Siemens G85139 operating instructions P077, P079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙

Page 29

5. SYSTEM PARAMETERS

 

 

 

 

 

 

 

 

 

 

English

Parameter

 

Function

 

Range

 

Description / Notes

 

 

 

 

[Default]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P077

 

Control mode

0 - 2

 

Controls the relationship between the speed of the motor and the

 

 

 

[1]

 

voltage supplied by the inverter. One of two modes can be selected:

 

 

 

 

 

 

0/1 = Linear voltage/frequency

 

 

 

 

 

 

Use this curve for synchronous motors or motors

 

 

 

 

 

 

connected in parallel.

 

 

 

 

 

 

2 = Quadratic voltage/frequency relationship

 

 

 

 

 

 

This is suitable for centrifugal pumps and fans.

 

 

 

 

 

 

VN

 

 

 

 

 

 

 

Vmax

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VN (P084)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0/1

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fN (P081)

P078 Continuous boost (%)

0 - 250

 

[100]

Operates continuously over the whole frequency range.

For many applications it is necessary to increase low frequency torque. This parameter sets the start-up voltage at 0 Hz to adjust the available torque for low frequency operation. 100% setting will produce rated motor current at low frequencies.

P079

P081

P082

P083

P084

P085

P089

P091

 

 

 

 

WARNING:

If P078 is set too high, overheating of the motor

 

 

 

 

 

 

and/or an overcurrent trip (F002) can occur.

 

 

 

 

 

Starting boost (%)

0 - 250

 

For drives which require a high initial starting torque, it is possible to

 

[0]

 

set an additional current (added to the setting in P078) during ramping.

 

 

 

 

This is only effective during initial start up and until the frequency

 

 

 

 

setpoint is reached.

 

 

 

 

Note:

This increase is in addition to P078.

 

 

 

 

 

 

Nominal frequency for motor (Hz)

0 - 400.00

 

 

 

 

 

[50.00]

 

 

 

 

Nominal speed for motor (RPM)

0 - 9999

 

 

 

 

 

[

]

These parameters must be set for the motor used.

Nominal current for motor (A)

0.1 - 99.9

Read the specifications on the motor’s rating plate (see Figure 10 in

 

 

[

]

section 3.2.1).

 

Nominal voltage for motor (V)

0 - 1000

Note: The inverter’s default setting vary according to the power rating.

 

 

[

]

 

 

 

Nominal power for motor (kW/hp)

0 - 100.0

 

 

 

 

 

[

]

 

 

 

Stator resistance (Ω)

0.01-100.00

The stator resistance of the motor should be entered in this parameter.

 

[

]

The value entered should be the resistance between any two phases

 

 

 

 

with the motor connected. The measurement should be made at the

 

 

 

 

inverter output terminals with power off.

 

 

 

 

Note:

If the value of P089 is too high then an overcurrent trip

 

 

 

 

 

(F002) may occur.

 

 

 

 

 

Serial link slave address

0 - 30

 

Up to 31 inverters can be connected via the serial link and controlled

 

[0]

 

by a computer or PLC using the USS protocol. This parameter sets a

 

 

 

 

unique address for the inverter.

 

 

 

 

 

 

 

© Siemens plc 1997G85139-H1750-U049-B

29

26/09/97

 

Image 29
Contents Micromaster Safety Instructions Overview Wiring Guidelines to Minimise the Effects of EMI InstallationExample of an RFI Suppression Filter Installation Hazard Mechanical InstallationIdeal Installation MMxxx/3 500 MMxxx MMxxx/2 ModelFrame Sizes All measurements in mm 141 160 175 184 149 172 174 138 215 185 195 204 232Power and Motor Connections Frame Size a Electrical InstallationPower Connections Single PhasePower Connections Access Diagram Frame Size B Power and Motor Connections Frame Size BPower Connections Access Diagram Frame Size C Power and Motor Connections Frame Size CControl Terminal Block Control ConnectionsFront Panel RS485 D-type Motor Overload Protection Block DiagramFront Panel Controls Front Panel Controls & Basic OperationBasic Operation Initial TestingGeneral Refer to for a full description of each parameterButton Display Basic Operation 10 Step GuideStep /Action Analogue Control Operating Modes 4.1 Digital ControlIf the Motor Does Not Start Up Local and Remote ControlStopping the Motor Parameter Settings Hardware SetupClosed Loop Control General DescriptionSystem Parameters Function Range P000Operating display Description / NotesP005 ∙ P006 P007 P004 ∙P009 ∙ FunctionP012 ∙ P013 ∙ P014 ∙ P015 ∙ P011P016 ∙ P017 ∙ P018 ∙P023 ∙ P024 ∙ P022 ∙P027 ∙ P028 ∙ P029 ∙ P031 ∙ P032 ∙ See P014P050 = P050 = 6 or P041 ∙ P042 ∙ P043 ∙ P044 ∙ P045P046 ∙ P047 ∙ P048 ∙ P050 P052 P051 P053 P056P062 P061P063 P064P074 ∙ P076 ∙ P066P073 ∙ P079 ∙ P081 P082 P083 P084 P085 P089 ∙ P091 ∙ Inverter output terminals with power offP077 P113 P111P112 P122 P121P123 P124P944 P971 ∙ Eeprom storage control P947 P958 P963 P967 P968 P970Fault Code Fault CodesF151 F153 Cause16-8BB40 21-0BC40 SpecificationsAppropriate manner see .1 Options / AccessoriesPlease contact your local Siemens sales office forSupplementary Information Setup procedure for a simple applicationApplication Example USS Status CodesClass 1 General Industrial Electro-Magnetic Compatibility EMCEMC Phenomenon StandardStandard Level Class 2 Filtered IndustrialIEC 1000-2-4 ENV 50 Model No Environmental AspectsEMC Class Filter Class Filter Part NoP702 P880 User’s Parameter SettingsP910 P918 P922 P923 P927 P928 P930 P931 P944 P947 P958 P963 P967 P968 P970 P971Bestell-Nr SE9286-4AA86