frequency 4 (Hz)

Jog frequency right (Hz)

Jog frequency left (Hz)

0 - 400.00

[0.00]

0 - 400.00

[0.00]

0 - 400.00

[0.00]

0 - 400.00

[5.00]

0 - 400.00

[5.00]

See P014.

See P014.

See P014.

Jogging is used to advance the motor by small amounts. It is controlled via the JOG button or with a non-latching switch on one of the digital inputs (P051 to P053).

If jog right is enabled (DINn = 7), this parameter controls the frequency at which the inverter will run when the switch is closed. Unlike other setpoints, it can be set lower than the minimum frequency.

If jog left is enabled (DINn = 8), this parameter controls the frequency at which the inverter will run when the switch is closed. Unlike other setpoints, it can be set lower than the minimum frequency.

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

24

 

Image 24
Contents Micromaster Safety Instructions Overview Installation Wiring Guidelines to Minimise the Effects of EMIExample of an RFI Suppression Filter Installation Mechanical Installation Ideal InstallationHazard MMxxx MMxxx/2 Model MMxxx/3 500Frame Sizes All measurements in mm 141 160 175 184 149 172 174 138 215 185 195 204 232Electrical Installation Power and Motor Connections Frame Size aSingle Phase Power ConnectionsPower and Motor Connections Frame Size B Power Connections Access Diagram Frame Size BPower and Motor Connections Frame Size C Power Connections Access Diagram Frame Size CControl Connections Front Panel RS485 D-typeControl Terminal Block Block Diagram Motor Overload ProtectionFront Panel Controls & Basic Operation Front Panel ControlsInitial Testing Basic OperationGeneral Refer to for a full description of each parameterBasic Operation 10 Step Guide Step /ActionButton Display Operating Modes 4.1 Digital Control Analogue ControlLocal and Remote Control Stopping the MotorIf the Motor Does Not Start Up Hardware Setup Parameter SettingsClosed Loop Control General DescriptionSystem Parameters P000 Function Range Operating display Description / NotesP004 ∙ P005 ∙ P006 P007P009 ∙ FunctionP011 P012 ∙ P013 ∙ P014 ∙ P015 ∙P016 ∙ P017 ∙ P018 ∙P022 ∙ P023 ∙ P024 ∙P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙ See P014P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045 P046 ∙ P047 ∙ P048 ∙ P050P050 = P050 = 6 or P051 P052P053 P056P061 P062P063 P064P066 P073 ∙P074 ∙ P076 ∙ Inverter output terminals with power off P077P079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ P111 P112P113 P121 P122P123 P124P944 P947 P958 P963 P967 P968 P970 P971 ∙ Eeprom storage controlFault Codes Fault CodeF151 F153 CauseSpecifications 16-8BB40 21-0BC40Options / Accessories Appropriate manner see .1Please contact your local Siemens sales office forSetup procedure for a simple application Supplementary InformationApplication Example USS Status CodesElectro-Magnetic Compatibility EMC Class 1 General IndustrialEMC Phenomenon StandardClass 2 Filtered Industrial IEC 1000-2-4 ENV 50Standard Level Environmental Aspects Model NoEMC Class Filter Class Filter Part NoUser’s Parameter Settings P702 P880P910 P918 P922 P923 P927 P928 P930 P931 P944 P947 P958 P963 P967 P968 P970 P971Bestell-Nr SE9286-4AA86