Hitachi L300P Series service manual Others

Page 10

Function mode

 

Code

Function name

 

SJ300 Setting range

Initial data

Note

 

 

-FE/-FU/-F

 

 

 

 

 

 

 

 

 

 

b034

RUN time/Power ON time level

0.-9999./1000-6553(10000-65530)hr

0.

 

 

b035

Operation direction restrict

00(Reverse is valid)/01(Only forward)/02(Only reverse)

00

 

 

b036

Start reduced voltage

 

00(Start reduced voltage time small)-06(Start reduced voltage time large)

06

 

 

b037

Display selection

 

 

00(all display)/01(each function display)/02(User setting / main setting)

00

 

 

b040

Torque limit mode selection

00(4 quadrant mode)/01(Terminal operation)/

00

 

 

02(Analog input)/03(Option1)/04(Option2)

 

 

 

 

 

 

 

 

 

 

 

b041

Torque limit level 1 setting

0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>

150.

 

 

(Forward-driving at

 

 

 

 

 

4 quadrant mode)

 

 

 

 

 

 

 

Torque limit level 2 setting

 

 

 

 

b042

(Reverse-regenerating at

0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>

150.

 

 

 

4 quadrant mode)

 

 

 

 

 

 

 

Torque limit level 3 setting

 

 

 

 

b043

(Reverse-driving at

 

 

0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>

150.

 

 

 

4 quadrant mode)

 

 

 

 

 

 

 

Torque limit level 4 setting

 

 

 

 

b044

(Forward-regenerating at

0.-200.(%)/no(Invalid) <0.-180.(%)/no(Invalid)>

150.

 

 

 

4 quadrant mode)

 

 

 

 

 

 

b045

Torque LAD-STOP selection

00(Invalid)/01(Valid)

00

 

 

b046

Reverse run prevention

 

00(Invalid)/01(Valid)

00

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b050

Selection of non-stop

 

00(Invalid)/01(Valid)

00

 

 

function at instantaneous

 

 

 

power failure

 

 

 

 

 

 

 

b051

Start voltage of non-stop

0.0-1000.(V)

0.0

 

 

function setting

 

 

 

 

 

 

 

 

 

 

 

b052

OV LAD-STOP level of non-

0.0-1000.(V)

0.0

 

 

stop function setting

 

 

 

 

 

 

 

 

 

 

others

b053

Deceleration

time

of

non-

0.01-99.99/100.0-999.9/1000.-3600.(s)

1.00

 

stop function setting

 

 

 

 

 

 

 

 

 

b054

Deceleration frequency widt h

0.00-10.00(Hz)

0.00

 

The

of non-stop function setting

 

 

 

 

 

b080

AM adjustment

 

 

0. - 255.

180

 

 

b081

FM adjustment

 

 

0. - 255.

60

 

 

b082

Start frequency adjustment

0.10-9.99(Hz)

0.50

 

 

b083

Carrier frequency setting

0.5-15.0(kHz) Derating enable, <0-10kHz>

5.0 <3.0>

 

 

b084

Initialize mode

 

 

00(Trip history clear)/01(Data initialization)/

00

 

 

 

 

02(Trip history clear + data initialization)

 

 

 

 

 

 

 

 

 

 

 

b085

Country code for initialization

00(Interior)/01(EC)/02(USA)

01/02/00

 

 

b086

Frequency scalar conversion

0.1-99.9

1.0

 

 

factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b087

STOP key enable

 

 

00(valid)/01(invalid)

00

 

 

b088

Resume on FRS cancellation

00(0Hz start)/01(Start f-equaling)

00

 

 

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b090

BRD usage ratio

 

 

0.0-100.0(%)

0.0

 

 

b091

Stop mode selection

 

00(deceleration stop)/01(Free-run stop)

00

 

 

b092

Cooling fan control

 

 

00(Always ON)/

00

 

 

 

 

01(ON during run, After power ON, then for 5 minutes on stop is implied.)

 

 

 

 

 

 

 

 

 

 

 

b095

BRD selection

 

 

 

00(invalid)/01(valid<invalid during stop>)/02(valid<valid during stop>)

00

 

 

b096

BRD ON level

 

 

 

330-380/660-760(V)

360/720

 

 

b098

Thermistor selection

 

00(invalid)/01(Positive temperature coefficient enable)/02 (NTC enable)

00

 

 

b099

Thermistor error level

 

0. - 9999. ( ohm)

3000.

