Hitachi L300P Series service manual Debug Mode, Monitor mode

Page 25

3.Debug Mode

Additional displays as follows can be seen by turning Debug mode ON (C091 ->1).

3.1 Monitor mode

No

Functional

Display code

SJ300/L300P A Monitor or data range

 

 

 

 

1

Control frequency monitor

d101

0.00-99.99/100.0-400.0Hz

2

Direct-current voltage monitor

d102

0.0-999.9V

3

BRD on-monitor

d103

0.00-99.99/100.0s

4

Electronic thermal monitor

d104

0.00-99.99/100.0%

5

Gate array trip factor monitor

d105

00-FF

6

MCU No. monitor

d106

0000-9999

d101 ( Output frequency monitor (Hz)): Monitor of the output frequency of the inverter.

d102 ( DC bus voltage monitor (V)): Monitor of the DC bus voltage (VPN) of the inverter.

d103 ( BRD ON monitor (s)): There is an integrated BRD circuit on 11kW and less for SJ300, and 15kW and less for L300P series. You can find accumulated turning ON time for the integrated BRD transistor.

d104 ( Electronic thermal monitor (%)):You can find the usage ratio of electronic thermal performance as %.

d105 (Trip cause monitor of gate array):There are 8 items of trips which are detected by the internal gate array and these items are transmitted to MCU.

Bit7

bit6

Bit5

bit4

bit3

bit2

bit1

bit0

Gate

array IGBT error

IGBT error

Over

Over voltage

Under voltage

IGBT error

Option

error

W phase

V phase

temperature

(E07)

(E09)

U phase

Ground fault

(E21)

 

 

(E14)

(E23)

(E30)

(E30)

 

 

(E30)

 

 

 

 

Contents of d105 are expressed in HEX.

(Example 1) 20

20 (HEX) = 00100000 (BIN)

bit5 = “1” -> IGBT error (V phase)

(Example 1) 62

62 (HEX) = 01100010 (BIN)

bit1, bit5, bit6 = “1 ” -> IGBT error (U, V, W phase)

d106(MCU No monitor): Display the software management number of MCU incorporated.

3- 1

Image 25
Contents Hitachi Inverter Revision History Table Inverter specification Investigation of the inverter 1 SJ300 Inverter specificationFunction Mode Code 2nd motor Signal output mode Others Allowable motor selection 20-75.0kW 160kW User 2 L300P FE/-FU/-FR PID Terminal Meter C083 O2 adjustment 9999./1000-655310000-65530 U006 User6 selection Inverter trip contents, remedy, advice Trouble ShootingIgbt Digital-input option board SJ-DG Option error Feed-back board SJ-FBDevice- Net option board SJ-DN Check of the trip monitor contents Check of the warning monitor contents Return to an initialization setup Factory-shipment state Monitor mode Debug ModeUSA Function modeSetting procedure Setup of an inverterInitial cofiguration completion check procedure Model selection code C198 Code SJ300 L300P Control signal Control power supplyMaintenance and Inspection Daily and annual maintenance Megger test How to check inverter & converter portion Parts replacement How to remove cooling fan for steel case How to fix DC bus capacitors for mold case Unit replacement English Internal block diagram SJ300-004-007LF Circuit Diagram SJ300-015 055LF Circuit Diagram SJ300-075-110LF , L300P-110-150LFR Circuit Diagram SJ300-150 220LF , L300P-185 300LFR Circuit Diagram SJ300-300LF, L300P-370LFR Circuit Diagram SJ300-370-450LF, L300P-450-550LFR Circuit Diagram SJ300-550LF,L300P-750LFR Circuit Diagram SJ300-007HF Circuit Diagram SJ300-015-055HF Circuit Diagram SJ300-075-110HF , L300P-110-150HFR Circuit Diagram SJ300-150 220HF , L300P-185 300HFR Circuit Diagram SJ300-300HF , L300P-370HFR Circuit Diagram SJ300-370- 550HF,L300P-450-750HFR Circuit Diagram DM Board SJ300-750-1320HF , L300P-900-1320HFR Circuit Diagram Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page SJ300/L300P Series Spare Parts List SJ3 CT PCB DM PCB NGMB25