Siemens G85139 operating instructions Fault Codes, F151 F153, Cause, Corrective Action

Page 34

English

6. FAULT CODES

6. FAULT CODES

In the event of a failure, the inverter switches off and a fault code appears on the display. The last fault that occurred is stored in parameter P930. e.g. ‘0003’ indicates that the last error was F003.

Fault Code

F001

F002

F003

F005

F008

F010

F011

F012

F013

F018

F030

F031

F033

F036

F074

F106

F112

F151 - F153

F188

F201

F212

Cause

Overvoltage

Overcurrent

Overload

Inverter overtemperature (internal PTC)

USS protocol timeout

Initialisation fault / Parameter loss *

Internal interface fault *

External trip (PTC)

Programme fault *

Auto-restart after fault.

PROFIBUS link failure

Option module to link failure

PROFIBUS configuration error

PROFIBUS module watchdog trip

Motor overtemperature by I2t calculation

Parameter fault P006

Parameter fault P012/P013

Digital input parameter fault

Automatic calibration failure

P006 = 1 while P201 = 2

Parameter fault P211/P212

Corrective Action

Check whether supply voltage is within the limits indicated on the rating plate. Increase the ramp down time (P003).

Check whether the required braking power is within the specified limits.

Check whether the motor power corresponds to the inverter power. Check that the cable length limits have not been exceeded.

Check motor lead and motor for short-circuits and earth faults.

Check whether the motor parameters (P081 - P086) correspond with the motor being used.

Check the stator resistance (P089). Increase the ramp-up time (P002). Reduce the boost set in P078 and P079.

Check whether the motor is obstructed or overloaded.

Check whether the motor is overloaded.

Increase the maximum motor frequency if a motor with high slip is used.

Check that the ambient temperature is not too high.

Check that the air inlet and outlet are not obstructed.

Check that the integral fan is working.

Check the serial interface.

Check the settings of the bus master and P091 - P093.

Check whether the timeout interval is too short (P093).

Check the entire parameter set. Set P009 to ‘0000’ before power down.

Switch off power and switch on again.

Check if motor is overloaded.

Switch off power and switch on again.

Automatic re-start after fault (P018) is pending.

WARNING: The inverter may start at any time.

Check the integrity of the link.

Check the integrity of the link.

Check the PROFIBUS configuration.

Replace PROFIBUS module

Check that the motor current does not exceed the value set in P083.

Parameterise fixed frequency(ies) and/or motor potentiometer on the digital inputs.

Set parameter P012 < P013.

Check the settings of digital inputs P051 to P053.

Motor not connected to inverter - connect motor.

If the fault persists, set P088 = 0 and then enter the stator resistance of the motor into P089 manually.

Change parameter P006 and/or P201.

Set parameter P211 < P212.

*Ensure that the wiring guidelines described in section 2.1 have been complied with.

When the fault has been corrected the inverter can be reset. To do this press button P twice (once to display P000 and the second time to reset the fault), or erase the fault via a binary input (see parameters P051 - P053 in section 5) or via the serial interface.

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

34

 

Image 34
Contents Micromaster Safety Instructions Overview Installation Wiring Guidelines to Minimise the Effects of EMIExample of an RFI Suppression Filter Installation Ideal Installation Mechanical InstallationHazard Frame Sizes All measurements in mm MMxxx MMxxx/2 ModelMMxxx/3 500 141 160 175 184 149 172 174 138 215 185 195 204 232Electrical Installation Power and Motor Connections Frame Size aSingle Phase Power ConnectionsPower and Motor Connections Frame Size B Power Connections Access Diagram Frame Size BPower and Motor Connections Frame Size C Power Connections Access Diagram Frame Size CFront Panel RS485 D-type Control ConnectionsControl Terminal Block Block Diagram Motor Overload ProtectionFront Panel Controls & Basic Operation Front Panel ControlsGeneral Initial TestingBasic Operation Refer to for a full description of each parameterStep /Action Basic Operation 10 Step GuideButton Display Operating Modes 4.1 Digital Control Analogue ControlStopping the Motor Local and Remote ControlIf the Motor Does Not Start Up Closed Loop Control Hardware SetupParameter Settings General DescriptionSystem Parameters Operating display P000Function Range Description / NotesP009 ∙ P004 ∙P005 ∙ P006 P007 FunctionP016 ∙ P011P012 ∙ P013 ∙ P014 ∙ P015 ∙ P017 ∙ P018 ∙P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙ P022 ∙P023 ∙ P024 ∙ See P014P046 ∙ P047 ∙ P048 ∙ P050 P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045P050 = P050 = 6 or P053 P051P052 P056P063 P061P062 P064P073 ∙ P066P074 ∙ P076 ∙ P077 Inverter output terminals with power offP079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ P112 P111P113 P123 P121 P122 P124P944 P947 P958 P963 P967 P968 P970 P971 ∙ Eeprom storage controlF151 F153 Fault CodesFault Code CauseSpecifications 16-8BB40 21-0BC40Please contact your local Options / AccessoriesAppropriate manner see .1 Siemens sales office forApplication Example Setup procedure for a simple applicationSupplementary Information USS Status CodesEMC Phenomenon Electro-Magnetic Compatibility EMCClass 1 General Industrial StandardIEC 1000-2-4 ENV 50 Class 2 Filtered IndustrialStandard Level EMC Class Environmental AspectsModel No Filter Class Filter Part NoP910 P918 P922 P923 P927 P928 P930 P931 P944 User’s Parameter SettingsP702 P880 P947 P958 P963 P967 P968 P970 P971Bestell-Nr SE9286-4AA86