Hitachi L300P Series service manual Igbt

Page 20

 

 

 

 

 

 

 

 

 

Digital

 

 

 

Trip

 

 

 

contents

 

operator

Remedy, advice

 

 

 

 

 

 

 

 

 

display

 

 

 

 

 

If Instant power failure 15ms or more happened, INV

 

Instant

power

failure

will shut the output. If the instant power failure is longer

Any incoming AC V drop

than preset allowable time or affordable control supply

detection

 

 

voltage time,

INV will work as normal power

off. This

No contact failure in MCB,Mg?

 

 

means INV will re-start with the run command after the

 

 

 

 

 

 

 

 

 

 

long instant power failure.

 

 

 

 

 

 

 

 

If main circuit temp. was exceeded specific level such

Any cooling fan failure, disturbance of

Over heat detection

as high ambient temp., fan failure, INV will shut the

the cooling such as dusty fin.

output.

 

 

 

 

Installation vertical

 

 

 

 

The temp. is detected at heat sink over 100 Celsius .

Ambient temp. high

Gate

array(INV

domestic

If there was

any communication error between micro

Any big noise near the INV

processor and gate array, or if gate array can’t detect

Any IGBT failure

problem)

 

 

 

 

IGBT’s turn on/off such as IGBT failure.

 

 

Connection of flat cable/ribbon cable

Input

 

phase

failure

If one of incoming 3 phase voltage was missed, INV will

Any missing phase

 

shut the output if the detect function was preset.

detection

 

 

No contact failure in MCB,Mg?

 

 

The detection delay is about 1 sec.

 

 

 

 

 

 

 

 

 

 

 

If instant over current happened between INV and the

Short circuit or earth contact (ground

IGBT

 

over

current

connected motor, INV will shut the output.

 

 

 

fault) in the motor or the motor cable

detection

(equivalent as

Under this INV trip, the detected phase is possible to

Any IGBT failure

refer at d105 display.

 

 

 

 

 

 

Any loose connection on main circuit

power module)

 

Even retry function is preset, INV can not retry after this

 

such as power board

 

 

 

 

detection.

 

 

 

 

 

Thermister(customer’s

If motor over temp. happened by integrated thermistor’s

Check the motor temp.

resistor value in the motor, INV will shut the output.

Any thermistor failure in the motor

selection)

 

 

 

 

After

INV output brake release signal,

INV

couldn’t

Any noise in the thermistor signal

Brake

error (customer’s

Is the brake working ON/OFF

detect

brake

on/off within

b124(waiting

time

for brake

Preset B124 too short

selection)

 

 

operation. (if

b120(brake

control switch) was preset

 

 

Brake signal/connection OK

 

 

“01 ”)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Detection of connected option card 1. For more details,

Make sure the connection of the card

Option board 1 error 0–9

refer to the instruction manual of the card.

-

1 Make sure if the usage is proper

 

 

 

 

 

 

 

 

 

Detection of connected option card 2. For more details,

Make sure the connection of the card

Option boad 2 error 0-9

refer to the instruction manual of the card.

-

2 Make sure if the usage is proper

 

 

 

 

 

 

 

 

 

Stand by condition because of low DC bus voltage such

Any incoming AC V drop

Power off/ waiting from AC

as power off, INV will shut the output.

 

 

No contact failure in MCB,Mg?

The detection level is same as under voltage trip.

Check the DC bus voltage

incoming voltage recovery

 

 

 

 

 

 

Perform above adjustment referring to

 

 

 

 

 

 

d102, so that the DC bus voltage does

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

not exceed the trip level.

2- 2

Image 20
Contents Hitachi Inverter Revision History Table Inverter specification Investigation of the inverter Inverter specification 1 SJ300Function Mode Code 2nd motor Signal output mode Others Allowable motor selection 20-75.0kW 160kW User 2 L300P FE/-FU/-FR PID Terminal Meter C083 O2 adjustment 9999./1000-655310000-65530 U006 User6 selection Trouble Shooting Inverter trip contents, remedy, adviceIgbt Device- Net option board SJ-DN Option error Feed-back board SJ-FBDigital-input option board SJ-DG Check of the trip monitor contents Check of the warning monitor contents Return to an initialization setup Factory-shipment state Debug Mode Monitor modeFunction mode USAInitial cofiguration completion check procedure Setup of an inverterSetting procedure Model selection code C198 Code SJ300 L300P Control power supply Control signalMaintenance and Inspection Daily and annual maintenance Megger test How to check inverter & converter portion Parts replacement How to remove cooling fan for steel case How to fix DC bus capacitors for mold case Unit replacement English Internal block diagram SJ300-004-007LF Circuit Diagram SJ300-015 055LF Circuit Diagram SJ300-075-110LF , L300P-110-150LFR Circuit Diagram SJ300-150 220LF , L300P-185 300LFR Circuit Diagram SJ300-300LF, L300P-370LFR Circuit Diagram SJ300-370-450LF, L300P-450-550LFR Circuit Diagram SJ300-550LF,L300P-750LFR Circuit Diagram SJ300-007HF Circuit Diagram SJ300-015-055HF Circuit Diagram SJ300-075-110HF , L300P-110-150HFR Circuit Diagram SJ300-150 220HF , L300P-185 300HFR Circuit Diagram SJ300-300HF , L300P-370HFR Circuit Diagram SJ300-370- 550HF,L300P-450-750HFR Circuit Diagram DM Board SJ300-750-1320HF , L300P-900-1320HFR Circuit Diagram Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page SJ300/L300P Series Spare Parts List SJ3 CT PCB DM PCB NGMB25