 

 

b120

Braking control selection

00(Invalid)/01(valid)

00

 

 

b121

Waiting time

for

releasing

0.00-5.00(s)

0.00

 

 

braking conformation

 

 

 

 

 

 

 

 

 

b122

Waiting time for acceleration

0.00-5.00(s)

0.00

 

 

b123

Waiting time for stop

 

0.00-5.00(s)

0.00

 

 

b124

Waiting

time for

signal

0.00-5.00(s)

0.00

 

 

conformation

 

 

 

 

 

 

 

 

 

 

 

 

 

b125

Releasing frequency

 

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

 

 

 

 

 

 

Rated

 

 

b126

Releasing current

 

 

0.00*rated current-2.00*rated current(A)

current of

 

 

 

 

 

 

 

 

 

inverter

 

 

C091

Debug mode selection

 

00(No display)/01(Display)

00

 

 

C101

UP/DWN selection

 

 

00(No frequency data)/01(Keep frequency data)

00

 

 

C102

Reset selection

 

 

00(Trip cancel during ON)/01(Trip cancel during OFF)/

00

 

 

 

 

02(Valid only during trip<Cancel during ON>)

 

 

 

 

 

 

 

 

 

 

 

C103

Reset f

frequency matching

00(0Hz start)/01(Start f-equaling)

00

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload

advance

notice

 

Inverter

 

 

C111

0.0-2.0*rated current(A)

rated

 

 

level

 

 

 

 

 

 

 

 

 

 

 

 

current

 

 

 

 

 

 

 

 

 

 

 

C121

O zero adjustment

 

 

0.-9999./1000-6553(10000-65530)

Set on

 

 

 

 

forwarding

 

 

 

 

 

 

 

 

 

 

 

C122

OI zero adjustment

 

 

0.-9999./1000-6553(10000-65530)

Set on

 

 

 

 

forwarding

 

 

 

 

 

 

 

 

 

 

 

C123

O2 zero adjustment

 

 

0.-9999./1000-6553(10000-65530)

Set on

 

 

 

 

forwarding

 

 

 

 

 

 

 

 

 

 

(Note) < > indicate the setting range of 75 to 150kW

1- 7

Image 10
Contents Hitachi Inverter Revision History Table Inverter specification Investigation of the inverter Inverter specification 1 SJ300Function Mode Code 2nd motor Signal output mode Others Allowable motor selection 20-75.0kW 160kW User 2 L300P FE/-FU/-FR PID Terminal Meter C083 O2 adjustment 9999./1000-655310000-65530 U006 User6 selection Trouble Shooting Inverter trip contents, remedy, adviceIgbt Digital-input option board SJ-DG Option error Feed-back board SJ-FBDevice- Net option board SJ-DN Check of the trip monitor contents Check of the warning monitor contents Return to an initialization setup Factory-shipment state Debug Mode Monitor modeFunction mode USASetting procedure Setup of an inverterInitial cofiguration completion check procedure Model selection code C198 Code SJ300 L300P Control power supply Control signalMaintenance and Inspection Daily and annual maintenance Megger test How to check inverter & converter portion Parts replacement How to remove cooling fan for steel case How to fix DC bus capacitors for mold case Unit replacement English Internal block diagram SJ300-004-007LF Circuit Diagram SJ300-015 055LF Circuit Diagram SJ300-075-110LF , L300P-110-150LFR Circuit Diagram SJ300-150 220LF , L300P-185 300LFR Circuit Diagram SJ300-300LF, L300P-370LFR Circuit Diagram SJ300-370-450LF, L300P-450-550LFR Circuit Diagram SJ300-550LF,L300P-750LFR Circuit Diagram SJ300-007HF Circuit Diagram SJ300-015-055HF Circuit Diagram SJ300-075-110HF , L300P-110-150HFR Circuit Diagram SJ300-150 220HF , L300P-185 300HFR Circuit Diagram SJ300-300HF , L300P-370HFR Circuit Diagram SJ300-370- 550HF,L300P-450-750HFR Circuit Diagram DM Board SJ300-750-1320HF , L300P-900-1320HFR Circuit Diagram Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page SJ300/L300P Series Spare Parts List SJ3 CT PCB DM PCB NGMB25