Siemens G85139 operating instructions P111, P112, P113

Page 30

English

 

 

 

5. SYSTEM PARAMETERS

Parameter

 

Function

 

Range

 

Description / Notes

 

 

 

 

[Default]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P092 Serial link baud rate

3 - 7

 

[6]

P093 Serial link timeout (seconds)

0 - 240

 

[0]

P094

 

Serial link nominal system setpoint

0 - 400.00

 

 

 

(Hz)

[50.00]

 

 

 

 

 

 

P095

 

USS compatibility

0 - 2

 

 

 

 

[0]

 

 

 

 

 

 

P099

 

Option module type

0 - 1

 

 

 

 

 

[0]

P101

 

Operation for Europe or USA

0 - 1

 

 

 

 

[0]

P111

 

Inverter power rating (kW/hp)

0.0 - 50.00

 

 

 

[

]

 

 

 

 

 

 

P112

 

Inverter type (model)

[

1 - 7

 

 

 

]

P113

Inverter type (power rating)

0 - 29

 

[

]

Sets the baud rate of the RS485 serial interface (USS protocol):

3= 1200 baud

4= 2400 baud

5= 4800 baud

6= 9600 baud

7= 19200 baud

Note: Some RS232 to RS485 converters are not capable of baud rates higher than 4800.

This is the maximum permissible period between two incoming data telegrams. This feature is used to turn off the inverter in the event of a communications failure.

Timing starts after a valid data telegram has been received and if a further data telegram is not received within the specified time period, the inverter will trip and display fault code F008.

Setting the value to zero switches off the control.

Setpoints are transmitted to the inverter via the serial link as percentages. The value entered in this parameter represents 100% (HSW = 4000H).

0 = Compatible with 0.1 Hz resolution

1 = Enable 0.01 Hz resolution

2 = HSW is not scaled but represents the actual frequency value to a resolution of 0.01 Hz (e.g. 5000 = 50 Hz).

0 = Option module not present

1 = PROFIBUS module (enables parameters relating to PROFIBUS)

This sets the inverter for European or USA supply and motor frequency:

0 = Europe (50 Hz)

1 = USA (60 Hz)

Note: After setting P101 = 1 the inverter must be re-set to factory defaults. i.e. P944 = 1 to automatically set P013 = 60 Hz, P081 = 60 Hz, P082 = 1680 rpm and P085 will be displayed in hp.

Read-only parameter that indicates the power rating of the inverter in kW. e.g. 0.55 = 550 W

Note: If P101 = 1 then the rating is displayed in hp.

Read-only parameter.

 

 

 

 

 

1 = MICROMASTER series 2 (MM2)

 

 

 

2 =

COMBIMASTER

 

 

 

 

 

3 =

MIDIMASTER

 

 

 

 

 

4 = MICROMASTER Junior (MMJ)

 

 

 

5 = MICROMASTER series 3 (MM3)

 

 

 

6 = MICROMASTER Vector (MMV)

 

 

 

7 = MIDIMASTER Vector (MDV)

 

 

 

 

 

 

 

 

 

 

Read-only parameter.

 

 

 

 

 

0 =

MM12

10

= MM12/2

20

= MM37/3

1 =

MM25

11

= MM25/2

21

= MM55/3

2 =

MM37

12

= MM37/2

22

= MM75/3

3 =

MM55

13

= MM55/2

23

= MM110/3

4 =

MM75

14

= MM75/2

24

= MM150/3

5 =

MM110

15

= MM110/2

25

= MM220/3

6 =

MM150

16

= MM150/2

26

= MM300/3

7 =

MM220

17

= MM220/2

27

= MM400/3

8 =

MM300

18

= MM300/2

28

= MM550/3

 

 

 

19

= MM400/2

29

= MM750/3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

30

 

Image 30
Contents Micromaster Safety Instructions Overview Installation Wiring Guidelines to Minimise the Effects of EMIExample of an RFI Suppression Filter Installation Mechanical Installation Ideal InstallationHazard Frame Sizes All measurements in mm MMxxx MMxxx/2 ModelMMxxx/3 500 141 160 175 184 149 172 174 138 215 185 195 204 232Electrical Installation Power and Motor Connections Frame Size aSingle Phase Power ConnectionsPower and Motor Connections Frame Size B Power Connections Access Diagram Frame Size BPower and Motor Connections Frame Size C Power Connections Access Diagram Frame Size CControl Connections Front Panel RS485 D-typeControl Terminal Block Block Diagram Motor Overload ProtectionFront Panel Controls & Basic Operation Front Panel ControlsGeneral Initial TestingBasic Operation Refer to for a full description of each parameterBasic Operation 10 Step Guide Step /ActionButton Display Operating Modes 4.1 Digital Control Analogue ControlLocal and Remote Control Stopping the MotorIf the Motor Does Not Start Up Closed Loop Control Hardware SetupParameter Settings General DescriptionSystem Parameters Operating display P000Function Range Description / NotesP009 ∙ P004 ∙P005 ∙ P006 P007 FunctionP016 ∙ P011P012 ∙ P013 ∙ P014 ∙ P015 ∙ P017 ∙ P018 ∙P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙ P022 ∙P023 ∙ P024 ∙ See P014P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045 P046 ∙ P047 ∙ P048 ∙ P050P050 = P050 = 6 or P053 P051P052 P056P063 P061P062 P064P066 P073 ∙P074 ∙ P076 ∙ Inverter output terminals with power off P077P079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ P111 P112P113 P123 P121P122 P124P944 P947 P958 P963 P967 P968 P970 P971 ∙ Eeprom storage controlF151 F153 Fault CodesFault Code CauseSpecifications 16-8BB40 21-0BC40Please contact your local Options / AccessoriesAppropriate manner see .1 Siemens sales office forApplication Example Setup procedure for a simple applicationSupplementary Information USS Status CodesEMC Phenomenon Electro-Magnetic Compatibility EMCClass 1 General Industrial StandardClass 2 Filtered Industrial IEC 1000-2-4 ENV 50Standard Level EMC Class Environmental AspectsModel No Filter Class Filter Part NoP910 P918 P922 P923 P927 P928 P930 P931 P944 User’s Parameter SettingsP702 P880 P947 P958 P963 P967 P968 P970 P971Bestell-Nr SE9286-4AA86