5. SYSTEM PARAMETERS

English

Parameter

P011

 

Function

 

Range

 

 

 

[Default]

 

 

 

 

 

 

 

Frequency setpoint memory

0 - 1

 

 

[0]

Description / Notes

0 = Disabled

1 = Enabled after switch-off. i.e. The setpoint alterations made with the Δ / buttons or digital inputs are stored even when power has been removed from the inverter.

P012

P013

P014

P015

Minimum motor frequency (Hz)

0 - 400.00

 

Sets the minimum motor frequency (must be less than the value of

 

[0.00]

 

P013).

 

 

 

 

 

 

Maximum motor frequency (Hz)

0 - 400.00

 

Sets the maximum motor frequency.

 

[50.00]

 

 

 

 

 

 

 

 

Skip frequency 1 (Hz)

0 - 400.00

 

A skip frequency can be set with this parameter to avoid the effects of

 

[0.00]

 

mechanical resonance. Frequencies within +/-(value of P019) of this

 

 

 

 

setting are suppressed. Stationary operation is not possible within the

 

 

 

 

suppressed frequency range - the range is just passed through.

 

 

 

 

 

Automatic restart after mains

0 - 1

 

Setting this parameter to ‘1’ enables the inverter to restart automatically

failure.

[0]

 

after a mains break or ‘brownout’, provided the run/stop switch is still

 

 

 

 

closed, P007 = 0 and P910 = 0, 2 or 4.

 

 

 

0 =

Disabled

 

 

 

1 =

Automatic restart

P016

Start on the fly

0 - 2

 

[0]

Allows the inverter to start onto a spinning motor.

Under normal circumstances the inverter runs the motor up from 0 Hz. However, if the motor is still spinning or is being driven by the load, it will undergo braking before running back up to the setpoint - this can cause an overcurrent trip. By using a flying restart, the inverter ‘homes in’ on the motor's speed and runs it up from that speed to the setpoint.Note: If the motor has stopped or is rotating slowly, some ‘rocking’ may occur as the inverter senses the direction of rotation prior to restarting.(See also P020)

0 = Normal restart

1 = Flying restart after power up, fault or OFF2 ( if P018 = 1).

2 = Flying restart every time (useful in circumstances where the motor can be driven by the load).

P017

P018

Smoothing type

1 - 2

1 =

Continuous smoothing (as defined by P004).

 

[1]

2 =

Discontinuous smoothing. This provides a fast unsmoothed

 

 

 

response to STOP commands and requests to reduce frequency.

Note: P004 must be set to a value > 0.0 for this parameter to have any effect.

Automatic restart after fault

0 - 1

Automatic restart after fault:

 

[0]

0 =

Disabled

 

 

1 =

The inverter will attempt to restart up to 5 times after a fault. If

 

 

 

the fault is not cleared after the 5th attempt, the inverter will

 

 

 

remain in the fault state until reset.

WARNING: While waiting to re-start, the display will flash. This means that a start is pending and may happen at any time. Fault codes can be observed in P930.

P019

P020

P021

Skip frequency bandwidth (Hz)

0 - 10.00

 

Frequencies set by P014, P027, P028 or P029 that are within +/- the

 

[2.00]

 

value of P019 are suppressed.

 

 

 

 

 

Flying start ramp time (seconds)

0.50 - 25.0

 

Used in conjunction with P016 (set longer times if persistent F002 trips

 

 

[5.0]

 

occur).

Minimum analogue frequency (Hz)

0 - 400.00

 

Frequency corresponding to the lowest analogue input value, i.e.

 

[0.00]

 

0 V or 2 V. This can be set to a higher value than P022 to give an

 

 

 

 

inverse relationship between analogue input and frequency output (see

 

 

 

 

diagram in P022).

© Siemens plc 1997G85139-H1750-U049-B

23

26/09/97

 

Image 23
Contents Micromaster Safety Instructions Overview Wiring Guidelines to Minimise the Effects of EMI InstallationExample of an RFI Suppression Filter Installation Hazard Mechanical InstallationIdeal Installation 141 160 175 184 149 172 174 138 215 185 195 204 232 MMxxx MMxxx/2 ModelMMxxx/3 500 Frame Sizes All measurements in mmPower and Motor Connections Frame Size a Electrical InstallationPower Connections Single PhasePower Connections Access Diagram Frame Size B Power and Motor Connections Frame Size BPower Connections Access Diagram Frame Size C Power and Motor Connections Frame Size CControl Terminal Block Control ConnectionsFront Panel RS485 D-type Motor Overload Protection Block DiagramFront Panel Controls Front Panel Controls & Basic OperationRefer to for a full description of each parameter Initial TestingBasic Operation GeneralButton Display Basic Operation 10 Step GuideStep /Action Analogue Control Operating Modes 4.1 Digital ControlIf the Motor Does Not Start Up Local and Remote ControlStopping the Motor General Description Hardware SetupParameter Settings Closed Loop ControlSystem Parameters Description / Notes P000Function Range Operating displayFunction P004 ∙P005 ∙ P006 P007 P009 ∙P017 ∙ P018 ∙ P011P012 ∙ P013 ∙ P014 ∙ P015 ∙ P016 ∙See P014 P022 ∙P023 ∙ P024 ∙ P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙P050 = P050 = 6 or P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045P046 ∙ P047 ∙ P048 ∙ P050 P056 P051P052 P053P064 P061P062 P063P074 ∙ P076 ∙ P066P073 ∙ P079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ Inverter output terminals with power offP077 P113 P111P112 P124 P121P122 P123P944 P971 ∙ Eeprom storage control P947 P958 P963 P967 P968 P970Cause Fault CodesFault Code F151 F15316-8BB40 21-0BC40 SpecificationsSiemens sales office for Options / AccessoriesAppropriate manner see .1 Please contact your localUSS Status Codes Setup procedure for a simple applicationSupplementary Information Application ExampleStandard Electro-Magnetic Compatibility EMCClass 1 General Industrial EMC PhenomenonStandard Level Class 2 Filtered IndustrialIEC 1000-2-4 ENV 50 Filter Class Filter Part No Environmental AspectsModel No EMC ClassP947 P958 P963 P967 P968 P970 P971 User’s Parameter SettingsP702 P880 P910 P918 P922 P923 P927 P928 P930 P931 P944Bestell-Nr SE9286-4AA86