5. SYSTEM PARAMETERS

Parameter

Function

 

Range

 

Description / Notes

 

 

 

 

[Default]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P004

Smoothing (seconds)

0 - 40.0

 

[0.0]

Used to smooth the acceleration/deceleration of the motor (useful in applications where it is important to avoid ‘jerking’, e.g. conveyor systems, textiles, etc.).

Smoothing is only effective if the ramp up/down time exceeds 0.3 s.

Frequency

 

 

P002 = 10 s

 

 

fmax

 

 

(P013)

 

 

0 Hz

 

 

P004

P004

Time

= 5 s

= 5 s

 

Total acceleration time

= 15 s

Note: The smoothing curve for deceleration is based on the ramp up gradient (P002) and is added to the ramp down time set by P003. Therefore, the ramp down time is affected by changes to P002.

P005

P006

P007

Digital frequency setpoint (Hz)

Frequency setpoint source selection

Keypad control

0 - 400.00

[5.00]

0 - 2

[0]

0 - 1

[1]

Sets the frequency that the inverter will run at when operated in digital mode. Only effective if P006 set to ‘0’.

Sets the control mode of the inverter.

0 = Digital. The inverter runs at the frequency set in P005. Alternatively, if P007 is set to zero, the frequency may be controlled by setting any two of binary inputs P051 - P053 to values of 11 and 12.

1 = Analogue. Control via analogue input signal.

2 = Fixed frequency or motor potentiometer. Fixed frequency is only selected if the value of at least one binary input (P051 - P053) = 6, 17 or 18.

Notes: (1) If P006 = 1 and the inverter is set up for remote control operation, the analogue inputs remain active.

(2)Motor potentiometer setpoints via digital inputs are stored when P011 = 1.

0 = Front panel buttons disabled (except STOP, Δ and ). Control is via digital inputs (see parameters P051 - P053). Δ and may still be used to control frequency provided that P124 = 1 and a digital input has not been selected to perform this function.

1 = Front panel buttons enabled (can be individually disabled depending on the setting of parameters P121 - P124).

Note: The digital inputs for RUN, REVERSE, JOG and increase/ decrease frequency are disabled.

P009

Parameter protection setting

0 - 3

 

[0]

Determines which parameters can be adjusted:

0 = Only parameters from P001 to P009 can be read/set.

1 = Parameters from P001 to P009 can be set and all other parameters can only be read.

2 = All parameters can be read/set but P009 automatically resets to 0 when power is removed.

3 = All parameters can be read/set.

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

22

 

Image 22
Contents Micromaster Safety Instructions Overview Installation Wiring Guidelines to Minimise the Effects of EMIExample of an RFI Suppression Filter Installation Ideal Installation Mechanical InstallationHazard Frame Sizes All measurements in mm MMxxx MMxxx/2 ModelMMxxx/3 500 141 160 175 184 149 172 174 138 215 185 195 204 232Electrical Installation Power and Motor Connections Frame Size aSingle Phase Power ConnectionsPower and Motor Connections Frame Size B Power Connections Access Diagram Frame Size BPower and Motor Connections Frame Size C Power Connections Access Diagram Frame Size CFront Panel RS485 D-type Control ConnectionsControl Terminal Block Block Diagram Motor Overload ProtectionFront Panel Controls & Basic Operation Front Panel ControlsGeneral Initial TestingBasic Operation Refer to for a full description of each parameterStep /Action Basic Operation 10 Step GuideButton Display Operating Modes 4.1 Digital Control Analogue ControlStopping the Motor Local and Remote ControlIf the Motor Does Not Start Up Closed Loop Control Hardware Setup Parameter Settings General DescriptionSystem Parameters Operating display P000Function Range Description / NotesP009 ∙ P004 ∙P005 ∙ P006 P007 FunctionP016 ∙ P011P012 ∙ P013 ∙ P014 ∙ P015 ∙ P017 ∙ P018 ∙P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙ P022 ∙P023 ∙ P024 ∙ See P014P046 ∙ P047 ∙ P048 ∙ P050 P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045P050 = P050 = 6 or P053 P051P052 P056P063 P061P062 P064P073 ∙ P066P074 ∙ P076 ∙ P077 Inverter output terminals with power offP079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ P112 P111P113 P123 P121P122 P124P944 P947 P958 P963 P967 P968 P970 P971 ∙ Eeprom storage controlF151 F153 Fault CodesFault Code CauseSpecifications 16-8BB40 21-0BC40Please contact your local Options / AccessoriesAppropriate manner see .1 Siemens sales office forApplication Example Setup procedure for a simple applicationSupplementary Information USS Status CodesEMC Phenomenon Electro-Magnetic Compatibility EMCClass 1 General Industrial StandardIEC 1000-2-4 ENV 50 Class 2 Filtered IndustrialStandard Level EMC Class Environmental AspectsModel No Filter Class Filter Part NoP910 P918 P922 P923 P927 P928 P930 P931 P944 User’s Parameter SettingsP702 P880 P947 P958 P963 P967 P968 P970 P971Bestell-Nr SE9286-4AA86