Siemens G85139 operating instructions P061, P062, P063, P064, P065

Page 27

5. SYSTEM PARAMETERS

Parameter

 

Function

Range

 

 

 

[Default]

 

 

 

 

 

 

 

P061

 

Selection relay output RL1

0 - 13

 

 

[6]

 

 

 

P062

 

Electro-mechanical brake option

0 - 4

 

 

control

[0]

 

 

 

 

 

P063

 

External brake release delay

0 - 20.0

 

 

(seconds)

[1.0]

 

 

 

 

 

P064

 

External brake stopping time

0 - 20.0

 

 

(seconds)

[1.0]

English

Description / Notes

Value

Relay function

Active 3

 

0

No function assigned (relay not active)

Low

 

1

Inverter is running

High

 

2

Inverter frequency 0.0 Hz

Low

 

3

Motor run right has been selected

High

 

4

External brake on (see parameters P063/P064)

Low

 

5

Inverter frequency less than or equal to minimum

Low

 

 

frequency

 

 

6

Fault indication 1

Low

 

7

Inverter frequency greater than or equal to setpoint

High

 

8

Warning active 2

Low

 

9

Output current greater than or equal to P065

High

 

10

Motor current limit (warning) 2

Low

 

11

Motor over temperature (warning) 2

Low

 

12

Closed loop motor LOW speed limit

High

 

13

Closed loop motor HIGH speed limit

High

1

Inverter switches off (see parameter P930 and section 6).

 

2

 

 

 

 

Inverter does not switch off (see parameter P931).

3‘Active low’ = relay OPEN. ‘Active high’ = relay CLOSED.

This operates in the same manner as the external brake control (described in P063/P064), except that the relay is not activated.

0 = Normal stop mode

1 - 3 = Do not use

4 = Combination stop mode

Only effective if the relay output is set to control an external brake (P061 = 4). In this case when the inverter is switched on, it will run at the minimum frequency for the time set by this parameter before releasing the brake control relay and ramping up (see illustration in P064).

As P063, only effective if the relay output is set to control an external brake. This defines the period for which the inverter continues to run at the minimum frequency after ramping down and while the external brake is applied.

f

ON

OFF

fmin

 

 

 

 

 

 

 

t

 

t

 

 

 

 

t

 

 

 

 

 

 

 

A = Brake applied

P063

 

 

 

 

P064

 

 

 

B

 

 

 

 

B = Brake removed

A

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

Notes: (1) Settings for P063 and P064 should be slightly longer

 

 

 

 

 

 

than the actual time taken for the external brake to

 

 

 

 

 

 

apply and release respectively.

 

 

 

 

 

 

(2) Setting P063 or P064 to too high a value, especially

 

 

 

 

 

 

with P012 set to a high value, can cause an

 

 

 

 

 

 

overcurrent warning or trip as the inverter attempts to

 

 

 

 

 

 

move a locked motor shaft.

P065

 

Current threshold for relay (A)

0 - 99.9

 

This parameter is used when P061 = 9. The relay switches on when

 

 

 

[1.0]

 

the motor current is greater than the value of P065 and switches off

 

 

 

 

 

 

when the current falls to 90% of the value of P065 (hysteresis).

 

 

 

 

 

 

 

© Siemens plc 1997G85139-H1750-U049-B

27

26/09/97

 

Image 27
Contents Micromaster Safety Instructions Overview Wiring Guidelines to Minimise the Effects of EMI InstallationExample of an RFI Suppression Filter Installation Mechanical Installation Ideal InstallationHazard 141 160 175 184 149 172 174 138 215 185 195 204 232 MMxxx MMxxx/2 ModelMMxxx/3 500 Frame Sizes All measurements in mmPower and Motor Connections Frame Size a Electrical InstallationPower Connections Single PhasePower Connections Access Diagram Frame Size B Power and Motor Connections Frame Size BPower Connections Access Diagram Frame Size C Power and Motor Connections Frame Size CControl Connections Front Panel RS485 D-typeControl Terminal Block Motor Overload Protection Block DiagramFront Panel Controls Front Panel Controls & Basic OperationRefer to for a full description of each parameter Initial TestingBasic Operation GeneralBasic Operation 10 Step Guide Step /ActionButton Display Analogue Control Operating Modes 4.1 Digital ControlLocal and Remote Control Stopping the MotorIf the Motor Does Not Start Up General Description Hardware SetupParameter Settings Closed Loop ControlSystem Parameters Description / Notes P000Function Range Operating displayFunction P004 ∙P005 ∙ P006 P007 P009 ∙P017 ∙ P018 ∙ P011P012 ∙ P013 ∙ P014 ∙ P015 ∙ P016 ∙See P014 P022 ∙P023 ∙ P024 ∙ P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045 P046 ∙ P047 ∙ P048 ∙ P050P050 = P050 = 6 or P056 P051P052 P053P064 P061P062 P063P066 P073 ∙P074 ∙ P076 ∙ Inverter output terminals with power off P077P079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ P111 P112P113 P124 P121P122 P123P944 P971 ∙ Eeprom storage control P947 P958 P963 P967 P968 P970Cause Fault CodesFault Code F151 F15316-8BB40 21-0BC40 SpecificationsSiemens sales office for Options / AccessoriesAppropriate manner see .1 Please contact your localUSS Status Codes Setup procedure for a simple applicationSupplementary Information Application ExampleStandard Electro-Magnetic Compatibility EMCClass 1 General Industrial EMC PhenomenonClass 2 Filtered Industrial IEC 1000-2-4 ENV 50Standard Level Filter Class Filter Part No Environmental AspectsModel No EMC ClassP947 P958 P963 P967 P968 P970 P971 User’s Parameter SettingsP702 P880 P910 P918 P922 P923 P927 P928 P930 P931 P944Bestell-Nr SE9286-4AA86