Siemens G85139 operating instructions Operating Modes 4.1 Digital Control, Analogue Control

Page 17

4. OPERATING MODES

English

4.OPERATING MODES 4.1 Digital Control

For a basic startup configuration using digital control, proceed as follows:

(1)Connect control terminal 5 to terminal 8 via a simple on/off switch. This sets up the motor for clockwise rotation (default).

(2)Apply mains power to the inverter. Set parameter P009 to 002 or 003 to enable all parameters to be adjusted.

(3)Check that parameter P006 is set to 000 to specify digital setpoint.

(4)Set parameter P007 to 000 to specify digital input (i.e. DIN1 (terminal 5) in this case) and disable the front panel controls.

(5)Set parameter P005 to the desired frequency setpoint.

(6)Set parameters P081 to P085 in accordance with the rating plate on the motor (see Figure 10).

Note: In many cases, when default factory parameters are used, the default stator resistance set in P089 will generally suit the default power rating set in P085. Should the inverter and motor ratings differ greatly, it is recommended that the stator resistance of the motor is measured and entered manually into P089. Continuous Boost (P078) and Starting Boost (P079) are dependent on the value of Stator Resistance - too high a value may cause overcurrent trips

(7)Set the external on/off switch to ON. The inverter will now drive the motor at the frequency set by P005.

4.2 Analogue Control

For a basic startup configuration using analogue voltage control, proceed as follows:

(1)Connect control terminal 5 to terminal 8 via a simple on/off switch. This sets up the motor for clockwise rotation (default).

(2)Connect a 4.7 kΩ potentiometer to the control terminals as shown in Figure 6 or connect pin 2 (0V) to pin 4 and a 0 - 10 V signal between pin 2 (0V) and pin 3 (AIN+).

(3)Apply mains power to the inverter. Set parameter P009 to 002 or 003 to enable all parameters to be adjusted.

(4)Set parameter P006 to 001 to specify analogue setpoint.

(5)Set parameter P007 to 000 to specify digital input (i.e. DIN1 (terminal 5) in this case) and disable the front panel controls.

(6)Set parameters P021 and P022 to specify the minimum and maximum output frequency settings.

(7)Set parameters P081 to P085 in accordance with the rating plate on the motor (see Figure 10).

Note: In many cases, when default factory parameters are used, the default stator resistance set in P089 will generally suit the default power rating set in P085. Should the inverter and motor ratings differ greatly, it is recommended that the stator resistance of the motor is measured and entered manually into P089. Continuous Boost (P078) and Starting Boost (P079) are dependent on the value of Stator Resistance - too high a value may cause overcurrent trips

(8)Set the external on/off switch to ON. Turn the potentiometer (or adjust the analogue control voltage) until the desired frequency is displayed on the inverter.

© Siemens plc 1997G85139-H1750-U049-B

17

26/09/97

 

Image 17
Contents Micromaster Safety Instructions Overview Wiring Guidelines to Minimise the Effects of EMI InstallationExample of an RFI Suppression Filter Installation Hazard Mechanical InstallationIdeal Installation MMxxx/3 500 MMxxx MMxxx/2 ModelFrame Sizes All measurements in mm 141 160 175 184 149 172 174 138 215 185 195 204 232Power and Motor Connections Frame Size a Electrical InstallationPower Connections Single PhasePower Connections Access Diagram Frame Size B Power and Motor Connections Frame Size BPower Connections Access Diagram Frame Size C Power and Motor Connections Frame Size CControl Terminal Block Control ConnectionsFront Panel RS485 D-type Motor Overload Protection Block DiagramFront Panel Controls Front Panel Controls & Basic OperationBasic Operation Initial TestingGeneral Refer to for a full description of each parameterButton Display Basic Operation 10 Step GuideStep /Action Analogue Control Operating Modes 4.1 Digital ControlIf the Motor Does Not Start Up Local and Remote ControlStopping the Motor Parameter Settings Hardware SetupClosed Loop Control General DescriptionSystem Parameters Function Range P000Operating display Description / NotesP005 ∙ P006 P007 P004 ∙P009 ∙ FunctionP012 ∙ P013 ∙ P014 ∙ P015 ∙ P011P016 ∙ P017 ∙ P018 ∙P023 ∙ P024 ∙ P022 ∙P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙ See P014P050 = P050 = 6 or P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045P046 ∙ P047 ∙ P048 ∙ P050 P052 P051P053 P056P062 P061P063 P064P074 ∙ P076 ∙ P066P073 ∙ P079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ Inverter output terminals with power offP077 P113 P111P112 P122 P121P123 P124P944 P971 ∙ Eeprom storage control P947 P958 P963 P967 P968 P970Fault Code Fault CodesF151 F153 Cause16-8BB40 21-0BC40 SpecificationsAppropriate manner see .1 Options / AccessoriesPlease contact your local Siemens sales office forSupplementary Information Setup procedure for a simple applicationApplication Example USS Status CodesClass 1 General Industrial Electro-Magnetic Compatibility EMCEMC Phenomenon StandardStandard Level Class 2 Filtered IndustrialIEC 1000-2-4 ENV 50 Model No Environmental AspectsEMC Class Filter Class Filter Part NoP702 P880 User’s Parameter SettingsP910 P918 P922 P923 P927 P928 P930 P931 P944 P947 P958 P963 P967 P968 P970 P971Bestell-Nr SE9286-4AA86